Wiring diagram: Indoor unit

No documento Installer reference guide (páginas 95-100)

14.6 Wiring diagram

14.6.2 Wiring diagram: Indoor unit

1 3 A8P

1 2 3 4

X5Y

DS1 A6P

X10A X10A

X5M

X1A

K2M

K3M K3M

K2M

M1S

X10A

X14A

X5M

X1Y X2Y

X3Y X4Y

X4Y

X4Y X24A.7

R3T -t°

R4T -t°

R5T -t°

R2T -t°

A1P X5A

1 2 X6A

1 2 X7A

1 2 X8A

1 2 X9A

1 2 X4A

1 2 3 4 2

X40A

1 3 4 5 6 7 8

3 2 1

X85A 4 5 6

3 2 1 X33A

4 5 6 R1T

-t°

S1S S2S S3S B1L

4 3 7 8 9 10

3 2 1

4 5 1

2 3

2 1

4 5

NO BLK

NCBRN N BLU

X24A.5

A4P

5 6 4 3 1 2

OFFON1 CN2

CN1

F1U F2U

SS1

PHC1

Y4 Y2

Y1 Y3

YC X4

X1 X2 X3

KFR

KCR KHRKHUR

F2U

X2A

X1A X13A X4A

PE

GND PWM

N L

GND PWM

N L PE

M3P MS3~

M1P MS3~

X80A

X801M OFFON DS1

Q3L 11

12 11 12 ON

OFF 8 7 6 5 4 3 2 1

A5P

3 2 1

X3A

4 5 6 7

8 R7T

-t°

S6S S7S S8S S9S 1 2 3 4 5 10 11 12 9 8 7 6 5 4 3 2 1

+12V

F1U

1 2 3 1 2 3 4 5

GND

7 6 5 4 3 2 1 6 5 4 3 2 1

21 X2M

28 29 X2M.8

A4P.Y2

X2M.29

21 X2M

28 29 X2M.8

4 4

1 2

3 2 1

1

5 1

5 4

3 4

3

X1Y L N

1 2

A4P.YC A4P.Y2

4D092009-1B_page 4

Power limitation digital inputs:

12 V DC / 12 mA detection (voltage supplied by PCB)

Space C/H On/OFF output Max. load 0.3 A - 250 V AC Min. load 20 mA - 5 V DC Demand PCB

Electric pulse meter inputs:

5 V DC pulse detection (voltage supplied by PCB)

Alarm output Max. load 0.3 A - 250 V AC Min. load 20 mA - 5 V DC Digital I/O PCB

Switch box Preferential kWh rate power supply contact: 16 V DC detection (voltage supplied by PCB)

only if no EKBPHT*

only for EKBPHT*

Options: bottom plate heater OR On/OFF output Only for digital I/O PCB option

Switch box

Safety thermostat

Options: boiler output, alarm output

to bottom plate heater

Only for demand PCB option

Ext. heat source Max. load 0.3 A - 250 V AC Min. load 20 mA - 5 V DC

OUTDOOR UNIT

4D092009-1C_page 5

EHV*

5 6

1 1

R1T -t°

A3P CCOMH

A3P

R1T -t°

CCOMH

R1H R1H

R1T -t°

R1T

X1M -t° X1M

%H20 %H20

H CCOM L N HCCOM LN

PC PC

A4P A4P

A3P A3P

X2M.1 X2M.2 X2M.3 X2M.4 X2M.1a X2M.2a X2M.3 X2M.4

1 3 5 7

1 3 5 7 1

2 1a 2a 3 4

X1A.1 X1A.3

1 2 1 3 1 3 1 3

1

3 1 3 5

1 2 3

1 2 3X1M X1M

X6YA X6Y X6YB

X6Y X6YB

X1M X1M

X2M 31 30

30 31X2M Q2DI

(SPST)

P1P2 P1P2

R6T -t°

-t°

R1T -t°

R1T A2P

A2P 21

X17A X1A X19A X26A X31A

X2M X3A X11A

FU1

KPR FU2

3 5 X16A

1

1 3 5

1 3 5 1 2 1 3 1 1 2

X20A

X2A X28A X15A X18A X22A

KCR KVR

K6R

X2M X5M X5M

M2P M

1~

35

34 12 56

NOBLK NC BRN

N BLU M3S

4 2

1

2 3

4 12

11 22

21 K1M

Q1L A2

A1 32

31 K1M TR1

Q1L

A1P

K1R

F1B

Q1DI

PE

I I

A3P A3P

X2M.4 X2M.1a X2M.4

X2M.1

R2T -t°

R2T -t°

4

X11M3 5 6 X11M345 6

5 6

3

3 M2S

M2S

X2M.5 X2M.7

X2M5 6 788a 9 1028 29 X2M.21 X24A

2

L N

X6YA123 123

N L

5 6

3 1

F1T E3H

X1HA 1X1H

2 3

X2M.2 X2M.4 X2M.1 X2M.2a X2M.4 X2M.1a

only for wired On/OFF thermostat only for wired

On/OFF thermostat

only for wireless On/OFF thermostat only for wireless

On/OFF thermostat

Add LWT zone Heatpump convector Main LWT zone

Heatpump convector

Switch box

User interface ext. ambient sensor option (indoor or outdoor) Remote

user interface DHW pump output

Max. load:

2 A (inrush) - 230 V AC 1 A (continuous) DHW pump 3 wire type

Shut-off valve

Switch box OUTDOOR

UNIT Only for preferential kWh rate power supply (outdoor) Use normal kWh rate power supply for indoor unit

Only for normal power supply (standard) Indoor unit supplied from outdoor

OUTDOOR UNIT

1N~, 50 Hz 230 V AC

only for ext.

sensor (floor or ambient) only for ext.

sensor (floor or ambient)

NO valve

NC valve 1N~, 50 Hz

230 V AC Normal kWh rate power supply

only for

A1P Main PCB

A2P User interface PCB

A3P * On/OFF thermostat (PC=power circuit)

A3P * Heat pump convector

A4P * Digital I/O PCB

A4P * Receiver PCB (Wireless On/OFF

thermostat)

A5P Bizone PCB

A6P Current loop PCB

A8P * Demand PCB

B1L Flow sensor

DS1 (A5P) * DIP switch DS1 (A8P) * DIP switch

E3H Backup heater element (3 kW)

F1B Overcurrent fuse backup heater

F1T Thermal fuse backup heater

F1U (A4P) * Fuse 5 A 250 V for digital I/O PCB F2U (A4P) * Fuse 5 A 250 V for digital I/O PCB F1U (A5P) Fuse T 2 A 250 V for PCB F2U (A5P) Fuse T 2 A 250 V for PCB FU1 (A1P) Fuse T 6.3 A 250 V for PCB FU2 (A1P) Fuse T 6.3 A 250 V for PCB

K1M Contactor backup heater

K2M Relay 3-way valve bypass

K3M Relay 3-way valve flow

K*R Relay on PCB

M1P Additional zone pump

M2P # Domestic hot water pump

M3P Main zone pump

M1S Mixing 3-way valve

M2S # 2-way valve for cooling mode

M3S 3-way valve for space heating/domestic hot water

PHC1 * Optocoupler input circuit Q1DI, Q2DI # Earth leakage circuit breaker

Q1L Thermal protector backup heater

Q3L # Safety thermostat

R1T (A1P) Outlet water heat exchanger thermistor R1T (A2P) Ambient sensor user interface R1T (A3P) * Ambient sensor On/OFF thermostat R2T (A1P) Outlet backup heater thermistor R2T (A3P) * External sensor (floor or ambient) R3T (A1P) Refrigerant liquid side thermistor R4T (A1P) Inlet water thermistor

R5T (A1P) Domestic hot water thermistor R6T (A1P) * External indoor or outdoor ambient

thermistor

R7T (A5P) Mixed leaving water thermistor R1H (A3P) * Humidity sensor

S1S # Preferential kWh rate power supply contact S2S # Electrical meter pulse input 1

S3S # Electrical meter pulse input 2 S6S~S9S # Digital power limitation inputs SS1 (A4P) * Selector switch

TR1 Power supply transformer

X1H Connector

X*M Terminal strip

X*Y Connector

* = Optional

# = Field supply

BLK Black

BRN Brown

GRY Grey

RED Red

Notes to go through before starting the unit

English Translation

X1M Main terminal

X2M Field wiring terminal for AC

X5M Field wiring terminal for DC

Earth wiring

15 Wire number 15

Field supply

**

/12.2 Connection ** continues on page 12 column 2

1 Several wiring possibilities

Option

Not mounted in switch box Wiring depending on model PCB

Electrical connection diagram

For more details, please check the unit wiring.

4D096036-1

A4P: Y1 X2M: 29 A4P:Y2

X2M:29 X1M: 1-2-3

X2M: 30-31 X5M: 3-4

X5M: 11-12

A8P: X801M: 1-5 A8P: X801M: 2-5 A8P: X801M: 3-5 A8P: X801M: 4-5

A4P: X1-X2 X1Y: 1-2 X1M: 1-2-3

230 V

230 V

230 V

A3P: X1M: C-com-H

A4P: X1M: H-C-com

X2M: L-N A3P: X1M: 1-3

X11M : 5-6 X2M: 34-35

X5M: 5-6 X5M: 7-8 X5M: 9-10 A4P: Y2 X2M: 29

2

2

2 1

1

2x0.75

X5M: 1-2 2x0.75

Power limitation demand input 1 Safety thermostat Field supply

Field supply

Power supply Standard part

Outdoor unit

In case of signal cable: keep minimum distance to power cables >5 cm

External room thermostat / Heat pump convector

(main and/or additional zone) Optional part

Note

Only for *KBPHT*

& depending on model Bottom plate heater X1M: L1-L2-L3-N-earth

or L-N-earthv

Field supply

2 core

F1B: L-N + earth

Alarm output

Changeover to ext. heat source output Cooling/heating On/OFF output

Cooling/heating On/OFF output

signal

2 core signal

2 core signal 2 core signal

2 core

2 core

2 core signal 2 core 2 core

2x0.75 3 core

230 V

2 core 230 V

2 core 230 V 2 core 230 V

2 core signal 2 core signal 2 core signal 2 core signal Power limitation

demand input 2 Power limitation demand input 3 Power limitation demand input 4

Only for *KRP1HB*

Cooling/heating On/OFF output Ext. heat source (eg boiler) alarm indication

NC valve: X2M: 5-7 NO valve: X2M: 6-7

Electricity meter pulse input 2 Electricity meter pulse input 1 M2S (*KHBX units) for cooling mode

external thermistor (indoor or outdoor)

Only for *KRTW (wired room thermostat) 2 core for H only operation

3 core for C/H operation

4 core for H only operation 5 core for C/H operation

Standard part

Optional part Only for

(heat pump convector) Only for *KRTR

(wireless room thermostat) 2 core (3m included)

signal

Only for

*KRTETS

Only for *KRUCBL*

Circulation pump for DHW

main: X2M: 1-2-4 add: X2M: 1a-2a-4 unit preferential kWh rate power supply:

400 V or 230 V + earth

Only for preferential kWh rate power supply installation

unit power supply: 400 V or 230 V + earth

Only for normal power supply installation

normal kWh rate power supply for indoor unit: 230 V

Preferential kWh rate power supply contact

backup heater power supply (3 kW): 230 V + earth 5 or 3 core 5 or 3 core

2 core 2 core

3 core

R2TExternal sensor (floor or ambient)

Indoor unit

2 core 2x0.75 communication Only for

*KRP1AHTA

2-way valve

Only for KRCS01-1 or EKRSCA1

A2P: P1-P2 user interface communication A2P: P1-P2 user interface main: X2M: 1-2-3-4

add: X2M: 1a-2a-3-4

main: X2M: 1-4 add: X2M: 1a-4

Electrical meter specification

• Pulse meter type/voltage-free contact for 5 V DC detection by PCB.

• Possible numbers of pulses

• 0.1 pulse/kWh

• 1 pulse/kWh

• 10 pulse/kWh

• 100 pulse/kWh

• 1000 pulse/kWh

• Pulse duration

• minimum On time: 40 ms

• minimum OFF time: 100 ms

• Measurement type (depending on installation)

• Single phase AC meter

• Three phase AC meter: balanced loads

• Three phase AC meter: unbalanced loads Electrical meter installation guideline

It is the responsibility of the installer to cover the complete power consumption with electrical meters (combination of estimation and metering is NOT allowed).

Required number of electrical meters.

Outdoor unit type ERLQ004~008CAV3 ERHQ011~016BAV3

ERLQ011~016CAV3

ERHQ011~016BAW1 ERLQ011~016CAW1

Indoor unit type EHVZ04+08 EHVZ16

Backup heater type 3V

Backup heater power supply 1~ 230 V

Backup heater configuration 3 kW

Normal kWh rate power supply

Electrical meter type 1~ 1 1 1 / —

3~ balanced — — 1 / —

3~ unbalanced — — 1 / —

Preferential kWh rate power supply

Electrical meter type 1~ 2 2 1

3~ unbalanced — — 1