After stopping the operation of the air conditioner, turn off the power supply switch and remove the power plug. Connecting these models to the MUZ-GF·VE series outdoor units enables low standby power management. These models can be connected to the MUZ-GF·VE series after once connected to the MXZ series and operated, for example, due to relocation.

The set time for the ON/OFF timer can be reduced to 1 second for every minute. After the breaker is turned on, the time for turning on the compressor, which normally takes 3 minutes, can be reduced to 1 minute. ADVICE MODIFICATION FOR INDIVIDUAL OPERATION A maximum of 4 indoor units with wireless remote controls can be used in a room.

In this case, to operate each indoor unit individually from each remote control, the remote control P.C. After you turn on the switch, the first remote controller that sends the signal to the indoor unit will be considered as the remote controller for the indoor unit. The indoor unit will only accept the signal from the remote controller assigned to the indoor unit after they are set.

The setting will be canceled if the switch is turned off or the power supply is turned off.

8-3. AUTO RESTART FUNCTION

Operation

NOTE

WIRELESS REMOTE CONTROLLER MSZ-GF60VE MSZ-GF71VE MSZ-GF60VE MSZ-GF71VE.

MICROPROCESSOR CONTROL9

The operation indicator on the right side of the indoor unit indicates the operation status. About 2°C or more away from the set temperature. The room temperature is. approaching the set temperature.

INDOOR UNIT DISPLAY SECTION

9-1. COOL ( ) OPERATION

Coil frost prevention

Low outside temperature operation

Indoor fan speed control

9-2. DRY ( ) OPERATION

  • Cold air prevention control
  • High pressure protection
  • Defrosting
  • Vertical vane (1) Vane motor drive
  • To release the timer

Confirmation of the standard position is carried out in the following cases:. a) When the procedure starts or ends (including the operation of the timer). If the room temperature is higher than the set temperature, operation in COOL mode starts. If the room temperature is equal to or lower than the set temperature, operation starts in HEATING mode.

The COOL mode switches to the HEAT mode when approximately 15 minutes have passed and the room temperature is 1°C below the set temperature. The HEAT mode switches to COOL mode when approximately 15 minutes have passed and the room temperature is 1°C above the set temperature. When you try to operate 2 or more indoor units at the same time with one outdoor unit, one for cooling and the other for heating, the operation mode of the indoor unit that operates first will be selected.

When the ECONO COOL button is pressed in COOL mode, the set temperature is automatically increased 2°C by the microprocessor. The air conditioner automatically adjusts the fan speed and set temperature and operates in POWERFUL mode. POWERFUL mode is automatically canceled 15 minutes after operation starts, or when the POWERFUL button is pressed again within 15 minutes after operation starts.

POWERFUL mode is also canceled if the OPERATE/STOP (ON/OFF) (GF60/71VE) / STOP/OPERATE (OFF/ON) (GF60/71VE2), ECONO COOL, FAN SPEED CONTROL or i-save button inside pressed. 15 minutes after operation starts, or after operation mode is changed. The direction, speed and angle of the motor are controlled by pulse signals (approximately 12 V) sent by the microprocessor. Setting the current time (a) Press the CLOCK setting button. b) Press the TIME SET buttons ( and ) to set the current time.

Each time the FORWARD ( ) button is pressed, the set time increases by 1 minute, and each time the BACKWARD ( ) button is pressed, the set time decreases by 1 minute. Set the timer time using the TIME SET ( and ) buttons. a) Press the OFF TIMER button ( ) during operation. Each time the FORWARD ( ) button is pressed, the set time increases by 10 minutes: each time the BACKWARD ( ) button is pressed, the set time decreases by 10 minutes.

PROGRAM TIMER

At first, the current time display on the TIME MONITOR flashes “0:00”, so set the current time correctly with the CLOCK SET button.

SWING)

9-7. WEEKLY TIMER OPERATION

  • How to set the weekly timer
  • Checking weekly timer setting Checking weekly timer setting
  • How to set i-save operation
  • How to cancel operation
  • Take care of the following during servicing
  • Troubleshooting procedure
  • How to replace batteries

When the weekly timer is ON, the day of the week the timer setting is completed will light up. When all days of the week are selected to view the settings and another setting is included, will be displayed. Emergency operation is available when the remote control is missing or has failed, or when the batteries in the remote control are running low.

The indoor fan is running at high speed and the temperature control is not working. In the test run or emergency operation, the horizontal vane operates in VANE AUTO mode ( ). Emergency operation continues until the EMERGENCY OPERATION button is pressed once or twice or the unit receives a signal from the remote control.

When the system is turned off, the compressor will not restart for 3 minutes because the 3-minute time delay function kicks in to protect the compressor from overload.

TROUBLESHOOTING10

How to install the horizontal vane

If the horizontal blade is not installed correctly, all operation indicator lamps will flash.

10-2. FAILURE MODE RECALL FUNCTION Outline of the function

Indoor unit failure mode table Upper lamp of OP-

10-3. INSTRUCTION OF TROUBLESHOOTING

10-4. TROUBLESHOOTING CHECK TABLE

The electricity is not routed to the latch switch (fan) of the horizontal fan. At the same time, the operation mode of each indoor unit is set differently to COOL (includes DRY) and HEAT, the operation mode of the indoor unit which was in operation first has the priority.

10-5. TROUBLE CRITERION OF MAIN PARTS

A Check of indoor fan motor 10-6. TROUBLESHOOTING FLOW

B Check of remote controller and indoor electronic control P.C. board Check if the remote controller is exclusive for this air conditioner

C Check of indoor P.C. board and indoor fan motor

D How to check miswiring and serial signal error

E Check of installation of the horizontal vane

F Electromagnetic noise enters into TV sets or radios

Power monitor receiver SW P.C. boardFuse

10-7. TEST POINT DIAGRAM AND VOLTAGE

Removing the panel

DISASSEMBLY INSTRUCTIONS11

OPERATING PROCEDURE PHOTOS

Removing the indoor electronic control P.C

  • Removing the indoor electrical box
  • Removing the nozzle assembly
  • Removing the horizontal vane motor (1) Remove the nozzle assembly. (Refer to 4.)
  • Removing the water cut, the indoor fan motor, the indoor coil thermistor, and the line flow fan

Removal of water cut, indoor fan motor, indoor coil thermistor and line flow fan, indoor coil thermistor and line flow fan (1) Remove the panel (Refer to 1.) and the corner box. When attaching the line flow fan, screw the line flow fan so that a 5 mm gap is provided between the right edge of the line flow fan and the right wall of the case air passage (Figure 1).

Fixing the indoor coil thermistor

Holder shapeClip shape

Position and procedure for mounting the clip-shape part

Referências

Documentos relacionados

Transmission indicator Timer indicator Remote controller display ON/OFF button Set Temperature buttons Fan Speed button Changes fan speed Airflow button Changes up/down airflow