PLANEJAMENTO ENERGÉTICO

Aula 3

Aula 3

P

la

ne

ja

m

en

to

E

ne

rg

éti

co

Prof. Edmarcio Antonio Belati

edmarcio.belati@ufabc.edu.br

Aula 3

Aula 3

28/07/2008

Banco de dados

(2)

U

FA

B

C

E

N

E

R

G

IA

-2009 - Edmarcio Belati

Um dos formatos muito utilizado em SEP é o formato PECO

(Philadelphia Electric Company). EX: ANAREDE

G

Y=4-j10 pu

Y=4-j5 pu

G

2

1

BANCO DE DADOS

EXEMPLO – Sistema 3 barras

P

la

ne

ja

m

en

to

E

ne

rg

éti

co

PV

slack

PQ

P

3

=200 MW

Q

3

=100 MVAr

P

2

=170 MW

3

1 2 barra1 1000 0. 0.0 0.0-9999 9999 0. 0.0

2 1 barra2 1000 0. 0.0 0.0 100 200 -170. 0.0

3 0 barra3 1000 0. 0.0 0.0 200. 100.

9999

1 3 9.756112.195

2 3 3.44838.6206

9999

Banco de dados

(3)

U

FA

B

C

E

N

E

R

G

IA

-2009 - Edmarcio Belati

BARRAS

Número, tipo (0–PQ, 1-PV, 2-referência) , nome, tensão, ângulo, potência ativa

gerada, potência reativa gerada, Limite inferior de injeção de potência reativa, limite

superior de injeção de potência reativa, Potência ativa da carga, potência reativa da

carga, susceptância shunt, área

9999 FIM DOS DADOS DE BARRA

LINHAS

Barra inicial, barra final, resistência (%), reatância (%), susceptância shunt, tap, tap

minímo, tap máximo, limite de fluxo de potência ativa.

BANCO DE DADOS

P

la

ne

ja

m

en

to

E

ne

rg

éti

co

XXXX000

X

XXXXXXXXXXXXXX

XXXX

XXXX

XXXXX

XXXXX

XXXXX

XXXXX00000

XXXXX

XXXXX

XXXXX

XX

1 2 barra1 1000 0. 0.0 0.0-9999 9999 0. 0.0

2 1 barra2 1000 0. 0.0 0.0 100 200 -170. 0.0

3 0 barra3 1000 0. 0.0 0.0 200. 100.

9999

XXXX0000

XXXX

00000XXXXXX

XXXXXX

XXXXXX

XXXXX

XXXXX

XXXXX

000000000

0

XXXX

1 3 9.756112.195

2 3 3.44838.6206

9999

minímo, tap máximo, limite de fluxo de potência ativa.

9999 FIM DOS DADOS DE LINHA

R e X dados em % para pu R/100 e X/100

(4)

U

FA

B

C

E

N

E

R

G

IA

-2009 - Edmarcio Belati

http://www.ee.washington.edu/research/pstca/

Neste link exitem vários bancos de dados de sistemas elétricos

utilizados para testes de algortmos de fluxo de carga e fluxo de

carga ótimo

Exemplo: Sistema de 14 barras:

BANCO DE DADOS

P

la

ne

ja

m

en

to

E

ne

rg

éti

co

Sistema de 14 barras - dados

Configuração

Exemplo: Sistema de 14 barras:

IEEE Common Data Format

PTI Power Flow Data Format

PECO PSAP Format

(5)

U

FA

B

C

E

N

E

R

G

IA

-2009 - Edmarcio Belati

BANCO DE DADOS

P

la

ne

ja

m

en

to

E

ne

rg

éti

co

(6)

UFABC – ENERGIA

-20

09

-E

dm

ar

ci

o

B

el

at

i

B

A

N

C

O

D

E

D

A

D

O

S

Planejamento Energético

(7)

U

FA

B

C

E

N

E

R

G

IA

-2009 - Edmarcio Belati

1 2 Bus 1 1059 0. 232. -17.-9999 9999 0. 0. 0. 2 1 Bus 2 1044 -5. 40. 42. -40. 50. 22. 13. 0. 3 1 Bus 3 1009-13. 0. 23. 0. 40. 94. 19. 0. 4 0 Bus 4 1019-10. 0. 0. 0. 0. 48. -4. 0. 5 0 Bus 5 1019 -9. 0. 0. 0. 0. 8. 2. 0. 6 1 Bus 6 1070-14. 0. 12. -6. 24. 11. 8. 0. 7 0 Bus 7 1062-13. 0. 0. 0. 0. 0. 0. 0. 8 1 Bus 8 1090-13. 0. 17. -6. 24. 0. 0. 0. 9 0 Bus 9 1055-15. 0. 0. 0. 0. 29. 17. 19. 10 0 Bus 10 1050-15. 0. 0. 0. 0. 9. 6. 0. 11 0 Bus 11 1057-15. 0. 0. 0. 0. 4. 2. 0. 12 0 Bus 12 1054-15. 0. 0. 0. 0. 6. 2. 0. 13 0 Bus 13 1049-15. 0. 0. 0. 0. 13. 6. 0. 14 0 Bus 14 1036-16. 0. 0. 0. 0. 15. 5. 0. 9999

BANCO DE DADOS

P

la

ne

ja

m

en

to

E

ne

rg

éti

co

1 2 1.94 5.92 5.2800.0000.0000.000 0.

1 5 5.40 22.30 4.9200.0000.0000.000 0.

2 3 4.70 19.80 4.3800.0000.0000.000 0.

2 4 5.81 17.63 3.4000.0000.0000.000 0.

2 5 5.69 17.39 3.4600.0000.0000.000 0.

3 4 6.70 17.10 1.2800.0000.0000.000 0.

4 5 1.33 4.21 0.0000.0000.0000.000 0.

4 7 0.00 20.91 0.0001.0000.1001.000 0.

4 9 0.00 55.62 0.0001.0000.1001.000 0.

5 6 0.00 25.20 0.0001.0000.1001.000 0.

6 11 9.50 19.89 0.0000.0000.0000.000 0.

6 12 12.29 25.58 0.0000.0000.0000.000 0.

6 13 6.62 13.03 0.0000.0000.0000.000 0.

7 8 0.00 17.61 0.0000.0000.0000.000 0.

7 9 0.00 11.00 0.0000.0000.0000.000 0.

9 10 3.18 8.45 0.0000.0000.0000.000 0.

9 14 12.71 27.04 0.0000.0000.0000.000 0.

10 11 8.20 19.21 0.0000.0000.0000.000 0.

12 13 22.09 19.99 0.0000.0000.0000.000 0.

(8)

U

FA

B

C

E

N

E

R

G

IA

-2009 - Edmarcio Belati

Utilizando o Matpower .

BANCO DE DADOS

P

la

ne

ja

m

en

to

E

ne

rg

éti

co

(9)

U

FA

B

C

E

N

E

R

G

IA

-2009 - Edmarcio Belati

BANCO DE DADOS – 14 barras

%% bus data

% bus_i type Pd Qd Gs Bs area Vm Va baseKV zone Vmax Vmin

bus = [

1 3 0 0 0 0 1 1.016 0 0 1 1.016 0.94;

2 2 21.7 12.7 0 0 1 1.045 -4.98 0 1 1.06 0.94;

3 2 94.2 19 0 0 1 1.01 -12.72 0 1 1.06 0.94;

4 1 47.8 -3.9 0 0 1 1.019 -10.33 0 1 1.06 0.94;

5 1 7.6 1.6 0 0 1 1.02 -8.78 0 1 1.06 0.94;

P

la

ne

ja

m

en

to

E

ne

rg

éti

co

(10)

U

FA

B

C

E

N

E

R

G

IA

-2009 - Edmarcio Belati

Generator Data Format

1 bus number

(-) (machine identifier, 0-9, A-Z)

2 Pg, real power output (MW)

3 Qg, reactive power output (MVAr)

4 Qmax, maximum reactive power output (MVAr)

5 Qmin, minimum reactive power output (MVAr)

6 Vg, voltage magnitude setpoint (p.u.)

(-) (remote controlled bus index)

7 mBase, total MVA base of this machine, defaults to baseMVA

(-) (machine impedance, p.u. on mBase)

(-) (step up transformer impedance, p.u. on mBase)

(-) (step up transformer off nominal turns ratio)

8 status, > 0 - machine in service

<= 0 - machine out of service

P

la

ne

ja

m

en

to

E

ne

rg

éti

co

<= 0 - machine out of service

(-) (% of total VAr's to come from this gen in order to hold V at

remote bus controlled by several generators)

9 Pmax, maximum real power output (MW)

10 Pmin, minimum real power output (MW)

(2) 11 Pc1, lower real power output of PQ capability curve (MW)

(2) 12 Pc2, upper real power output of PQ capability curve (MW)

(2) 13 Qc1min, minimum reactive power output at Pc1 (MVAr)

(2) 14 Qc1max, maximum reactive power output at Pc1 (MVAr)

(2) 15 Qc2min, minimum reactive power output at Pc2 (MVAr)

(2) 16 Qc2max, maximum reactive power output at Pc2 (MVAr)

(2) 17 ramp rate for load following/AGC (MW/min)

(2) 18 ramp rate for 10 minute reserves (MW)

(2) 19 ramp rate for 30 minute reserves (MW)

(2) 20 ramp rate for reactive power (2 sec timescale) (MVAr/min)

(11)

U

FA

B

C

E

N

E

R

G

IA

-2009 - Edmarcio Belati

%% generator data

% bus Pg Qg Qmax Qmin Vg mBase status Pmax Pmin

gen = [

1 232.4 -16.9 10 0 1.06 100 1 332.4 0;

2 40 42.4 50 -40 1.045 100 1 140 0;

3 0 23.4 40 0 1.01 100 1 100 0;

6 0 12.2 24 -6 1.07 100 1 100 0;

BANCO DE DADOS – 14 barras

P

la

ne

ja

m

en

to

E

ne

rg

éti

co

(12)

U

FA

B

C

E

N

E

R

G

IA

-2009 - Edmarcio Belati

Banco de dados utilizado no programa do Matlab.

BANCO DE DADOS

P

la

ne

ja

m

en

to

E

ne

rg

éti

co

(13)

U

FA

B

C

E

N

E

R

G

IA

-2009 - Edmarcio Belati

%% branch data

% fbus tbus r x b rateA rateB rateC ratio angle status

branch = [

1 2 0.01938 0.05917 0.0528 9900 0 0 0 0 1;

1 5 0.05403 0.22304 0.0492 9900 0 0 0 0 1;

2 3 0.04699 0.19797 0.0438 9900 0 0 0 0 1;

2 4 0.05811 0.17632 0.034 9900 0 0 0 0 1;

2 5 0.05695 0.17388 0.0346 9900 0 0 0 0 1;

3 4 0.06701 0.17103 0.0128 9900 0 0 0 0 1;

4 5 0.01335 0.04211 0 9900 0 0 0 0 1;

BANCO DE DADOS – 14 barras

P

la

ne

ja

m

en

to

E

ne

rg

éti

co

(14)

U

FA

B

C

E

N

E

R

G

IA

-2009 - Edmarcio Belati

Running a Power Flow

To run a simple Newton power flow on the 9-bus system specified

in the file case9.m, with the default algorithm options, at the ATLAB

prompt, type:

>> runpf('case9')

Getting Help

USANDO O

MATPOWER

P

la

ne

ja

m

en

to

E

ne

rg

éti

co

14

Getting Help

As with MATLAB’s built-in functions and toolbox routines, you can

type help followed by the name of a command or M-file to get help

on that particular function. Nearly all of

MATPOWER’s M-files

have such documentation. For example:

>> help runpf

(15)

U

FA

B

C

E

N

E

R

G

IA

-2009 - Edmarcio Belati

Considerar o sistema de três barras e três linhas cujos dados são

mostrado a seguir.

barra

tipo

P (p.u.)

Q (p.u.)

V (p.u)

θ

θ

θ

θ

(

°

°

°

°

)

1

V

θ

θ

θ

θ

--- ---

1,00

0,00

2

PV

0,15

---

0,98

---3

PQ

-0,20

-0,10

---linha

r (p.u.)

x (p.u)

b

sh

(p.u.) *

EXERÇÍCIO 1– RESOLVER NO

MATPOWER

P

la

ne

ja

m

en

to

E

ne

rg

éti

co

linha

r (p.u.)

x (p.u)

b

sh

(p.u.) *

1-2

0,04

0,09

0,08

1-3

0,02

0,07

0,06

2-3

0,04

0,12

0,09

* carregamento total.

Iniciar os cálculos com

θ

= 0,0

°

para as barras PV e PQ e V= 1,0 (p.u)

para as barras PQ.

(16)

U

FA

B

C

E

N

E

R

G

IA

-2009 - Edmarcio Belati

EXERÇÍCIO 2 – RESOLVER NO

MATPOWER

O

case14

a)

Rodar o problema de 14 barras (case14);

b)

Retirar o gerador da barra 2 e rodar novamente. Comparar os

resultados.

P

la

ne

ja

m

en

to

E

ne

rg

éti

co

c)

Retirar a linha 2-5 e analisar as perdas do sistema.

d)

Tentar encontar uma uma ponto de operação ( alterar as

potências nos geradores) que minimiza as perdas do sistema.

e)

Qual a melhor barra do sistema para colocar 50 MW de

Referências

Documentos relacionados

O Banco de dados ESPACENET possui mais de 90 milhões de patentes de diversos países e por este motivo, foi escolhida para se encontrar todas as patentes

Alterações das funções executivas estão presentes em diversos transtornos, tais como o Transtorno de Déficit de Atenção e Hiperatividade Transtornos da Aprendizagem (tais como

deverão ser indicadas com a expressão (informação verbal) entre parênteses, mencionando-se os dados disponíveis somente em notas de rodapé.

Dessa forma, para o Zero Hora, os interesses de seu público-alvo estão de acordo apenas com os clientes do aplicativo e com a empresa Uber Technologies, que é a

Peixaria: peixes frescos e congelados Higiene Pessoal: absorventes, fraldas, shampoos, creme dental, desodorantes, etc Limpeza: desinfetantes, detergentes, sabão em pó,

cearensis apresenta potencial antioxidante atuando neutralização de radicais livres e redução de íons metálicos; (2) caracterizar qualitativamente a presença de metabólitos

O a-TCP contendo pequena quantidade de hidró- xido de cálcio pode ser clinicamente útil como um agente de capeamento, com uma consistente indu- ção de formação de tecido

O efeito da densidade de estocagem no crescimento e sobrevivência de larvas, juvenis e adultos de moluscos bivalves tem sido amplamente estudado FRÉCHETTE, 2005, principalmente