Indoor unit D
Power receiver LEV A
LEV B
LEV C
LEV D
Oil separator Compressor
Muffler
4-way valve
LEV E Indoor unit
C Indoor unit
B Indoor unit
A
Indoor unit A Indoor unit
B Indoor unit
C Indoor unit
D
Capillary tube
Capillary tube
Discharge temperature thermistor RT62
Strainer
#100 Strainer
#100
Strainer
#100 Strainer
#100
Strainer
#100 R.V. coil
OFF
ON Refrigerant flow in cooling Refrigerant flow in heating
Distributor
HEX-OUT
Outdoor heat exchanger temperature thermistor RT68
Defrost thermistor RT61 Capillary tube
Ambient temperature thermistor RT65 FAN-OUT
Strainer
#100 Stop valve with service port
Stop valve High-pressure switch
UNIT: mm
a
b
c
d
Outdoor unit Indoor
units
15 m
10 m 15 m Max.Height difference
UNIT: mm (inch) Outdoor unit union diameter
For
Indoor unit A Liquid 6.35(1/4) Gas 12.7(1/2) Indoor unit B Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit C Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit D Liquid 6.35(1/4) Gas 9.52(3/8) Refrigerant pipe diameter is different according to indoor unit to be
connected. When using extension pipes, refer to the right table.
When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe, refer to "PARTS CATALOG".
MAX REFRIGERANT PIPING LENGTH
Piping length each indoor unit (a, b, c, d) 25 m
Total piping length (a+b+c+d) 60 m
Bending point for each unit 25
Total bending point 60
It is irrelevant which unit is higher.
ADDITIONAL REFRIGERANT CHARGE
Outdoor unit precharged
(g)
Refrigerant piping length (one way, 4 unit total)
40 m 50 m 60 m
2,700 0 200 400
Calculation : Xg = 20 g/m x (Refrigerant piping length (m) - 40)
WHEN CONNECTING TO MFZ-KJ SERIES INDOOR UNIT MXZ-4E72VA
No. of MFZ-KJ indoor units
Refrigerant piping length (L) Maximum amount of refrigerant
~ 40 m ~ 60 m
None Charge-less (2,700 g) (L-40) x 20 g/m 3,100 g
1 unit 100 g additional charge (2,800 g) 100 g + (L-40) x 20 g/m 3,200 g 2 units 200 g additional charge (2,900 g) 200 g + (L-40) x 20 g/m 3,300 g 3 units 300 g additional charge (3,000 g) 300 g + (L-40) x 20 g/m 3,400 g 4 units 400 g additional charge (3,100 g) 400 g + (L-40) x 20 g/m 3,500 g
OBH723D
47
a
b
c
d
Outdoor unit Indoor
units
15 m 15 m
10 m Refrigerant piping length (one way, 4 unit total)
Calculation : Xg = 20 g/m x (Refrigerant piping length (m) - 25)
Max.Height difference
Outdoor unit precharged
(g) 40 m
300 25 m
2,990 0
55 m 600
70 m 900
R.V.coil
OFF Refrigerant flow in heating ON Refrigerant flow in cooling
Charge pipe Compressor
Muffler High pressure switch
Ø6.35 Ø6.35 Ø9.52 Ø12.7
Accumulator
Ø6.35 LEV A
Ø9.52
Strainer
#100 Strainer
#100 Strainer
#100 Strainer
#100 Union
Union Header(Gas)
Stop valve
Header (Evaporator)
Ø6.35 Ø9.52
Submuffler
Discharge temperature thermistor RT62
Outdoor heat exchanger temperature thermistor RT68
Ambient temperature thermistor RT65 Defrost
temperature thermistor RT61 Capillary tube
Ø4.0 x Ø2.8 x 100 Indoor unit A
Indoor unit D Indoor unit C Indoor unit B
4-way valve Stop valve
(with service port)
Indoor unit A
Indoor unit D Indoor unit C Indoor unit B
LEV B LEV C LEV D
Outdoor heat exchanger
Capillary tube
Distributor Strainer
#100
Strainer
#50
MXZ-4E83VA
UNIT: mmRefrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the tables below.
When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe, refer to "PARTS CATALOG".
UNIT: mm (inch) Piping length each indoor unit (a, b, c, d) 25 m
Total piping length (a+b+c+d) 70 m
Bending point for each unit 25
Total bending point 70
MAX REFRIGERANT PIPING LENGTH
Outdoor unit union diameter For
Indoor unit A Liquid 6.35(1/4) Gas 12.7(1/2) Indoor unit B Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit C Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit D Liquid 6.35(1/4) Gas 9.52(3/8) It is irrelevant which unit is higher.
ADDITIONAL REFRIGERANT CHARGE
OBH723D
48
a
b
c
d
Outdoor unit Indoor
units
15 m
10 m 15 m Refrigerant piping length (one way, 5 unit total)
Calculation : Xg = 20 g/m x (Refrigerant piping length (m) - 0)
e
Max.Height difference
Outdoor unit precharged
(g) 20 m
400 0 m
2,990 0
40 m 800
60 m 1,200
80 m 1,600
R.V.coil
OFF Refrigerant flow in heating ON Refrigerant flow in cooling
Compressor
Muffler High pressure switch
Ø6.35 Ø6.35 Ø9.52 Ø12.7
Accumulator
Ø6.35 LEV A
Ø9.52
Strainer
#100 Strainer
#100 Strainer
#100 Strainer
#100 Union
Union Header(Gas)
Stop valve
Header (Evaporator)
Ø6.35 Ø9.52
Submuffler
Discharge temperature thermistor RT62
Outdoor heat exchanger temperature thermistor RT68
Ambient temperature thermistor RT65 Defrost
temperature thermistor RT61 Capillary tube
Ø4.0 x Ø2.8 x 100 Indoor unit A
Indoor unit D Indoor unit C
Ø9.52 Indoor unit E Indoor unit B
4-way valve Stop valve
(with service port)
Indoor unit A
Indoor unit D Indoor unit C Indoor unit B
LEV B
LEV C LEV D Strainer
Ø6.35 #100
Indoor unit E LEV E
Outdoor heat exchanger
Capillary tube
Distributor Strainer
#100
Strainer
#50 Charge pipe
MXZ-5E102VA
UNIT: mmRefrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the tables below.
When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe, refer to "PARTS CATALOG".
UNIT: mm (inch) Piping length each indoor unit (a, b, c, d,e) 25 m
Total piping length (a+b+c+d+e) 80 m
Bending point for each unit 25
Total bending point 80
MAX REFRIGERANT PIPING LENGTH
Outdoor unit union diameter For
Indoor unit A Liquid 6.35(1/4) Gas 12.7(1/2) Indoor unit B Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit C Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit D Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit E Liquid 6.35(1/4) Gas 9.52(3/8) It is irrelevant which unit is higher.
ADDITIONAL REFRIGERANT CHARGE
OBH723D
49 Refrigerant piping length (one way, 2 unit total)
Calculation : Xg = 20 g/m x (Refrigerant piping length (m) - 20)
a
b
Outdoor unit Indoor
units
15 m
10 m
15 m Max.Height
difference
Outdoor unit precharged
(g) 25 m
100 20 m
2,000 0
30 m 200
R.V.coil
OFF Refrigerant flow in heating ON Refrigerant flow in cooling
Compressor
Muffler High pressure switch
Ø6.35 Ø9.52 Ø9.52
Accumulator
Ø6.35 Strainer LEV A
#100
Strainer
#100 Strainer Union
Union Header(Gas)
Stop valve
Header (Evaporator) Submuffler
Discharge temperature thermistor RT62
Outdoor heat exchanger temperature thermistor RT68
Ambient temperature thermistor RT65 Defrost
temperature thermistor RT61 Capillary tube
Ø4.0 x Ø2.8 x 100 Indoor unit A
Indoor unit B
4-way valve Stop valve
(with service port)
Indoor unit A
Indoor unit B
LEV B
Outdoor heat exchanger
Capillary tube
Distributor Strainer
#100
Strainer
#50 Charge pipe
MXZ-2E53VAHZ
UNIT: mmRefrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the tables below.
When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe, refer to "PARTS CATALOG".
UNIT: mm (inch) Piping length each indoor unit (a, b) 20 m
Total piping length (a+b) 30 m
Bending point for each unit 20
Total bending point 30
MAX REFRIGERANT PIPING LENGTH
Outdoor unit union diameter For
Indoor unit A Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit B Liquid 6.35(1/4) Gas 9.52(3/8) It is irrelevant which unit is higher.
ADDITIONAL REFRIGERANT CHARGE
OBH723D
50
MXZ-4E83VAHZ
R.V.coil
OFF Refrigerant flow in heating ON Refrigerant flow in cooling
Compressor
Oil separator High pressure switch
Ø6.35 Ø6.35 Ø9.52 Ø12.7 Indoor unit A
Accumulator
Ø6.35 LEV A
Ø9.52
2-way solenoid valve
Distributor Strainer #100
Union
Union Header(Gas)
Stop valve Strainer
Strainer Strainer #50
#50
#100
Header(Evaporator) Charge pipe
Capillary tube
Capillary tube Ø2.5 x Ø0.6 x 1000
Ø4.0 x Ø3.0 x 200 Ø6.35
Discharge temperature thermistor RT62
Outdoor heat exchanger temperature thermistor RT68
Ambient temperature thermistor RT65 Defrost
temperature thermistor RT61 Capillary tube
Ø4.0 x Ø2.8 x 100
Outdoor heat exchanger 4-way valve
Stop valve (with service port) Indoor unit B
Indoor unit C Ø9.52 Indoor unit D
Indoor unit A Indoor unit B
Indoor unit C Indoor unit D
Strainer #100 Strainer #100
Strainer #100 LEV B
LEV D LEV C
Capillary tube
Refrigerant piping length (one way, 4 unit total)
Calculation : Xg = 20 g/m x (Refrigerant piping length (m) - 25) Outdoor unit
precharged
(g) 40 m
300 25 m
3,900 0
55 m 600
70 m 900
a
b
c
d
Outdoor unit Indoor
units
15 m 15 m
10 m Max.Height difference
UNIT: mm
Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the tables below.
When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe, refer to "PARTS CATALOG".
Piping length each indoor unit (a, b, c, d) 25 m
Total piping length (a+b+c+d) 70 m
Bending point for each unit 25
Total bending point 70
MAX REFRIGERANT PIPING LENGTH
It is irrelevant which unit is higher.
ADDITIONAL REFRIGERANT CHARGE
UNIT: mm (inch) Outdoor unit union diameter
For
Indoor unit A Liquid 6.35(1/4) Gas 12.7(1/2) Indoor unit B Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit C Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit D Liquid 6.35(1/4) Gas 9.52(3/8)
OBH723D
51
When relocating or disposing of the air conditioner, pump down the system following the procedure below so that no refrigerant is released into the atmosphere.
1) Turn off the breaker.
2) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.
3) Fully close the stop valve on the liquid pipe side of the outdoor unit.
4) Turn on the breaker.
5) Start the emergency COOL operation on all the indoor units.
6) When the pressure gauge shows 0.05 to 0 MPa [Gauge] (approximately 0.5 to 0 kgf/cm²), fully close the stop valve on the gas pipe side of the outdoor unit and stop the operation. (Refer to the indoor unit installation manual about the method for stopping the operation.)
* If too much refrigerant has been added to the air conditioner system, the pressure may not drop to 0.05 to 0 MPa [Gauge] (ap- proximately 0.5 to 0 kgf/cm²), or the protection function may operate due to the pressure increase in the high pressure refriger- ant circuit. If this occurs, use a refrigerant collecting device to collect all of the refrigerant in the system, and then recharge the system with the correct amount of refrigerant after the indoor and outdoor units have been relocated.
7) Turn off the breaker. Remove the pressure gauge and the refrigerant piping.
When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes.
The compressor may burst and cause injury if any foreign substance, such as air, enters the pipes.
WARNING