HEAT RECOVERY UNITS. UR
GB
General rules 4
Operating principle 5
Nominal technical data 6
Identification of the unit 8
Description of the unit 9
Accessories 11
Accessory compatibility charts 12
Vent positioning 13
Free cooling operation 14
Approximate dimensions and weights 15
Fan characteristic curves 17
Heat recovery unit performance curves 24
Water type heating coild yield curves 26
Pressure drop curves 29
Electric coil yield tables 31
Cooling coil capacity tables 32
Direct expansion coils 39
Noise data 53
Installation and maintenance manual 54
Main condition of warranty 54
General considerations 54
Description of icons 55
General safety rules 55
Unit identification 56
Handling 56
Packing 56
Transport 56
Checks at material receipt 57
Stocking at site 57
Installation 57
Sizes 58
Technical spaces 63
Inside components positioning and vent opening 63
Positioning of the support brackets 64
Unit lifting and positioning 65
Coil module and silencer assembly 66
Aeraulic connections 66
Hydraulic connections 67
Water coil connections 67
Correspondence valve-battery 68
Electrical wiring 68
First start-up checks 74
Usage TFD accessory 75
Unit maintenance 76
Decommissioning of the unit 77
Diagnosis and Troubleshooting 78
General rules
The present manual is an integral part of the docu- mentation enclosed with the machine.
It must be conserved for future reference and must accompany the machine throughout its working life.
The manual defines the purpose for which the machine was built and establishes the correct installation and use limits.
• All use, installation and maintenance instructions of the unit are described in this manual as well as the main accident prevention standards.
• Read carefully and fully all informa- tion contained in this manual before the installation, start-up, use, main- tenance and cleaning of the unit. Pay particular attention to the use regu- lations accompanied by the words
“DANGER” or “WARNING”: failure to observe them could cause damage to the machine and/or persons and pro- perty.
• For irregularities not contemplated by this manual, consult the local After Sales Service.
• AERMEC S.p.A. decline any respon- sibility for any damage due to the improper use of the machine, and to a partial or superficial reading of the information contained in this manual.
• Installation and maintenance must be carried out by trained and qualified personnel, having the requirements laid down by law 46/90 and/or DPR 380/2001 for electric/electronic and air conditioning installations, with consequent registration at the local CHAMBER of COMMERCE. Otherwise AERMEC S.p.A. decline all responsibili- ty regarding the safety of the product.
THE MANUFACTURER DECLINES ANY RESPONSIBILITY FOR DAMAGE TO PROPERTY, PERSONS OR ANIMALS CAUSED BY THE NON-OBSERVANCE OF THE INDICATIONS AND REGULATIONS CONTAINED IN THIS MANUAL.
Even though a suitable risk analysis was carried out during the design of the UR unit, pay ATTENTION to the pictograms on the machine; these make it easier to read the manual, quickly drawing the reader’s attention to risks that cannot be avoided or sufficiently limited with the adoption of protection means and measures.
GENERAL DANGER SIGNS
Carefully observe all indications at the side of the pictogram.
The non observance of the indications could cause hazardous conditions with possible injury to the operator and to the user in general.
VOLTAGE DANGER SIGN
Carefully observe all indications at the side of the pictogram.
The signs indicate components on the unit or, in the present manual, identify areas that could generate risks of an electrical nature.
GENERAL WARNING SIGNS
Carefully observe all indications to the side of the pictogram that limit some actions in order to ensure grea- ter safety for the operator.
M A I N G U A R A N T E E CONDITIONS
• The guarantee does not include pay- ment for damages due to incorrect installation by the installer.
• The guarantee does not include pay- ment for damages due to the improper use of the unit by the user.
• The manufacture is not responsible for injuries to the installer or user, caused by incorrect installation or improper use of the unit;
• The equipment must be installed in
nance and/or repair operations;
• The guarantee does not cover in any case costs due to turntable ladders, scaffolding or other similar elevating systems that are necessary to carry out operations under guarantee.
The guarantee is not valid if:
• the services and repairs have been carried out by unauthorised personnel or companies;
• the unit has been previously repaired or modified with non-original parts;
• the unit has not been suitably maintai- ned;
• the instructions given in this manual have not been observed;
• unauthorised modifications have been made.
NB:
the manufacturer reserves the right to carry out modifications at any time dee- med necessary to improve its product, and is not obliged to apply the said modifica- tions to previously manufactured machi- nes that have already been delivered or are being constructed.
The general conditions are in any case subject to the general sale conditions foreseen on the stipulation of the con- tract.
Operating principle
The UR series brings together the ventilation, filtering and recovery sections into a single unit that also permits connection with various accessories for meeting the specific levels of comfort each environment requires.
Environmental comfort is provided by the extraction of stale air from the room and the simultaneous replacement of new air from the outside. The air is filtered adequately by means of filters on both supply and recovery. Energy recovery is pro- vided by an efficient recovery unit with aluminium plates that makes it possible to save more than 50% of the energy in winter that would otherwise be lost through the expulsion of stale air.
The careful design of the product has made it possible to reduce the dimensions and thereby make it extremely easy to install in suspended ceilings or in cramped areas, improving, among other things, the accessibility for the maintenance of all the machine components, as well.
The range consisting of seven models (with rated air flow rates of 350 m3/h to 3300 m3/h), available in both vertical and horizontal versions
ESTERNO
OUTDOOR INTERNO
INDOOR
BATTERIA FREDDA COOLING COIL BATTERIA CALDA
HEATING COIL BATTERIA DI POST RISCALDAMENTO
RE - HEATING COIL
HEATING COIL COOLING COIL RE-HEATING COIL
E X P U L S I O N FAN
SUPPLY FAN
FILTERS
Nominal technical data
UR MODEL 35 55 75 100 150 210 330
Nominal air flow m3/h 350 550 750 1000 1500 2100 3300
Available static pressure (for
URxxB and URxxVB) (*) Pa 125 140 170 150 120 120 150
Nominal air flow 35 55 75 100 150 210 330
Available static pressure (for
URxxB and URxxVB) (*) % 52,1 55,0 54,3 54,4 53,1 52,7 52,0
Recovered thermal power (**) kW 1,5 2,5 3,4 4,6 6,7 9,3 14,3
Recovered cooling capacity
(***) kW 0,4 0,7 1 1,3 1,9 2,6 4,3
Motor ventilating assembly 35 55 75 100 150 210 330
Number of fans n° 2 2 2 2 2 2 4
Total maximum input power kW 0,15 0,35 0,35 1,12 1,12 2 4
Power supply (voltage/[pha- ses/frequency)
V/Ph/
Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Maximum input power A 0,66 1,55 1,55 5 5 8,6 17,2
Electrical protection IP 44 44 44 55 55 55 55
Insulation class F F F F F F F
Filters 35 55 75 100 150 210 330
Classification according to
EN779 G3 G3 G3 G3 G3 G3 G3
Efficiency % 80 80 80 80 80 80 80
Inside water heating coil
(URxxA) 35 55 75 100 150 210 330
Rows n° 3 3 3 3 3 3 3
Fin Pitch mm 1,8 1,8 1,8 1,8 1,8 1,8 2,1
Face area m2 0,027 0,047 0,052 0,092 0,119 0,165 0,237
Air side pressure drop Pa 105 86 123 74 97 99 102
Thermal power (aria ing. 8°C;
acqua 80/70°C) kW 4,9 8,1 10,6 15,5 22,4 31 43
Thermal power (aria ing. 8°C;
acqua 70/60°C) kW 4,1 6,7 8,8 13 18,7 25,9 36,6
Thermal power (aria ing. 8°C;
acqua 45/40°C) kW 2,4 4 5,2 7,7 11,2 15,4 22
Inside electric heating coil
(URxxE) 35 55 75 100 150 210 330
Thermal power kW 2,5 2,5 5,0 5,0 10,0 15,0 25,0
Air side pressure drop Pa 10 10 10 10 10 10 10
Power supply(voltage/[phases/
frequency) V/Ph/
Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
Stages n° 2 2 2 2 3 3 3
Absorption A 4,6 4,6 9,1 9,1 15,2 22,7 37,9
Water-cooling coil (BF Module) 35 55 75 100 150 210 330
Rows n° 4 4 4 4 4 4 4
Fin pitch mm 2,5 2,5 2,5 2,5 2,5 2,5 2,5
Face area m2 0,075 0,075 0,113 0,213 0,213 0,25 0,325
Air side pressure drop Pa 22 52 43 23 48 66 93
Cooling power (input air
30°C,RH 60%; water 7/12°C) kW 3,4 4,9 6,5 10,2 13,8 18,5 28
Direct expansion cooling coil
in R407C (modulo BFD) 35 55 75 100 150 210 330
Rows n° 4 4 4 4 4 4 4
Fin pitch mm 2,5 2,5 2,5 2,5 2,5 2,5 2,5
Face area m2 0,075 0,075 0,113 0,213 0,213 0,25 0,325
Air side pressure drop Pa 22 52 43 23 48 66 105
Cooling power (input air
30°C,RH 60%;Tev/Tcon 5/47°C) kW 3,8 5,1 7,2 10,9 14,8 19,2 27
Direct expansion cooling coil
in R410A (modulo BFDR) 35 55 75 100 150 210 330
Rows n° 4 4 4 4 4 4 4
Fin pitch mm 2,5 2,5 2,5 2,5 2,5 2,5 2,5
Face area m2 0,075 0,075 0,113 0,213 0,213 0,25 0,325
Air side pressure drop Pa 22 52 43 23 48 66 105
C o o l i n g p o w e r ( i n p u t air.30°C,UR 60%;Tev/Tcon 9/47°C)
kW 3,4 4,2 6,4 9,8 12,5 16,2 23,3
Water-reheating coil (MPW,
BFDW module) 35 55 75 100 150 210 330
Rows n° 1 1 1 1 1 1 1
Fin pitch mm 2,5 1,8 1,8 2,1 2,1 2,1 2,1
Face area m2 0,05 0,05 0,068 0,128 0,128 0,15 0,195
Air side pressure drop Pa 6 17 18 8 17 23 32
Heating power (input air
17°C,RH 90%; water 80/70°C) kW 1,9 3 4,2 5,9 7,1 9,1 12,7
Thermal power (input air
17°C,RH 90%; water 70/60°C) kW 1,5 2,4 3,4 4,8 5,7 7,4 10,2
Thermal power (input air
17°C,RH 90%; water 45/40°C) kW 0,8 1,2 1,7 2,5 3 3,8 5,2
Electric-reheating coil (MPX,
BFDX module) 35 55 75 100 150 210 330
Thermal power kW 1,5 2 3 4 6 8 13
Air side pressure drop Pa 10 10 10 10 10 10 10
Power supply (voltage/[pha-
ses/frequency) V/Ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
Stages n° 2 2 2 2 3 3 3
Absorption A 2,3 3 4,6 5,3 9,1 12,1 19,7
(*) At full motor speed with a stretch of channelling at least 1 m long for supply and with clean filters.
(**) Performance referring to: renewal air flow rate equal to the expulsion air flow rate; external air temperature on input -5° C, 80% RH; room air temperature 20° C, 50% RH.
(***) Performance referring to: renewal air flow rate equal to the expulsion air flow rate; external air temperature on input 34° C, 50% RH; room air temperature 26° C, 50% RH.
Identification of the unit
UR XX X X
SIZE
35, 55, 75, 100, 150, 210, 330 CONFIGURATIONS
NONE: HORIZONTAL V: VERTICAL
VERSIONS B: BASIC
A: INTERNAL WATER-HEATING COIL
E: INTERNAL ELECTRICAL-
HEATING COIL
Description of the unit
H O R I Z O N T A L CONFIGURATION (version URxxB)
Structure
The structure consists of self-bearing sandwich panels 20 mm thick made of galvanised steel plate with insulation formed by injected polyurethane (den- sity 40 kg/m3). The steel sheet is fit- ted with pre-shearing near the opening for the aeraulic connections (in such a way as to permit the motorfan assem- blies to be oriented in different ways), and near the exits of the manifolds of any water-heating coil (URxxA version) for plumbing connections.
Inspection capacity
It is possible from below (ceiling installation) by easily dismantling the panels.
Supply and intake motor- fan assembly
The forward-curved centrifugal fans are double inlet directly coupled to electric motors. Electric motors are single speed UR for sizes 100, 150, 210, 330 while four-speed for sizes 35, 55 and 75. The fans are aspiring for the recovery to ensure maximum uni- formity of flow on the recovery itself, and hence the maximum yield.
Filters
These are cell type with an undulating septum positioned before the recovery unit on airflow deliver and return. The standard filters are class G3 type in accordance with classification UNI EN 779 with weighted efficiency of 80%.
They are 48 mm thick and are easily unthreaded for cleaning and replace- ment.
Heat recovery unit
This is static with crossover flows made of aluminium sheets. During winter operation, the average efficiency is above 50% ensuring first-class energy recovery from the air expelled from the room.
Condensate collection tank
This is made of galvanised steel and positioned under the heat recovery unit and under any water or electric coils supplied as accessories. It is easy to dismantle because of the rubber fitting lining the threaded discharge tubing with a diameter of ½” G UNI 338 positioned near the sidewall of the unit.
Support brackets
these allow rapid and secure fitting to the ceiling or the floor.
H O R I Z O N T A L CONFIGURATION (version URxxA)
In addition to all the previous there are also those features:
Water-type heating coils
In three rows with copper pipes, alu- minium fins positioned downline from the heat recovery unit on the fresh air flow. The manifolds are fitted with threaded female attachments for the water to enter and exit. Sleeves with 1” G UNI 338 threaded attachment and bleed valve are supplied as standard.
H O R I Z O N T A L CONFIGURATION (version URxxE)
In addition to all the previous there are also those features:
Electric heating coil
Made with reinforced finned coils with two or three stages according to the size positioned down line from the heat recovery unit on the fresh air flow. The coil is fitted with a safety thermostat with manual resetting.
V E R T I C A L CONFIGURATION (version URxxVB)
Structure
The structure consists of self-bearing sandwich panels 20 mm thick made of galvanised steel plate with insula- tion formed by injected polyurethane (density 40 kg/m3). The steel sheet is fitted with pre-shearing near the ope- ning for the aeraulic connections (in such a way as to permit the motorfan assemblies to be oriented in different ways), and near the exits of the mani- folds of any water heating coil (URxxVA version) for plumbing connections. The structure has feet and two tanks for condensate collection, one positio- ned near the heat recovery unity and one near the motor extractor fan unit.
Any condensate in the last tank is led directed into the lower tank through a flexible rubber tube.
Inspection capacity
It is guaranteed by easily dismantling the panels.
Supply and supply motor- fan assembly
The forward-curved centrifugal fans are double inlet directly coupled to electric motors. Electric motors are single speed UR for sizes 100, 150, 210, 33 while four-speed for sizes 35, 55 and 75. The fans are aspiring for the recovery to ensure maximum uni- formity of flow on the recovery itself, and hence the maximum yield.
Filters
These are cell type with an undulating septum positioned before the recovery unit on airflow deliver and return. The standard filters are class G3 type in accordance with classification UNI EN 779 with weighted efficiency of ’80%.
They are 48 mm thick and are easily unthreaded for cleaning and replace-
Heat recovery unit
This is static with crossover flows made of aluminium sheets. During winter operation, the average efficiency is above 50% ensuring first-class energy recovery from the air expelled from the room.
Condensate collection tanks
These are made of galvanised steel and are positioned under the heat recovery unit and under the motor extractor fan assembly . The condensate collection tank that leads to the outside if fitted with a ½” G UNI 338 threaded dischar- ge.
Support brackets
These permit rapid and secure fixing of the wall unit.
V E R T I C A L CONFIGURATION (version URxxVA)
In addition to all the previous there are also those features:
Water-type heating coils
Made in three rows with copper pipes, aluminium fins positioned downline from the heat recovery unit on the fresh air flow. The manifolds are fitted with threaded female attachments for the entry and exit of the water, slee- ves with 1” G UNI 338 threaded attach- ment and bleed valve. Both of these components come as standard.
V E R T I C A L CONFIGURATION (version URxxVE)
In addition to all the previous there are also those features:
Electric heating coil
Made with reinforced finned coils with two or three stages according to the size positioned down line from the heat recovery unit on the fresh air flow. The coil is fitted with a safety thermostat with manual resetting.
Accessories
BF Water cold coil module
This is an outside module that can be installed downline from the motor fan assembly on the fresh air flow, fitted with:
Water-cooling coil on four rows with copper pipes and aluminium fins and a tank for collecting condensate with threaded diameter ½” G UNI 338 drai- nage pipe.
The manifolds are fitted with threaded female attachments for the water to enter and exit. Sleeves with 1” G UNI 338 threaded attachment and bleed valve are supplied as standard.
MPW Water cold coil and water re hea- ting module
This is an outside module that can be installed downline from the motor fan assembly on the fresh air flow, fitted with a water-cooling coil with four rows with copper piping and aluminium fins.
The manifolds are fitted with threaded female attachments for the water to enter and exit. Sleeves with 1” G UNI 338 threaded attachment and bleed valve are supplied as standard.
There is also a water-reheating coil with two rows with copper piping and aluminium fins. The manifolds are fit- ted with threaded female attachments for the water to enter and exit. Sleeves with 1” G UNI 338 threaded attach- ment and bleed valve are supplied as standard.
The condensate collection tank in gal- vanised steel with threaded drainage pipe with diameter ½” G UNI 338.
MPX Water cold coil and electric re heating module
This is an outside module that can be installed downline from the motor fan assembly on the fresh air flow, fitted with water-cooling coil with four rows with copper piping and aluminium fins.
The manifolds are fitted with threaded female attachments for the water to enter and exit. Sleeves with 1” G UNI 338 threaded attachment and bleed valve are supplied as standard.
There is also an electric reheating coil
with reinforced finned coils with two or three stages according to the size posi- tioned downline from the heat recove- ry unit on the fresh air flow fitted with a safety thermostat that can be reset manually.
A condensate collection tank in gal- vanised steel with threaded drainage pipe with diameter ½” G UNI 338.
BFD Direct expansion cold coil module in R407C
This is an outside module that can be installed downline from the motor fan assembly on the fresh air flow, fitted with a direct expansion cooling coil with R407C refrigerant with four rows with copper piping and aluminium fins.
The condensate collection tank in gal- vanised steel with threaded drainage pipe with diameter ½” G UNI 338.
BFDR Direct expansion cold coil module in R410A
This is an outside module that can be installed downline from the motor fan assembly on the fresh air flow, fitted with a direct expansion cooling coil with R407C refrigerant with four rows with copper piping and aluminium fins.
The condensate collection tank in gal- vanised steel with threaded drainage pipe with diameter ½” G UNI 338.
BFDW Module with direct expansion R407C type cold coil and water re hea- ting
This is an outside module that can be installed downline from the motor fan assembly on the fresh air flow, fitted with a direct expansion cooling coil with R407C refrigerant with four rows with copper piping and aluminium fins.
There is also a water-reheating coil with two rows with copper piping and aluminium fins. The manifolds are fit- ted with threaded female attachments for the water to enter and exit. Sleeves with 1” G UNI 338 threaded attach- ment and bleed valve are supplied as standard.
The condensate collection tank in gal- vanised steel with threaded drainage pipe with diameter ½” G UNI 338.
BFDX Module with direct expansion R407C type cold coil and electric re heating
This is an outside module that can be installed downline from the motor fan assembly on the fresh air flow, fitted with a Direct expansion cooling coil with R407C refrigerant with four rows with copper piping and aluminium fins.
G4 G4 efficiency filters
The units can be fitted with two cell- type filters with undulated septum in class G4 according to the UNI EN 779 classification (weighted efficiency of 90%) that can be positioned as a repla- cement of those in class G3. The filte- ring cell is 48 mm thick.
SU Silencers
An accessory only available for the horizontal configuration.
There are two modules that can be installed on the side turned towards the room fitted with silencer septums made of rock wool panels with surfaces in contact with the air protected by polyester film containing two or three stretched and micro-perforated galva- nised zinc plates.
FGC Circular Flanges
The accessory is not available for the UR21 and UR33 sizes and is supplied as one unit.
The accessory consists of a flange to couple with the rectangular mouths of the unit in such a way as to consent the use of circular section channels.
SE Dampers
They can be used with the antifreeze function or to provide the bypass for the free-cooling function. The consist of a galvanised sheet frame and alumi- nium fins with nylon wheel mechanism.
The gate pin can be servo-commanded.
The accessory comes as two units.
RG Adjustment kit complete with elec- trical and power panel
The control kit allows for the control of the functions of the unit and it includes: microprocessor control with LCD room terminal. The controller with 230Vac supply and 8VA power input (without additional loads), IP30 protection class (with dedicated protections) is equipped with 2 phase- cut outputs, 10 ON/OFF outputs (relay type) under voltage (230Vac), 4 0..10V
outputs, 8 digital inputs, 4 NTC inputs and 4 universal inputs.The LDC teminal visualises the state of operation of the unit and any malfunctioning, besides controlling the settings of the unit.Tthe control, based upon the retun sensor, controls the 3-way valve ON/OFF type 230Vac, 2-stages electric batteries (with a dedicated electric power board), actuators for dampers type ON/
OFF 230Vac, filters pressure switches, humidity sensor.
TDF Electronic fans speed regulator by these it is possible to regulate the fan motor speed continuously and independently for optimal flow rate calibration. The regulators have three speed indicators in addition to the indicator showing the direction of fan air flow. The electronic regulators are supplied as kit.
UR 35 55 75 100 150 210 330
BF BF35 BF55 BF75 BF100 BF150 BF210 BF330
MPW MPW35 MPW55 MPW75 MPW100 MPW150 MPW210 MPW330
MPX MPX35 MPX55 MPX75 MPX100 MPX150 MPX210 MPX330
BFD BFD35 BFD55 BFD75 BFD100 BFD150 BFD210 BFD330
BFDR BFD35R BFD55R BFD75R BFD100R BFD150R BFD210R BFD330R
BFDW BFDW35 BFDW55 BFDW75 BFDW100 BFDW150 BFDW210 BFDW330
BFDX BFDX35 BFDX55 BFDX75 BFDX100 BFDX150 BFDX210 BFDX330
G4 G435 G455 G475 G4100 G4150 G4210 G4330
SU SU1 SU1 SU2 SU3 SU3 SU4 SU5
FGC FGC1 FGC1 FGC1 FGC2 FGC2 - -
SE SE1 SE1 SE2 SE3 SE3 SE4 SE5
TDF TDF1 TDF1 TDF1 TDF2 TDF2 TDF3 TDF4
RG RG35 RG55 RG75 RG100 RG150 RG210 RG300
Accessory compatibily charts
HORIZONTAL CONFIGURATION
VERTICAL CONFIGURATION
UR 35 55 75 100 150 210 330
BF - - - -
MPW - - - -
MPX - - - -
BFD - - - -
BFDR - - - -
BFDW - - - -
BFDX - - - -
G4 G435 G455 G475 G4100 G4150 G4210 G4330
SU - - - -
FGC FGC1 FGC1 FGC1 FGC2 FGC2 - -
SE SE1 SE1 SE2 SE3 SE3 SE4 SE5
TDF TDF1 TDF1 TDF1 TDF2 TDF2 TDF3 TDF4
RG RG35 RG55 RG75 RG100 RG150 RG210 RG330
Vent positioning
The units come with all the vents clo- sed and with the inside components positioned as shown in figure 1. below.
At the moment of installation the arrangement of the internal compo-
nents can be varied in accordance with the specific system requirements (posi- tion 2, 3, 4 for the horizontal configu- ration and position 2 for the vertical configuration) following the indications
in the use, maintenance and installa- tion manual.
Mandata aria ambiente
Aspirazione aria di rinnovo
Espulsione aria viziata
Ripresa aria ambiente
Mandata aria ambiente
Aspirazione aria di rinnovo Espulsione aria viziata
Ripresa aria ambiente
Mandata aria ambiente
Espulsione aria viziata Ripresa
aria ambiente
Aspirazione
aria di rinnovo Mandata aria
ambiente Aspirazione
aria di rinnovo Espulsione
aria viziata
Ripresa aria ambiente
1 2
3 4
HORIZONTAL CONFIGURATION
VERTICAL CONFIGURATION
Ripresa aria ambiente Aspirazione
aria di rinnovo Espulsione
aria viziata Mandata aria
ambiente
Ripresa aria ambiente
Aspirazione aria di rinnovo Espulsione aria viziata Mandata aria
ambiente
1 2
E x p u l s i o n dirty air
S u p p l y room air
Intake room I n t a k e air
external air
S u p p l y room air
E x p u l s i o n dirty air Intake exter-
nal air Intake room air
S u p p l y
room air E x p u l s i o n
dirty air
Intake room
air I n t a k e
external air
E x p u l s i o n dirty air I n t a k e
external air
Intake room air
S u p p l y room air
E x p u l s i o n dirty air
S u p p l y room air
Intake exter-
nal air Intake room
air
S u p p l y
room air E x p u l s i o n
dirty air
Intake room air
Intake exter- nal air
Free-cooling operation
ESTERNO OUTDOOR
INTERNO INDOOR
C B
A Free-cooling function requires the expelled-air flow from the room does not affect the heat recovery unit going directly to the outside through a chan- nel attached to the vent (A).
The fresh air flow thus passes throu- gh the filter and the heat recovery unit without being touched by the heat
exchangers.
To use the free-cooling function it is therefore necessary to have a channel to couple to the opening (A) and then position two gates with opposite action (B and C).
When the external air temperature is near the ideal temperature for the
room, the gate (C) is closed while gate (B) is open.
B
C
A
Approximate dimensions and weights
BASIC UNIT
A B
C B
A
60
COIL MODULES C
UR MODEL 35 55 75 100 150 210 330
Dimensions
A mm 800 800 850 970 970 970 970
B mm 460 460 510 635 635 710 860
C mm 300 300 330 390 390 390 390
Weights
BF kg 40 40 50 60 60 70 75
MPW kg 43 43 54 65 65 76 85
MPX kg 45 45 57 68 68 79 90
BFD kg 40 40 50 60 60 70 75
BFDR kg 40 40 50 60 60 70 75
BFDW kg 43 43 54 65 65 76 85
BFDX kg 45 45 57 68 68 79 90
UR MODEL 35 55 75 100 150 210 330
Dimensions
A mm 1090 1090 1190 1500 1500 1750 2500
B mm 900 900 1000 1250 1250 1400 1750
C mm 300 300 330 390 390 390 390
Weights
URxxB; URxxVB kg 61 65 74 115 140 180 330
URxxA; URxxVA kg 66 70 79 121 146 188 340
URxxE; URxxVE kg 68 73 84 126 152 195 350
SILENCERS
UR MODEL 35 55 75 100 150 210 330
Dimensions
A mm 800 800 800 800 800 800 800
B mm 380 380 430 550 550 620 820
C mm 300 300 330 390 390 390 390
Weights
SU kg 25 25 30 36 36 45 60
A
B
C
DAMPERS
A 70
20 20
20 B 20
UR MODEL 35 55 75 100 150 210 330
Dimensions
A mm 250 250 250 320 320 500 700
B mm 200 200 250 250 250 250 250
CIRCULAR FLANGES
UR MODEL 35 55 75 100 150 210 330
Dimensions
A mm 290 290 290 320 320 \ \
B mm 250 250 250 300 300 \ \
B
A
Fan characteristic curves
The characteristic curves of the fans are shown in the following diagrams, for each base unit size in the horizontal and vertical configurations.
The curves refer to the maximum and minimum fan speed. For intermediate speeds the curves move in the range between the two curves shown.
The static pressure available is read on
the ordinate, for a determined air flow expressed in m³/h providing that a sup- ply channel equal to at least one meter is installed downline from the fan.
The pressure drops for each accessory to be subtracted from the value of the useful static pressure read in function of the flow rate are shown in the table next to each graph.
The static pressures are net of the pres- sure drops of the heat recovery unit and the clean filters.
400 450
350
300
200 250
150
50 100
0 50
0 0 5 0
0 4 0
0 3 0
0 2 0
0 1 0
UR 35B; UR 35VB
Air flow rate [m³/h]
Static pressure [P a]
Additional pressure drops [Pa]
Air flow rate [m3/h] 200 250 300 350 400 450
UR 35 E/VE 10 10 10 10 10 10
UR 35 A/VA 37 56 79 105 134 167
ACCESSORIES
BF 35 8 12 17 22 29 36
MPW 35 10 15 22 28 37 45
MPX 35 18 22 27 32 39 46
BFD 35 8 12 17 22 29 36
BFD 35 R 8 12 17 22 29 36
BFDW 35 10 15 22 28 37 45
BFDX 35 18 22 27 32 39 46
G4 35 0 0 0 0 0 0
SU 1 50 50 50 50 50 50
450 500
400
300 350
250
150 200
100
0 50
0 100 200 300 400 500 600 700 800 900 1000
UR 55B; UR 55VB
Air flow rate [m³/h]
Static pressure [P a]
Additional pressure drops [Pa]
Air flow rate [m3/h] 300 350 400 450 500 550 600 650
UR 55 E/VE 10 10 10 10 10 10 10 10
UR 55 A/VA 28 37 48 59 72 86 101 117
ACCESSORIES
BF 55 17 22 29 36 43 52 61 70
MPW 55 23 30 39 48 58 69 81 93
MPX 55 27 32 39 46 53 62 71 80
BFD 55 17 22 29 36 43 52 61 70
BFD 55R 23 30 39 48 58 69 81 93
BFDW 55 23 30 39 48 58 69 81 93
BFDX 55 27 32 39 46 53 62 71 80
G4 55 0 0 0 0 0 0 0 0
SU 1 50 50 50 50 50 50 50 50
450 500
400
300 350
250
150 200
100
0 50
0 100 200 300 400 500 600 700 800 900 1000
Additional pressure drops [Pa]
Air flow rare [m3/h] 500 550 600 650 700 750 800 850 900
UR 75 E/VE 10 10 10 10 10 10 10 10 10
UR 75 A/VA 58 69 81 94 108 123 138 155 172
ACCESSORIES
BF 75 20 24 29 33 38 43 49 54 61
MPW 75 29 34 41 47 54 61 69 76 85
MPX 75 30 34 39 43 48 53 59 64 71
BFD 75 20 24 29 33 38 43 49 54 61
BFD 75R 20 24 29 33 38 43 49 54 61
BFDW 75 29 34 41 47 54 61 69 76 85
BFDX 75 30 34 39 43 48 53 59 64 71
G4 75 0 0 0 0 0 0 0 0 0
SU 2 50 50 50 50 50 50 50 50 50
UR 75B; UR 75VB
Air flow rate [m³/h]
Static pressure [P a]
NRC10B ; NRC10VB
0 50 100 150 200 250
700 800 900 1000 1100 1200 1300 1400 1500
Portata aria [m
3/h]
P ressi one stati ca uti le [P a]
Max. vel.
Min. vel.
UR 100B; UR 100VB
Portata d’aria [m³/h]
Pressione statica utile [P a]
Additional pressure drops [Pa]
Air flow rate [m3/h] 700 800 900 1000 1100 1200 1300 1400
UR 100 E/VE 10 10 10 10 10 10 10 10
UR 100 A/VA 38 49 61 74 89 104 121 139
ACCESSORIES
BF 100 12 15 19 23 27 32 37 42
MPW 100 17 21 26 31 37 44 50 57
MPX 100 22 25 29 33 37 42 47 52
BFD 100 12 15 19 23 27 32 37 42
BFD 100R 12 15 19 23 27 32 37 42
BFDW 100 17 21 26 31 37 44 50 57
BFDX 100 22 25 29 33 37 42 47 52
G4 100 0 0 0 0 0 0 0 0
SU 3 50 50 50 50 50 50 50 50
NRC15B ; NRC15VB
0 50 100 150 200 250
900 1100 1300 1500 1700 1900
Portata aria [m
3/h]
P ressi o n e stati ca uti le [P a]
Max. vel.
Min. vel.
UR 150B; UR 150VB
Air flow rate [m³/h]
Static pressure [P a]
Additional pressure drops [Pa]
Air flow rate [m3/h] 900 1100 1300 1500 1700 1900
UR 150 E/VE 10 10 10 10 10 10
UR 150 A/VA 38 55 74 97 122 150
ACCESSORIES
BF 150 19 27 37 48 61 74
MPW 150 26 37 50 65 82 100
MPX 150 29 37 47 58 71 84
BFD 150 19 27 37 48 61 74
BFD 150R 19 27 37 48 61 74
BFDW 150 26 37 50 65 82 100
BFDX 150 29 37 47 58 71 84
G4 150 0 0 0 0 0 0
SU 3 50 50 50 50 50 50
NRC21B ; NRC21VB
0 50 100 150 200 250 300
1200 1400 1600 1800 2000 2200 2400 2600 Portata aria [m
3/h]
P ressi one stat ica uti le [P a]
Max. vel.
Min. vel.
UR 210B; UR 210VB
Static pressure [P a]
Air flow rate [m³/h]
Additional pressure drops [Pa]
Air flow rate [m3/h] 1200 1400 1600 1800 2000 2200 2400
UR 210 E/VE 10 10 10 10 10 10 10
UR 210 A/VA 35 47 60 74 90 108 126
ACCESSORIES
BF 210 24 31 40 50 61 72 85
MPW 210 33 42 54 68 82 97 114
MPX 210 34 41 50 60 71 82 95
BFD 210 24 31 40 50 61 72 85
BFD 210R 24 31 40 50 61 72 85
BFDW 210 33 42 54 68 82 97 114
BFDX 210 34 41 50 60 71 82 95
G4 210 0 0 0 0 0 0 0
SU 4 50 50 50 50 50 50 50
NRC33B ; NRC33VB
0 50 100 150 200 250 300 350
1800 2200 2600 3000 3400 3800 4200 Portata aria [m
3/h]
P ressi one sta ti ca uti le [P a]
Max. vel.
Min. vel.
UR 330B; UR 330VB
Static pressure [P a]
Air flow rate [m³/h]
Additional pressure drops [Pa]
Air flow rate [m3/h] 1800 2200 2600 3000 3400 3800
UR 330 E/VE 10 10 10 10 10 10
UR 330 A/VA 33 48 66 86 108 133
ACCESSORIES
BF 330 31 44 61 79 99 122
MPW 330 42 60 82 106 133 164
MPX 330 41 54 71 89 109 132
BFD 330 31 44 61 79 99 122
BFD 330R 31 44 61 79 99 122
BFDW 330 42 60 82 106 133 164
BFDX 330 41 54 71 89 109 132
G4 330 0 0 0 0 0 0
SU 5 50 50 50 50 50 50
Heat recovery unit performance curves
The following diagrams represent the heat recovery units’ performance (efficiency, recovered power) in function of the air flow for each unit size.
The performance refers to the following conditions:
• Winter functioning: fresh air flow rate equal to the expulsion air flow rate; external air temperature on input - 5° C, 80%
RH; room air temperature 20° C, 50% RH.
• Summer operation: fresh air flow rate equal to the expulsion air flow rate; external air temperature 34° C, 50% RH; room air temperature 26° C, 50% RH.
For conditions other than the ones shown above, the values read in the diagram must be multiplied by the respective correc- tive coefficient in the following tables.
WINTER MODE
Potenza Recuperata [kW]
0 2 4 6 8 10 12 14 16 18
0 250 500 750 1000 1250 1500 1750 2000 2250 2500 2750 3000 3250 3500 3750 4000 4250 Portata aria [m3/h]
Potenza recuperata [kW]
Efficiency [%]
Efficiency [%]
Recovered power [kW]
Recovered power [kW]
Air flow rate [m3/h]
Efficienza [%]
50 51 52 53 54 55 56 57 58
0 250 500 750 1000 1250 1500 1750 2000 2250 2500 2750 3000 3250 3500 3750 4000 4250 Portata aria [m3/h]
Efficienza [%]
NRC03 NRC05
NRC07 NRC10
NRC15
NRC21 NRC33
UR35
UR55 UR100
UR150
UR75 UR210
UR330
Air flow rate [m3/h]
Efficiency [%]
T External air [°C] K Efficiency K Recovered power
-15 1,05 1,47
-10 1,03 1,23
-5 1 1
0 0,93 0,75
5 0,90 0,52
10 0,89 0,36
SUMMER MODE
Efficienza [%]
44 45 46 47 48 49 50 51 52 53 54
0 250 500 750 1000 1250 1500 1750 2000 2250 2500 2750 3000 3250 3500 3750 4000 4250 Portata aria [m3/h]
Efficienza [%]
NRC03 NRC05
NRC07 NRC10
NRC15 NRC21
NRC33
Potenza Recuperata [kW]
0 1 2 3 4 5 6
0 250 500 750 1000 1250 1500 1750 2000 2250 2500 2750 3000 3250 3500 3750 4000 4250 Portata aria [m3/h]
Potenza recuparata [kW]
T External air [°C] K Efficiency K Recovered power
28 1 0,25
30 1 0,50
32 1 0,75
34 1 1
Efficiency [%]
Efficiency [%]
Air flow rate [m3/h]
Recovered power [kW]
Efficiency [kW]
Air flow rate [m3/h]
UR35 UR55
UR100
UR150 UR75
UR210
UR330
WATER TYPE HEATING COIL YIELD CURVES
INDOOR HEATING COIL
The heat power exchanged by the heating coils downline from the heat recovery units can be read for each unit size and in function of the air flow in the following diagrams.
The diagrams refer to:
• air temperature on input to the coil (that coincides with the air temperature leaving the heat recovery unit) equal to 8°C;
• water temperature entering/leaving the coil equal to 45/40°C, 70/60°C and 80/70°C respectively.
For input air conditions of coils other than those shown above (6°C, 10°C, 12°C), the value read on the ordina- te in the diagram must be multiplied by the corrective coefficient (K) shown in the tables below.
Potenza termica [kW] (aria 8°C; acqua 45/40°C)
0 5 10 15 20 25 30
0 250 500 750 1000 1250 1500 1750 2000 2250 2500 2750 3000 3250 3500 3750 4000 4250 Portata dell'aria [m3/h]
NRC03
NRC05 NRC07
NRC10 NRC15
NRC21
NRC33
T air in [°C] 6 10 12
K 1,07 0,93 0,87
Potenza termica [kW] (aria 8°C; acqua 70/60°C)
0 5 10 15 20 25 30 35 40 45
0 250 500 750 1000 1250 1500 1750 2000 2250 2500 2750 3000 3250 3500 3750 4000 4250 Portata aria [m3/h]
NRC03
NRC05 NRC07
NRC10
NRC15 NRC21
NRC33
T air in [°C] 6 10 12
Air flow rate [m3/h]
Air flow rate [m3/h]
Thermal Power [kW] (air 8 °C; water 45/40°C)
Thermal Power [kW] (air 8 °C; water 70/60°C) UR35 UR55
UR100 UR150
UR75
UR210
UR330
UR35 UR55
UR100 UR75
UR210
UR330
UR150
UR55
Potenza temica [kW] (aria 8°C; acqua 80/70°C)
0 5 10 15 20 25 30 35 40 45 50 55
0 250 500 750 1000 1250 1500 1750 2000 2250 2500 2750 3000 3250 3500 3750 4000 4250 Portata aria [m3/h]
NRC03 NRC05
NRC07 NRC10
NRC15
NRC21
NRC33
T air in [°C] 6 10 12
K 1,03 0,96 0,93
POST-HEATING COIL (MPW-BFDW)
The heat power exchanged by the hea- ting coils downline from the cold coil in the “coil module” can be read for each unit size and in function of the air flow, in the following diagrams.
The diagrams refer to:
• air temperature on input to the coil (that coincides with the air temperature leaving the cold coil) equal to 17°C;
• water temperature entering/lea- ving the coil equal to 45/40°C, 70/60°C and 80/70°C respectively.
Potenza termica [kW] (aria 17°C; acqua 45/40°C)
0 1 2 3 4 5 6
0 250 500 750 1000 1250 1500 1750 2000 2250 2500 2750 3000 3250 3500 3750 4000 4250 Portata aria [m3/h]
NRC03 NRC05
NRC07
NRC10 NRC15
NRC21
NRC33
Thermal Power [kW] (air 8 °C; water 80/70°C)
Air flow rate [m3/h]
Thermal Power [kW] (air 17 °C; water 45/40°C)
Air flow rate [m3/h]
UR35 UR55
UR100 UR150
UR75
UR210
UR330
UR35 UR55
UR75 UR100
UR210
UR150
UR330
Potenza termica [kW] (aria 17°C; acqua 70/60°C)
0 1 2 3 4 5 6 7 8 9 10 11 12
0 250 500 750 1000 1250 1500 1750 2000 2250 2500 2750 3000 3250 3500 3750 4000 4250 Portata aria [m3/h]
NRC03
NRC05 NRC07
NRC10 NRC15
NRC21
NRC33
Potenza termica [kW] (aria 17°C; acqua 80/70°C)
0 2 4 6 8 10 12 14 16
0 250 500 750 1000 1250 1500 1750 2000 2250 2500 2750 3000 3250 3500 3750 4000 4250 Portata aria [m3/h]
NRC03
NRC05 NRC07
NRC10 NRC15
NRC21
NRC33
Thermal Power [kW] (air 17 °C; water 70/60°C)
Air flow rate [m3/h]
Thermal Power [kW] (air 17 °C; water 80/70°C)
Air flow rate [m3/h]
UR55 UR75
UR35 UR100
UR210
UR150
UR330
UR55 UR75
UR35 UR100
UR210
UR150
UR330
The pressure drops on the water side of the heating coil situated immediately after the heat recovery unit and the reheating coil in the “coil module” are shown in the following diagrams.
The pressure drops on the air side can be read in function of the air flow rate and the size, on the ordinate axis.
As far as the pressure loss on the water side is concerned the following proce-
dure must be adopted:
• in diagram 1, when the thermal power required by the coil and the thermal head of the water is known, the water supply flow rate is found on the ordinate axis;
• in diagram 2, when the water flow rate taken from diagram 1 is known, the pressure drops of the coil (including the manifold
pressure drops) are read on the ordinate axis. The curves proposed in diagram 2 refer to the 80/70°C supply water: to get the water side pressure drops for other supply temperatures, the values read on the ordinate in diagram 2 must be multiplied the coefficients present in the table.
INSIDE WATER TYPE HEATING COIL (URxxA)
Perdita di carico lato aria [Pa]
0 20 40 60 80 100 120 140 160 180
0 250 500 750 1000 1250 1500 1750 2000 2250 2500 2750 3000 3250 3500 3750 4000 4250 Portata aria [m3/h]
NRC03 NRC05
NRC07
NRC10
NRC15
NRC21 NRC33
Perdite di carico lato acqua Diagramma 1
0 0,5 1 1,5 2 2,5 3 3,5 4 4,5
0 5 10 15 20 25 30 35 40 45 50
Potenza termica [kW]
Portata acqua [m3 /h]
Acqua 70/60; 80/70 Acqua 45/40
Pressure drops air side [Pa]
Air flow rate [m3/h]
Pressure drops water side [kPa]
Thermal Power [kW]
Water flow rate [m3/h]
water 45/40 water 70/60; 80/70
Pressure drop curves
UR330 UR210
UR150 UR100
UR75
UR55 UR35
Perdita di carico lato aria [Pa]
0 10 20 30 40 50
0 250 500 750 1000 1250 1500 1750 2000 2250 2500 2750 3000 3250 3500 3750 4000 4250 Portata aria [m3/h]
NRC03 NRC05
NRC07
NRC10
NRC15
NRC21 UR330NRC33 UR210
UR150
UR100 UR75 UR55
UR35
Perdite di carico lato acqua [kPa]
Diagramma 2 (Acqua 80/70)
0 5 10 15 20 25 30 35 40 45
0 0,5 1 1,5 2 2,5 3 3,5 4 4,5
Portata acqua [m3/h]
NRC03
NRC05 NRC07
NRC10
NRC15
NRC21 UR330NRC33
UR210 UR150
UR100 UR75
UR55 UR35
T water in / T water out [°C] K
45/40 1,15
70/60 0,8
80/70 1,0
WATER TYPE REHEATING COIL (MPW, BFDW)
Perdite di carico lato acqua [kPa]
Diagramma 1
0 0,5 1 1,5
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Acqua 70/60; 80/70 Acqua 45/40
Pressure drops water side [kPa]
Pressure drops air side [Pa]
Air flow rate [m3/h]
Air flow rate [m3/h]
water 45/40
water 70/60; 80/70 Pressure drops water side [kPa]
Perdite di carico lato acqua [kPa]
Diagramma 2 (Acqua 80/70)
0 5 10 15 20 25 30 35
0 0,25 0,5 0,75 1 1,25
Portata acqua [m3/h]
NRC03
NRC05 NRC07
NRC10
NRC15 NRC21
NRC33
T water in / T water
out [°C] K
45/40 0,85
70/60 0,75
80/70 1
Electric coils yield tables
INSIDE HEATING COIL (URxxE, URxxVE)
UR MODEL 35 55 75 100 150 210 330
Thermal power kW 2,5 2,5 5,0 5,0 10,0 15,0 25,0
Air side pressure
drop (*) Pa 10 10 10 10 10 10 10
Power supply V/Ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
Stages n° 2 2 2 2 3 3 3
Absorption A 4,6 4,6 9,1 9,1 15,2 22,7 37,9
Thermal head (*) °C 26 17 24 18 20 21 23
REHEATING COIL (MPX, BFDX)
UR MODEL 35 55 75 100 150 210 330
Thermal power kW 1,5 2 3 4 6 8 13
Air side pressure
drop (*) Pa 10 10 10 10 10 10 10
Power supply V/Ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
Stages n° 2 2 2 2 3 3 3
Absorption A 2,3 3 4,6 5,3 9,1 12,1 19,7
Thermal head (*) °C 13 11 12 12 12 11 12
(*) At nominal air flow (*) At nominal air flow
Pressure drops water side [kPa]
Water 80/70
UR35 UR55
UR75
UR100
UR210
UR150
UR330
Cooling coil capacity tables
COOLING WATER COIL (BF, MPW, MPX)
It is possible to read the operating data for the water cooling coil in the “coil module” in the following table for each unit size and dependent on the air flow rate.
LEGEND
Pa: Air flow rate [m3/h]
Tia: Input air temperature [°C]
UR: Relative humidity [%]
Tua: Air output temperature [°C]
Qtot: Total refrigerating capacity [kW]
Qsen: Sensitive refrigerating capacity [kW]
Pw: Feed water flow rate [l/h]
DPw: Water side pressure drops (including the coil manifold pressure drops) [kPa]
DPa: Air side pressure drop [Pa]
UR 35 [Water in 7/ out 12 °C]
Pa [m3/h] Tia [°C] UR [%] Tua [°C] UR [%] Qtot [kW] Qsen [kW] Pw [l/h] DPw [kPa] DPa [Pa]
200
27 60 13,4 95 1,63 0,89 280 5,7 8
28 60 13,6 95 1,80 0,94 309 5,7 8
29 60 13,8 95 1,98 0,99 340 7,6 8
30 60 14,2 95 2,12 1,03 365 9,5 8
250
27 60 14,2 93 1,90 1,05 326 7,6 12
28 60 14,4 93 2,11 1,11 363 9,5 12
29 60 14,6 93 2,33 1,18 402 9,5 12
30 60 14,7 93 2,58 1,25 443 11,4 12
300
27 60 14,8 92 2,15 1,20 370 9,5 17
28 60 15,0 92 2,41 1,28 414 11,4 17
29 60 15,1 92 2,68 1,36 461 13,3 17
30 60 15,3 92 2,97 1,44 511 15,2 17
350
27 60 15,3 91 2,40 1,35 413 11,4 22
28 60 15,5 91 2,70 1,44 465 13,3 22
29 60 15,6 91 3,02 1,53 520 17,1 22
30 60 15,7 91 3,37 1,63 579 19 22
400
27 60 15,7 90 2,64 1,49 455 13,3 29
28 60 15,9 90 2,98 1,59 512 15,2 29
29 60 16,0 90 3,37 1,70 579 19 29
30 60 16,1 90 3,76 1,81 647 24,7 29
450
27 60 16,0 89 2,88 1,63 496 15,2 36
28 60 16,2 89 3,28 1,75 564 19 36
29 60 16,3 89 3,71 1,87 638 22,8 36
30 60 16,4 89 4,16 2,00 715 28,5 36
UR 55 [Water in 7/ out 12 °C]
Pa [m3/h] Tia [°C] UR [%] Tua [°C] UR [%] Qtot [kW] Qsen [kW] Pw [l/h] DPw [kPa] DPa [Pa]
300
27 60 14,8 92 2,15 1,20 370 9,5 17
28 60 15,0 92 2,41 1,28 414 11,4 17
29 60 15,1 92 2,68 1,36 461 13,3 17
30 60 15,3 92 2,97 1,44 511 15,2 17
350
27 60 15,3 91 2,40 1,35 413 11,4 22
28 60 15,5 91 2,70 1,44 465 13,3 22
29 60 15,6 91 3,02 1,53 520 17,1 22
30 60 15,7 91 3,37 1,63 579 19 22
400
27 60 15,7 90 2,64 1,49 455 13,3 29
28 60 15,9 90 2,98 1,59 512 15,2 29
29 60 16,0 90 3,37 1,70 579 19 29
30 60 16,1 90 3,76 1,81 647 24,7 29
450
27 60 16,0 89 2,88 1,63 496 15,2 36
28 60 16,2 89 3,28 1,75 564 19 36
29 60 16,3 89 3,71 1,87 638 22,8 36
30 60 16,4 89 4,16 2,00 715 28,5 36
500
27 60 16,3 89 3,13 1,76 538 17,1 43
28 60 16,4 88 3,57 1,90 614 20,9 43
29 60 16,5 88 4,05 2,04 696 26,6 43
30 60 16,6 88 4,55 2,18 783 32,3 43
550
27 60 16,5 88 3,37 1,90 579 19 52
28 60 16,6 88 3,86 2,05 665 24,7 52
29 60 16,7 87 4,39 2,20 755 30,4 52
30 60 16,8 87 4,94 2,35 850 38 52
600
27 60 16,7 87 3,61 2,03 620 22,8 61
28 60 16,8 87 4,16 2,20 715 28,5 61
29 60 16,9 87 4,73 2,36 814 36,1 61
30 60 17,0 87 5,33 2,53 916 43,7 61
650
27 60 16,9 86 3,86 2,16 664 24,7 70
28 60 17,0 86 4,45 2,34 766 32,3 70
29 60 17,1 86 5,08 2,53 873 39,9 70
30 60 17,2 86 5,71 2,70 982 49,4 70
UR 75 [Water in 7/ out 12 °C]
Pa [m3/h] Tia [°C] UR [%] Tua [°C] UR [%] Qtot [kW] Qsen [kW] Pw [l/h] DPw [kPa] DPa [Pa]
500
27 60 15,6 92 3,3 1,88 567 5,7 20
28 60 15,8 92 3,71 2 638 7,6 20
29 60 15,9 91 4,15 2,13 714 9,5 20
30 60 16,1 91 4,62 2,26 795 11,4 20
550
27 60 15,9 91 3,51 2,01 605 7,6 24
28 60 16,1 91 3,97 2,15 682 9,5 24
29 60 16,3 91 4,43 2,28 762 11,4 24
30 60 16,4 91 4,99 2,44 858 13,3 24
600
27 60 16,1 90 3,73 2,15 641 7,6 29
28 60 16,3 90 4,23 2,29 727 9,5 29
29 60 16,5 90 4,77 2,45 820 11,4 29
30 60 16,6 90 5,35 2,62 920 15,2 29
650
27 60 16,4 90 3,94 2,27 678 9,5 33
28 60 16,6 90 4,48 2,44 771 11,4 33
29 60 16,7 90 5,08 2,61 873 13,3 33
30 60 16,8 89 5,72 2,79 983 17,1 33
700
27 60 16,6 89 4,15 2,4 714 9,5 38
28 60 16,8 89 4,74 2,58 816 11,4 38
29 60 16,9 89 5,39 2,77 927 15,2 38
30 60 17,0 89 6,08 2,96 1046 19 38
750
27 60 16,8 89 4,36 2,53 750 9,5 43
28 60 16,9 89 5 2,72 860 13,3 43
29 60 17,1 88 5,7 2,92 980 17,1 43
30 60 17,2 88 6,45 3,13 1109 20,9 43
800
27 60 16,9 88 4,57 2,65 786 11,4 49
28 60 17,1 88 5,25 2,86 904 15,2 49
29 60 17,2 88 6,01 3,08 1034 19 49
30 60 17,3 88 6,82 3,3 1172 22,8 49
850
27 60 17,1 88 4,77 2,77 820 11,4 54
28 60 17,2 88 5,53 3 950 15,2 54
29 60 17,3 87 6,33 3,23 1089 19 54
30 60 17,4 87 7,18 3,48 1236 24,7 54
900
27 60 17,2 87 4,99 2,9 859 13,3 61
28 60 17,4 87 5,79 3,14 996 17,1 61
29 60 17,5 87 6,65 3,39 1144 20,9 61
30 60 17,6 87 7,55 3,64 1299 26,6 61
UR 100 [Water in 7/ out 12 °C]
Pa [m3/h] Tia [°C] UR [%] Tua [°C] UR [%] Qtot [kW] Qsen [kW] Pw [l/h] DPw [kPa] DPa [Pa]
700
27 60 14,1 93 5,35 2,96 921 9,5 12
28 60 14,2 93 6,02 3,16 1035 11,4 12
29 60 14,2 93 6,72 3,37 1156 13,3 12
30 60 14,3 93 7,46 3,59 1283 17,1 12
800
27 60 14,5 93 5,94 3,29 1022 11,4 15
28 60 14,5 92 6,71 3,53 1154 13,3 15
29 60 14,6 92 7,53 3,77 1294 17,1 15
30 60 14,6 92 8,38 4,02 1441 20,9 15
900
27 60 14,8 92 6,53 3,62 1123 13,3 19
28 60 14,8 92 7,41 3,89 1275 17,1 19
29 60 14,8 92 8,32 4,16 1431 20,9 19
30 60 14,8 91 9,29 4,44 1598 24,7 19
1000
27 60 15,0 91 7,12 3,94 1225 15,2 23
28 60 15,0 91 8,11 4,25 1395 19 23
29 60 15,1 91 9,14 4,55 1572 24,7 23
30 60 15,1 91 10,2 4,86 1755 28,5 23
1100
27 60 15,2 90 7,72 4,26 1328 17,1 27
28 60 15,2 90 8,81 4,6 1516 22,8 27
29 60 15,3 90 9,94 4,94 1711 28,5 27
30 60 15,3 90 11,11 5,27 1911 34,2 27
1200
27 60 15,4 90 8,32 4,59 1431 20,9 32
28 60 15,4 89 9,52 4,95 1637 26,6 32
29 60 15,4 89 10,75 5,32 1849 32,3 32
30 60 15,5 89 12 5,68 2064 38 32
1300
27 60 15,5 89 8,93 4,9 1535 22,8 37
28 60 15,5 89 10,22 5,3 1758 28,5 37
29 60 15,6 89 11,54 5,69 1985 36,1 37
30 60 15,6 88 12,88 6,07 2215 43,7 37
1400
27 60 15,7 88 9,53 5,22 1639 26,6 42
28 60 15,7 88 10,92 5,65 1879 32,3 42
29 60 15,7 88 12,32 6,06 2120 39,9 42
30 60 15,8 88 13,74 6,46 2365 49,4 42
UR 150 [Water in 7/ out 12 °C]
Pa [m3/h] Tia [°C] UR [%] Tua [°C] UR [%] Qtot [kW] Qsen [kW] Pw [l/h] DPw [kPa] DPa [Pa]
900
27 60 15,2 92 6,15 3,48 1059 7,6 19
28 60 15,4 92 6,98 3,73 1201 9,5 19
29 60 15,4 92 7,87 3,99 1353 13,3 19
30 60 15,4 92 8,81 4,26 1515 15,2 19
1100
27 60 15,8 90 7,18 4,07 1235 11,4 27
28 60 15,8 90 8,22 4,39 1414 13,3 27
29 60 15,9 90 9,33 4,72 1605 17,1 27
30 60 15,9 90 10,5 5,05 1806 20,9 27
1300
27 60 16,1 89 8,2 4,64 1411 13,3 37
28 60 16,2 89 9,48 5,03 1630 17,1 37
29 60 16,2 89 10,81 5,43 1859 22,8 37
30 60 16,2 89 12,18 5,82 2096 26,6 37
1500
27 60 16,4 88 9,29 5,23 1597 17,1 48
28 60 16,4 88 10,76 5,68 1851 22,8 48
29 60 16,5 88 12,29 6,13 2114 28,5 48
30 60 16,5 87 13,84 6,57 2381 34,2 48
1700
27 60 16,6 87 10,37 5,8 1784 20,9 61
28 60 16,7 87 12,05 6,32 2073 26,6 61
29 60 16,7 87 13,75 6,82 2366 34,2 61
30 60 16,8 86 15,47 7,3 2661 41,8 61
1900
27 60 16,8 86 11,48 6,38 1974 24,7 74
28 60 16,8 86 13,33 6,95 2294 32,3 74
29 60 16,9 86 15,19 7,49 2613 39,9 74
30 60 17,1 86 16,94 7,97 2914 49,4 74
UR 210 [Water in 7/ out 12 °C]
Pa [m3/h] Tia [°C] UR [%] Tua [°C] UR [%] Qtot [kW] Qsen [kW] Pw [l/h] DPw [kPa] DPa [Pa]
1200
27 60 15,9 91 7,58 4,37 1304 7,6 24
28 60 16,0 91 8,68 4,71 1493 9,5 24
29 60 16,1 91 9,88 5,06 1699 11,4 24
30 60 16,1 91 11,15 5,43 1918 13,3 24
1400
27 60 16,3 90 8,5 4,92 1462 9,5 31
28 60 16,4 90 9,86 5,33 1695 11,4 31
29 60 16,4 90 11,28 5,76 1941 15,2 31
30 60 16,4 90 12,78 6,19 2199 17,1 31
1600
27 60 16,6 89 9,5 5,48 1633 11,4 40
28 60 16,6 89 11,05 5,96 1901 13,3 40
29 60 16,7 89 12,71 6,45 2186 17,1 40
30 60 16,7 89 14,43 6,94 2482 22,8 40
1800
27 60 16,8 88 10,49 6,03 1804 13,3 50
28 60 16,8 88 12,28 6,58 2113 17,1 50
29 60 16,9 88 14,15 7,14 2434 20,9 50
30 60 16,9 87 16,06 7,68 2763 26,6 50
2000
27 60 17,0 87 11,51 6,59 1981 15,2 61
28 60 17,0 87 13,53 7,2 2327 19 61
29 60 17,0 87 15,59 7,81 2681 24,7 61
30 60 17,1 87 17,67 8,4 3039 32,3 61
2200
27 60 17,1 86 12,56 7,14 2161 17,1 72
28 60 17,1 86 14,78 7,82 2542 22,8 72
29 60 17,2 86 17,01 8,48 2927 30,4 72
30 60 17,3 86 19,25 9,11 3311 36,1 72
2400
27 60 17,2 86 13,63 7,7 2344 20,9 85
28 60 17,3 85 16,02 8,43 2756 26,6 85
29 60 17,3 85 18,42 9,13 3169 34,2 85
30 60 17,5 85 20,74 9,78 3568 41,8 85
UR 330 [Water in 7/ out 12 °C]
Pa [m3/h] Tia [°C] UR [%] Tua [°C] UR [%] Qtot [kW] Qsen [kW] Pw [l/h] DPw [kPa] DPa [Pa]
1800
27 60 16,5 90 10,64 6,22 1830 7,6 31
28 60 16,5 90 12,4 6,77 2134 9,5 31
29 60 16,5 90 14,32 7,34 2462 13,3 31
30 60 16,5 90 16,31 7,92 2806 15,2 31
2200
27 60 16,9 88 12,6 7,34 2168 9,5 44
28 60 16,8 88 14,87 8,04 2558 13,3 44
29 60 16,8 88 17,24 8,75 2966 17,1 44
30 60 16,8 88 19,65 9,44 3380 22,8 44
2600
27 60 17,1 87 14,68 8,46 2526 13,3 61
28 60 17,1 87 17,41 9,3 2995 17,1 61
29 60 17,1 87 20,17 10,13 3470 22,8 61
30 60 17,1 87 22,93 10,91 3945 28,5 61
3000
27 60 17,3 86 16,85 9,59 2899 17,1 79
28 60 17,3 86 19,97 10,56 3435 22,8 79
29 60 17,3 86 23,06 11,47 3967 28,5 79
30 60 17,4 85 26,11 12,32 4491 36,1 79
3400
27 60 17,4 85 19,06 10,72 3278 20,9 99
28 60 17,4 85 22,51 11,78 3871 28,5 99
29 60 17,5 84 25,88 12,76 4452 36,1 99
30 60 17,8 84 28,64 13,49 4927 41,8 99
3800
27 60 17,5 84 21,27 11,83 3658 24,7 122
28 60 17,6 84 24,99 12,96 4299 34,2 122
29 60 17,8 84 28,14 13,85 4840 41,8 122
30 60 18,2 83 31,14 14,64 5358 49,4 122
UR 35 [R407C; Tev 5°C; Tcond 47°C]
Pa [m3/h] Tia [°C] UR [%] Tua [°C] UR [%] Qtot [kW] Qsen [kW] DPf [kPa] DPa [Pa]
200
27 60 10,9 94 2,03 1,06 7 8
28 60 11,2 94 2,19 1,1 8 8
29 60 11,4 94 2,36 1,15 9 8
30 60 11,6 94 2,54 1,2 10 8
250
27 60 11,8 93 2,4 1,25 9 12
28 60 12,1 93 2,6 1,31 10 12
29 60 12,3 93 2,8 1,36 12 12
30 60 12,6 93 3,01 1,41 14 12
300
27 60 12,5 92 2,74 1,43 12 17
28 60 12,8 91 2,96 1,49 13 17
29 60 13,2 91 3,19 1,55 15 17
30 60 13,5 91 3,43 1,61 17 17
350
27 60 13,2 90 3,05 1,59 14 22
28 60 13,5 90 3,29 1,66 16 22
29 60 13,9 90 3,55 1,73 18 22
30 60 14,2 90 3,82 1,79 21 22
400
27 60 13,7 89 3,33 1,74 16 29
28 60 14,1 89 3,6 1,82 19 29
29 60 14,5 89 3,88 1,89 21 29
30 60 14,9 89 4,17 1,96 24 29
450
27 60 14,2 89 3,59 1,89 19 36
28 60 14,7 89 3,88 1,97 21 36
29 60 15,1 89 4,18 2,04 25 36
30 60 15,5 89 4,5 2,12 28 36
It is possible to read the operating data for the direct expansion cooling coil in the “coil module” in the following table for each unit size and dependent on the air flow rate.
The performance refers to the following conditions:
• R407C refrigerant; average evaporation temperature 5°C; condensing temperature 47°C.
• R410A refrigerant; average evaporation temperature 9°C; condensing temperature 47°C.
LEGEND
Pa: Air flow rate [m3/h]
Tia: Input air temperature [°C]
UR: Relative humidity [%]
Tua: Air output temperature [°C]
Qtot: Total refrigerating capacity [kW]
Qsen: Sensitive refrigerating capacity [kW]
DPf: Frigorigenic fluid side pressure drop DPa: Air side pressure drop
Direct expansions cooling coils (Accessories BFD, BFDR, BFDX,
BFDW)
UR 55 [R407C; Tev 5°C; Tcond 47°C]
Pa [m3/h] Tia [°C] UR [%] Tua [°C] UR [%] Qtot [kW] Qsen [kW] DPf [kPa] DPa [Pa]
300
27 60 12,5 92 2,74 1,43 12 17
28 60 12,8 91 2,96 1,49 13 17
29 60 13,2 91 3,19 1,55 15 17
30 60 13,5 91 3,43 1,61 17 17
350
27 60 13,2 90 3,05 1,59 14 22
28 60 13,5 90 3,29 1,66 16 22
29 60 13,9 90 3,55 1,73 18 22
30 60 14,2 90 3,82 1,79 21 22
400
27 60 13,7 89 3,33 1,74 16 29
28 60 14,1 89 3,6 1,82 19 29
29 60 14,5 89 3,88 1,89 21 29
30 60 14,9 89 4,17 1,96 24 29
450
27 60 14,2 89 3,59 1,89 19 36
28 60 14,7 89 3,88 1,97 21 36
29 60 15,1 89 4,18 2,04 25 36
30 60 15,5 89 4,5 2,12 28 36
500
27 60 14,7 88 3,83 2,02 21 43
28 60 15,2 88 4,14 2,1 24 43
29 60 15,6 88 4,47 2,19 28 43
30 60 16,1 88 4,8 2,27 31 43
550
27 60 15,1 87 4,05 2,15 23 52
28 60 15,6 87 4,38 2,24 27 52
29 60 16,1 87 4,73 2,32 31 52
30 60 16,6 87 5,09 2,41 35 52
600
27 60 15,5 87 4,26 2,27 25 61
28 60 16 87 4,61 2,36 29 61
29 60 16,5 87 4,98 2,45 33 61
30 60 17 87 5,35 2,54 38 61
650
27 60 15,9 86 4,46 2,38 28 70
28 60 16,4 86 4,83 2,48 32 70
29 60 16,9 86 5,21 2,57 36 70
30 60 17,4 86 5,6 2,66 41 70