• Nenhum resultado encontrado

CASSETTE-TYPE FAN COIL

N/A
N/A
Protected

Academic year: 2023

Share "CASSETTE-TYPE FAN COIL"

Copied!
84
0
0

Texto

Do not use chemical products or solvents to clean any part of the fan coil unit. Do not spray water on the external or internal surfaces of the fan coil unit (this may cause short circuits). In cooling mode, water vapor may be present in the air supply of the fan coil unit.

Water probe upstream of the valve: the probe measures the temperature of the water in the system. SW4 probe: As an optional extra, a probe can be installed to measure the temperature of the water in the system. With the help of the flanges (accessories), the ducts (for renewal of the ambient air and/or delivery to an adjacent room) can be connected to the sides.

Performance values ​​refer to the following conditions:. at the maximum motor speed;. the total input power is determined by adding the input power for the unit to the input power for the accessories connected and explained in the corresponding manuals. The sound pressure and power levels of the fan coils at the different speeds are shown in the tables.

FCL (Standard)

4-pipe system2-pipe system

FCL (V2)

FCL (Standard) with electric heater 4-pipe system

FCL (V2) with electric heater 4-pipe system

FCL (VL) without valves

RXLE

Only for models and confi gurations

Performance certified EUROVENT 6/3 - Acoustic tests certified EUROVENT 8/2 (ISO 3741/2001)

C] = wet bulb inlet air temperature Ta D.B.[°C] = dry bulb inlet air temperature Pc [w] = total cooling capacity. If significant power values ​​are above the total power, this means that cooling is carried out without dehumidification. To determine the cooling capacity according to the speed (air flow), the values ​​shown in the table must be multiplied by the following factors (k):.

COOLING CAPACITY CORRECTION FACTORS

COOLING CAPACITY CORRECTION FACTORS 5

COOLING CAPACITY CORRECTION FACTORS 11

HEATING CAPACITY CORRECTION FACTORS

FCL 102

FCL 104

FCL 122

FCL 124

Pressure drops [kPa] with water 50°C

Water fl ow rate [l/h] FCL32 FCL36 FCL42 FCL62 FCL72 FCL82 FCL102 FCL122

Pressure drops [kPa] with water 70°C

Water fl ow rate [l/h] FCL34 FCL38 FCL44 FCL64 FCL84 FCL104 FCL124

Pressure drops [kPa] with water 7°C

GLYCOL WATER AT 10%

GLYCOL WATER AT 35%

GLYCOL WATER AT 20%

COOLING FUNCTION MODE HEATING FUNCTION MODE

FCL34

FCL36 FCL38

FCL42 FCL44

FCL62 FCL64

FCL72

FCL82 FCL84

FCL102 FCL104

FCL122 FCL124

SOUND PRESSURE LEVEL expressed in db (a)

Suction and delivery grille units

Standard control panels (electronic and electromechanical)

Intake and delivery grille units with electronic thermostat incorporated for the VMF System

Wall-mounted control panel for the VMF System

Accessories Perimeter casing accessory for ceiling installation

Accessory for air purifi cation

Accessories for air delivery in an adjacent room and for connection to a fresh air intake

Probe accessories for standard control panels (also consult the control panel documentation) SW3**

SWA**

Interface card accessories for standard control panels

Obligatory accessories, essential for unit operation

The GLL, GLL_R and GLL_N range intake and delivery grille units with electric box are compulsory accessories as the FCL units are dispatched without these components (they also include the electrical box for the FCL)

Requires GLL_M, GLL_R or GLL_N

Electric resistor accessories

Accessories for VMF System (FCL with GLL_N grille) Obligatory accessories, essential for unit operation

The individual or network master units are required to be combined with the VMF-E4 / VMF-E4D control panel

The Slave network units do not require the VMF-E4 / VMF-E4D control panel, they simply need to be connected (TTL) to the Master unit

Each network Master unit can have up to 5 Slave units connected to it

The Master network units can be connected to a VMF-E5B or VMF-E5N main interface panel to manage the system

VMF System control panel accessory (connected to the individual units or only to the Master units)

M ain interface panel Accessory to manage the VMF System network (connected to the Master units)

Accessory water temperature probe for a 2-pipe system

Accessories water temperature probes for a 4-pipe system

GLL10 (600x600) GLL20 (840x840)

Intake and delivery grille unit (obligatory accessory)

GLL10 - GLLI20 INTAKE AND DELIVERY GRILLE UNITunits are compulsory accessories as the

GLL10M INTAKE AND DELIVERY GRILLE UNIT WITH MOTORISED FINS GLL10M (600x600)

Intake and delivery grille unit with motorised fins and remote control (obligatory accessory)

GLL10R (600x600) GLL20R (840x840)

GLL10R - GLL20R INTAKE AND DELIVERY GRILLE UNIT

The GLL_N accessory consists of

GLL10N (600x600) GLL20N (840x840)

Intake and delivery grille unit with "VMF System" advanced electronic thermostat (obligatory accessory)

FCLMC10

FCLMC20

FCLMC SUCTION FLANGE

FCLMC10 FCLMC20

KFLD

KFL20 (***)

KFLD SUCTION FLANGE

KFL20

KFLD20

KFLD20 (***)

VHL2 - VHL22

Obligatory accessory for 4-pipe systems with variable flow rates

VHL2 - VHL22 2-WAY VALVES KIT

VHL1 - VHL20

Obligatory accessory for 4-pipe systems

SIT3

SIT3 - SIT5 INTERFACE CARDS

The electronic control panels or those with valve control must be interfaced with a SIT 5

The electromechanical control panels with just the speed control can be fitted directly to the SIT 3 without the SIT 5

RXLE RXLE20

This accessory can only be used with the FCL models fitted with GLL_M, GLL_R or GLL_N range grilles

SW4 WATER TEMPERATURE PROBE FOR

2-PIPE SYSTEMS

HOT WATER CIRCUIT IN 4-PIPE SYSTEMS SW4

SW3 MINIMUM WATER TEMPERATURE SENSOR

SWA MINIMUM WATER AND AIR TEMPERATURE PROBE

Wired control panel, user interface for thermostats built into GLL10N and GLL20N grid units, and for all other VMF thermostats. Supervisor-controlled operation mode (VMF-E5B / VMF-E5N) See the accessories manual for full information on this.

VMF-E4 / VMF-E4D

FCL + GLL10N FCL + GLL20N

VMF-E4

PANTONE COOL GRAY 1C

VMF-E4D

PANTONE 425C (METAL)

FCL+GLL_N

WARNING: The VMF-E5B / VMF-E5N panel allows management of the individual masters; The slave units connected to each master cannot be managed individually from the VMF-E5B / VMF-E5N panel, but they get the settings from the master they are connected to. Heat recovery units: Allow up to 3 per programmable recovery units based on timing and/or by metering.

See the accessories manual for complete information on its features

The most important feature is the possibility to manage the plant by means of dedicated algorithms to achieve a comfortable environment with energy saving in mind. Thermostat for fan coils installed in systems with 4 pipes, 2 pipes and 2 pipes with heater, with the possibility of connecting two On - Off valves to shut off the water feeding the coils.

See the accessories manual for complete information on its features

WMT10 CONTROL PANEL WITH ELECTROMECHANICAL THERMOSTAT

PX: control panel with selector

PX CONTROL PANEL WITH SPEED SELECTOR

ATTENTION: before carrying out any work, wear the appropriate individual

ATTENTION: The appliance must be installed in compliance with national

ATTENTION: the electric connections, the installation of the fan coils and

In particular, for the electric connec- tions, checks relative to the following

Measurement of the electric plant iso- lation resistance

Continuity test of the protection wires

ATTENTION: Install a device, master switch or electric plug that allows to

Do not install at height of above three metres

2-pipe system with resistance (Only for models and confi gu-

4-pipe system with resistance (Only for models and confi gu-

SYSTEM EXAMPLES

Choose where to install the machine according to the layout of the room, the number of units to be installed and any constraints imposed by the architecture. Remove the box, it is recommended to cut the corners of the box and remove the cardboard one by one. Operate the nut to adjust the height, finally check that the unit is installed in a horizontal position.

Run the hydraulic lines through the suspended ceiling to the mounting plate on the unit;. Vent the system, the vent valve for the two-pipe circuit is located externally on the connection plate. The vent valve for the heating circuit of the 4-pipe system is internal, remove the polystyrene tray to access it.

Instructions for mounting and connecting the electrical cabinet are in the manual that comes with the network accessories. After you have completed the connections and the electrical box is inserted into the housing in the FCL unit, secure it with two screws. ATTENTION: attach the safety cable to the screw terminal of the electrical box, which is located on the side of the hydraulic connections.

For GLL10M and GLL10R only: apply any air probe (SA) to the center of the fan grill, secure the cable with the supplied ties, lay the excess cable in the grooves made in the polystyrene. The grill frame should be positioned so that the AERMEC logo holder matches the corner of the electrical box. For GLL10M and GLL10R only: make the connections between the electrical box and the receiver.

Using the nuts, adjust the position of the unit against the support bracket so that the unit is level and the frame rests slightly on the suspended ceiling.

INSTALLATION IN PROXIMITY OF A WALL

Do not handle the unit using the hydraulic connections but use the

ATTENTION!! tighten the screws with maximum coupling torque

ATTENTION: fix a safety cable snap hook must then be attached to the grid

Disassembly for maintenance - Before performing any operation on

Electric box maintenance

In the 4-pipe version of the unit, it is mandatory to install the hot water coil valve accessory. For this purpose use the gaskets provided, the accessory has gaskets for connection to the system. Flow and return pipes must be equal, dimensioned and suitably insulated to avoid heat dissipation and dripping during operation in cooling mode.

CONDENSATE DRAIN CONNECTIONS During functioning in cooling mode the

The draining hole must always be closed again using the rubber cap

The electrical supply to the pump-float device must never be interrupted

SC = Condensate drain (male Ø 16mm)

CONNECTIONS FOR THE INTAKE OF EXTERNAL FRESH AIR

CONNECTION FOR THE AIR FLOW CONDITIONED IN AN ADJOINING ROOM

4) out(2) out

4) out (2) out

4) in Air out

The fan coils of the FCL cassette must be powered by 230V ~ 50Hz power and have a ground connection. The mains voltage must remain within the tolerance of ±10% in relation to the nominal value. The electrical power supply cable must be type H07 V-K or N07 V-K with 450/750V insulation if inside a pipe or raceway.

GLL10 GLL20

GLL10M - GLL10R - GLL20R - GLL10N - GLL20N

GLL10N - GLL20N

INSTALACIÓN Y SUSTITUCIÓN DEL FILTRO "Módul 600"

PERICOLO: Togliere tensione prima d’iniziare le operazioni di pulizia del filtro e/o dell’unità

DANGER: Switch off power supply before cleaning filter and/or unit

DANGER: Couper la tension avant de commencer les opérations de nettoyage du filtre et/ou de l'unité

GEFAHR: Vor der Reinigung des Filters und/oder des Gerätes die Strom versorgung abschalten

PELIGRO: Quitar la tensión antes de iniciar las operaciones de limpieza del filtro o de la unidad

PELIGRO: Apague la alimentación antes de comenzar a limpiar el filtro o la unidad.

INSTALACIÓN Y SUSTITUCIÓN DEL FILTRO "Módul 840"

KFLDKFL

FCL 36

IN OUT

IN OUT OUT

KFLD20 KFL20

FCL 102

Die Schaltpläne werden ständig aktualisiert, daher sollten Sie sich immer an dem Schaltplan orientieren, der dem Gerät beiliegt. AMP=Contatto alarme pump ràjo condensa Contact alarm entladung der kondensat pumpe Contact d'alarme de decharge de pompe. M = Morsettiera • Anschlussplatte Boitier • Anschlussplatte Placa de bornes DM = Motore aletta Louvre motor Moteur defl eteur Motorklappe Lamas motorizadas MP = Pompa ràjo condensa.

GND Erdungsanschluss Mise à terre Erdungsanschluss Toma de tierra RE = Resistenza elettrica RXLE Elektroheizung Resistance électrique Elt. Heizregister Resistencia eléctrica SA = Raumfühler Raumfühler Raumfühler Raumfühler Raumtemperaturfühler Raumfühler SC = Steuerungsschema. Die Schaltpläne werden ständig aktualisiert. Beachten Sie daher immer den dem Gerät beiliegenden Schaltplan.

GLL10 / GLL20

VHL1 / VHL2 + VHL20 / VHL22

RXLEGLL10M

VHL1 / VHL2 + RXLE

RXLEGLL10R / GLL20R

WMT10 + VHL1 / VHL2

PXAE

FMT10

GLL10 /GLL20

MARO

GLL10N / GLL20N

FCL_VL

SA LED

PXAE SIT3

AERMEC S.p.A

Imagem

Graphic back-lit LCD display and  capacitive keyboard.

Referências

Documentos relacionados