Ground source heat pump

N/A
N/A
Protected

Academic year: 2023

Share "Ground source heat pump"

Copied!
80
0
0

Texto

Improper installation may cause explosion, personal injury, water leakage, refrigerant leakage, electric shock and fire. If the density of the coolant exceeds the limit, in case of any leakage, oxygen deficiency may occur, which may cause serious accidents. Improper installation locations may cause the unit to fall and cause property damage and personal injury.

This can cause extremely high pressure in the process circuit, which can cause explosions and personal injury. Touching rotating equipment, hot surfaces, or high-voltage parts may cause personal injury due to entrapment, burns, or electric shock. Failure to disconnect the power may cause electric shock, damage, and malfunction of the device.

Connecting the unit with copper wire or other metal wire may cause damage to the unit and fire. Any remaining packing material may cause personal injury as it may contain nails and wood.

Pipe connections

HVAC components

Sensors etc

Electrical components

Miscellaneous

Electrical cabinets

Cooling section

Cooling components

General

Symbol key

System diagram

4 Pipe connections

Dimensions and pipe connec- tions

Pipe dimensions

Brine side

Collector

Connecting the brine side

Connecting external brine pump (40 and 60kW only)

Expansion vessel

Heating medium side

Connecting the climate system

Hot water heater

Connecting the hot water heater

Fixed condensing

Docking alternatives

Explanation

The heat pump (EB100) prioritizes the charging of hot water with half the power (cooling module EP14) via a reversing valve (QN10). When the water heater/accumulator tank (CP10) is fully charged (EB100-QN10) switches to the heating circuit. Additional heat (EB1) is automatically connected when the energy demand exceeds the heat pump capacity.

The heat pump (EB100) prioritizes the charging of hot water with half the power (cooling module EP14) via a reversing valve (EB100-QN10). When the water heater/accumulator tank (CP10 and CP11) is fully charged (EB100-QN10) switches to the heating circuit. Additional heat (EM1) is automatically connected when the energy demand exceeds the heat pump capacity.

If the water heater/accumulator tank (CP10) is equipped with an immersion heater and a junction box, the function. For 40 and 60 kW the brine pump is supplied (not valid for all locations, see list of supplied items) and must be installed outside the heat pump.

Miniature circuit-breaker

All electrical equipment, except the outdoor sensors, room sensors and current sensors, are already connected in the factory. ႑ If the building is equipped with an earth leakage circuit breaker, each F1345 must be fitted with a separate one. ႑ Communication and sensor cables to external connections must not be laid near power cables.

႑ The minimum area of ​​communication and sensor cables for external connections must be 0.5 mm² up to 50 m, for example EKKX or LiYY or equivalent. ႑ For cable routing in F1345, cable glands must be used (e.g. UB2, power cables and UB3, signal cables, marked in the picture). Electrical installation and service must be carried out under the supervision of a qualified electrician.

Electrical installation and wiring must be carried out in accordance with the applicable regulations.

Motor cut-out

5 Electrical connections

Cable lock

Connections

Power connection

Tariff control

Connecting external operating voltage for the control system

Outside sensor

Temperature sensor, hot water charging The temperature sensor, hot water charging (BT6) is

Temperature sensor, hot water top

Temperature sensor, external flow line Connect temperature sensor, external flow (BT25) to

Temperature sensor, external return line Connect temperature sensor, external return line (BT71)

Optional connections

Master/Slave

Load monitor

Room sensor

Step controlled additional heat

Relay output for emergency mode

Reversing valves

NIBE Uplink™

External connection options

Possible selection for AUX inputs

႑ Switch for external blocking of additional heat In cases where external blocking of additional heat is desired, it can be connected to connection block X6, which is installed behind the front cover. Additional heating is disconnected by connecting the potential-free switch function to the input selected in menu 5.4. In these cases, an external compressor lockout (EP14) and/or (EP15) is required, this can be connected to terminal block X6, located behind the front cover.

The compressor (EP14) and/or (EP15) is disconnected by connecting a potential-free switch function to the input selected in menu 5.4. In those cases where external rate blocking is desired, it can be connected to terminal block X6, which is placed behind the front cover. ႑ Switch for external blocking of heating In those cases external blocking of heat is used, it can be connected to terminal block X6, which is placed behind the cover.

Heating is switched off by connecting a potential-free switch function to the input selected in menu 5.4. ႑ Contact for external forced control of the brine pump In cases where external forced control of the brine pump is used, this can be connected to terminal block X6, which is located behind the front cover. The brine pump can be forcibly controlled by connecting a potential-free contact function to the input selected in menu 5.4.

An external contact function can be connected to F1345 for activation of the "temporary luxury" hot water function. The switch must be potential free and connected to the selected input (menu 5.4) on terminal block X6, which is behind An external contact function can be connected to F1345 to change the flow temperature and the room temperature.

The contact must be potential-free and connected to the selected input (menu 5.4) on terminal X6. An external switch function can be connected to F1345 for activation of one of the four fan speeds. If a pressure/level/flow monitor is desired for the coolant installation, it can be connected to the selected input (menu 5.4) on terminal block X6 located behind the front cover).

Possible selection for AUX output (potential free variable relay)

Tariff blocking means that supplemental heat, compressor and heat are disconnected by connecting a potential-free contact function to the input selected in menu 5.4. The external contact function only works if the accessory FLM is installed and activated. If any of the above is installed on terminal X5, it must be selected in menu 5.4.

An accessory card is required if several functions are connected to terminal block X5 while the buzzer alarm is activated (see page 37). External circulation pump, ground water pump or hot water circulation pump connected to the buzzer alarm relay as shown below.

Connecting accessories

Preparations

Filling and venting

Filling and venting the climate system

Filling and venting the brine system

6 Commissioning and adjusting

Start guide

Commissioning

Operation in the start guide

Post adjustment and venting

Pump capacity diagrams, collector side To set the correct flow in the brine system the correct

Pump capacity diagrams, heating medium side

Readjusting, venting, heat medium side Air is initially released from the hot water and venting

Readjusting, venting, collector side

Post adjusting the room temperat- ure

Accessory card AXC 50

Air module, collector AMB 30 Part no. 065 046

Auxiliary relay HR 10 Part no. 089 423

Buffer vessel UKV

Communications module MODBUS 40 MODBUS 40 enables F1345 to be controlled and mon-

Communications module SMS 40

Connection box K11

Exhaust air module FLM

External electrical addition ELK

Extra shunt group ECS 40/ECS 41

Filling valve kit KB 32

Hot water control

7 Accessories

Room sensor RTS 40 Part no. 067 065

Room unit RMU 40

Dimensions and setting-out coordinates

8 Technical data

Technical specifications IP 21

IP class

C Average heating temperature max/min. kg Heat pump with full weight .. kg Cooling module with weight only. 1) Max. permissible impedance at the point connected to the network, in accordance with EN Inrush currents can cause short voltage drops that can affect other devices under unfavorable conditions. If the impedance at the network connection point is higher than that stated, it is possible that interference will occur.

If the impedance at the mains connection point is higher than that stated, check with the power supplier before purchasing the device.

Working range heat pump, compressor oper- ation

Wiring diagram, 3x400V 24 kW

Wiring diagram, 3x400V 30 kW

Wiring diagram, 3x400V 40 and 60 kW

Item register

9 Item register

Room temperature readjustment, 36 Pump capacity diagrams, collector side, 32 Pump capacity diagrams, heating system side, 34 Readjustment, venting, heating system side, 36 Power connection, 22. Switch for external blocking of additional heat, 28 Switch for external blocking of heating, 28 Switch for external forced control of brine pump, 28 Symbol key, 13, 30. Heat pump working range, 42 Temperature sensor, cooling/heating, 27 Temperature sensor, external supply line, 23 Temperature sensor, hot water charging , 23 Temperature sensor, hot water top, 23 The design of the heat pump, 8.