• Nenhum resultado encontrado

Abstract  This paper aims to evaluate the performance of

N/A
N/A
Protected

Academic year: 2019

Share "Abstract  This paper aims to evaluate the performance of"

Copied!
6
0
0

Texto

(1)

Comparative Analysis of Measurements

Time-Varying Harmonics

Frederico M. Carvalho, Fernando N. Belchior, IEEE Member, Paulo F. Ribeiro, IEEE Fellow Member Federal University of Itajubá, Itajubá – MG, Brazil

Abstract This paper aims to evaluate the performance of commercial power quality (PQ) instruments. By using a high precision programmable voltage and current source, two meters from different manufacturers are analyzed and compared. Three-phase voltage signals are applied to PQ instruments of different classes, considering 3 situations of time varying harmonic distortions. This work is relevant considering that Brazil is deploying standardization in terms of power quality measurements aiming towards regulatory procedures and index limits.

Index Terms Electrical Engineering, Indexes, Monitoring, Power Engineering, Power Quality.

I.INTRODUCTION

Power Quality (PQ) is an important subject for electric utilities by several reasons, among them the need to develop rules that provide means to measure, in an appropriate way, the PQ indices. Poor PQ indices affect functioning of utilities, different industrial units, productions, customer services and other system performance and operating costs [1].

The increased requirements on supervision, control, and performance in modern power systems make power quality monitoring a required practice for utilities. Power Quality is related to a set of parameters about disturbances in voltage and current with goals of monitoring, mitigating, regulating. It makes possible the distribution of electricity to end users according to accepted requirements for normal operation of the electrical distribution system and characteristics of voltage (magnitude, frequency, symmetry, waveform etc.). Some electronic devices, such as microprocessors, micro-controllers, sensitive computerized equipment etc., use ground as the reference for all their internal operations and connect throughout the plant. This makes them susceptible to ground differences and to power quality problems. Power disturbances compromise product quality, increase downtime, and reduce customer satisfaction. By knowing the amount of harmonics, transient impulses and noise distortion in the system, it is possible to take appropriate actions to reduce the harmful effects [1], [2].

Consequently, there is an ever increasing need for power quality monitoring systems. This performance analysis is of particular interest because it has been found that different PQ instruments fully meeting characteristics prescribed in the standards may still disagree significantly in some specific actual measurements [3], [4], [5]. It is important to mention

that most references listed in this paper about PQ monitoring are consistent with the IEC framework [6], [7].1

In Brazil there is not yet a standardization of measurement protocols for PQ instruments and different values of the same phenomenon may be presented by instruments of different manufacturers [3].

Paper [4] moves into a direction of definition of a test protocol to perform a full metrological characterization of measurement instrument for power quality monitoring. These testing protocols aim to reproduce the PQ situations associated with voltage and current signals.

Papers [5], [8] describe voltage harmonic distortion measurements in a laboratory-based comparison of power quality class A analyzers. The tested measuring instruments were designed in accordance to the requirements of the IEC 61000-4-30 standard. [6]. Four tests have indicated the variation of ±5%, based on the measured value.

Paper [9] presents an implementation of a test system for advanced calibration and performance verification of flickermeter. This is justified because it can be shown that different digital flickermeter implementations that fully meet performance tests defined in IEC 61000-4-15 [10] can still disagree significantly in some actual measurements.

With the focus on energy meters, paper [11] proposes a methodology to guide the verification of single-phase energy meters under sinusoidal and nonsinusoidal conditions. A design of an experiment that allows the testing meters under a combination of disturbances showing positive and negative correlations are described. A hardware and software system to perform verification procedures in complex situations is also presented.

It is also important to consider the calibration on the instruments. In this context, paper [12] proposes an innovative procedure, based on the Monte Carlo method. Starting from the determination of the probability density function of the uncertainty contribution of every device from the signal input stage to the analog-to-digital conversion stage, this procedure estimates the probability density function of the measurement results and the measurement standard uncertainty as the standard deviation associated with this function. The result of the experimental work done on a prototype of a power quality measuring instrument is reported.

Considering PQ monitoring by virtual instrumentation, it is common the use of the LabVIEW platform. References [13],

1

(2)

[14], [15], [16], [17] and [18] give the development of a power quality monitoring system that is suitable for utilities and end-users. With virtual instrumentation, engineers and researchers can reduce development time, design higher quality products, lower their design costs, and keep close watch on waveforms. This helps in the efficient use of electric power, and systems reliability.

In this work, different PQ instruments were subjected to the same tests condition in a laboratory and their performance were evaluated comparing the obtained values, when compared to the data that are injected by a high accuracy programmable voltage and current source.

The work has been based on the measurement procedures presented by IEC 61000-4-30 [6]. In addition, the recommendations of the Brazilian Electricity Regulatory Agency through the Distribution Procedures document - PRODIST [19], as well as the IEEE standard [20], which was taken into account.

This paper aims to show a comparative analysis of PQ instruments considering time harmonics varying [21, 22, 23]. For all cases, the results are compared with software developed at the LabVIEW platform.

II.DEFINITIONS TO VOLTAGE MEASUREMENTS

A. Voltage Magnitude

According to IEC 61000-4-30, the measuring method rms voltage must be done during a time interval of 10 cycles for 50Hz or 12 cycles for 60Hz. Each interval of 10/12 cycles must be contiguous and not overlap the adjacent intervals. This method of measurement is used for quasi-stationary signals and is not used for voltage dip, voltage swell, voltage interruption and others transients.

The rms value, by definition, includes fundamental frequency plus harmonics and inter-harmonics. The uncertainty of measurement should not exceed ±1% of the supply voltage.

B. Harmonic Voltage

The harmonic voltage measurements are defined in the IEC 61000-4-7 [24]. This standard defines a measurement of harmonics subgroups without discontinuity, composing 15 subdivisions of 10/12 cycles. Besides the harmonic rms value any instrument must be able to measure the individual harmonic voltage distortion of order h (Uh) and the total harmonic distortion of voltage (THD), as well as the phase angle of the harmonic component.

III.POWER QUALITY MEASUREMENTS

The voltage and current signals were generated by the OMICRON CMC 256-6 [25] (Fig. 1) programmable source and applied to the PQ instruments, with high-accuracy. For voltage and current the accuracy is less than 0.05%.

The electric powers and power factors showed in equations (1) to (7) were calculated using software developed at the LabVIEW platform. For this, the DAQ Acquisition NI USB-6212 (Fig. 2) [26] was used, with 16 bits of resolution, voltage transducer (0.2% of error) and a current transducer (0.15% of error).

Fig. 1. OMICRON CMC 256-6 programmable source.

Fig. 2. DAQ Acquisition NI USB-6212.

V.LABORATORY TESTS

Two commercial instruments, denoted as Class S and Class A [6], were used (Fig. 3).

Fig. 3. Setup to test the PQ where instruments were connected to the Programmable Source.

For this paper, three tests have made. Table I shows the amount of harmonics for all tests.

TABLE I.THD APPLIED IN ALL TESTS.

THD(%) U3(%) U5(%) U7(%) U11(%) U13(%)

2.9 0 0 2 1.5 1.5

10.9 3.5 10 2 1.5 1.5

15.6 3.5 15 2 1.5 1.5

6.7 3.5 5 2 1.5 1.5

The differences between each test are the duration of the harmonic’s application. Tables II, III and IV show the duration of tests I, II and III, respectively.

TABLE II.CHARACTERISTICS OF TIME-VARYING HARMONICS –TEST I.

THD (%) 2.9 0 10.9 0 15.6 0 6.7 0 2.9 0 2.9 0

Duration(s) 5 2 5 2 5 2 5 2 5 2 5 2

TABLE III.CHARACTERISTICS OF TIME-VARYING HARMONICS –TEST II.

THD (%) 2.9 0 10.9 0 15.6 0 6.7 0 2.9 0 2.9 0

(3)

TABLE IV.CHARACTERISTICS OF TIME-VARYING HARMONICS –TEST III.

THD (%) 2.9 0 10.9 0 15.6 0 6.7 0 2.9 0 2.9 0

Duration(s) 10 2 10 2 10 2 10 2 10 2 10 2

The Figs. In the next page show the results, comparing the total harmonic distortion (THD) and only the individual harmonics of 3rd and 5th orders that have changed. Figs. 4, 5 and 6 show the results of the test I. Figs. 7, 8 and 9 shows the

results of the test II. Figs. 10, 11 e 12 shows the results of the test III.

To facilitate the analysis, the tables V, VI and VII were created with the corresponding values to the Figs. 4 to12. It is important to notice that the ‘Ref’ at these tables is related to ‘Omicron results’.

Fig 4. Comparison of THD between the instruments - Test I.

Fig. 5. Comparison of U3 (%) between the instruments - Test I.

Fig. 6. Comparison of U5 (%) between the instruments - Test I.

Fig 7. Comparison of THD between the instruments - Test II.

0 2 4 6 8 10 12 14 16 18

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115

T

H

D

(%

)

TIME(s)

CLASS A CLASS S OMICRON

0 0,5 1 1,5 2 2,5 3 3,5 4

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115

U

3

(%

)

TIME(s)

CLASS A CLASS S OMICRON

0 2 4 6 8 10 12 14 16

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115

U

5

(%

)

TIME(s)

CLASS A CLASS S OMICRON

0 5 10 15 20

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125

T

H

D

(%

)

TIME(s)

(4)

Fig 8. Comparison of U3 (%) between the instruments - Test II.

Fig. 9. Comparison of U5 (%) between the instruments - Test II.

Fig. 10. Comparison of THD between the instruments - Test III.

Fig 11. Comparison of U3 (%) between the instruments - Test III. 0

1 2 3 4 5

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125

U

3

(%

)

TIME(s)

CLASS A CLASS S OMICRON

0 2 4 6 8 10 12 14 16

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125

U

5

(%

)

TIME(s)

CLASS A CLASS S OMICRON

0 5 10 15 20

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115

T

H

D

(%

)

TIME(s)

CLASS A CLASS S OMICRON

0 0,5 1 1,5 2 2,5 3 3,5 4

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115

U

3

(%

)

TIME(s)

(5)

Fig 12. Comparison of U5 (%) between the instruments - Test III.

TABLE V.RESULTS FROM TEST I.

THD(%) U3(%) U5(%)

Time (s)

Class S

Class A Ref

Class S

Class A Ref

Class S

Class A Ref

0 0.1 0.41 0.91 0 0.13 0.06 0 0.04 0.10

5 0.2 0.15 0.66 0.1 0.04 0.10 0 0.01 0.05

10 0.2 0.01 2.91 0 0 0.05 0 0 0.03

15 3 0.49 0.31 0 0 0.03 0 0 0.09

20 0.2 2.9 10.96 0.1 0 3.59 0 0 9.90

25 11 4.41 15.62 3.5 1.24 3.47 10 3.57 15.00

30 15.7 9.03 0.71 3.5 2.37 0.20 15 8.47 0.18

35 0.2 13.06 6.76 0 2.91 3.53 0 12.49 5.00

40 6.8 4.5 0.59 3.5 2.32 0.24 5 3.33 0.08

45 0.1 3.43 2.89 0 1.77 0.06 0 2.51 0.06

50 2.9 2.43 0.44 0 0.01 0.04 0 0 0.04

55 0.2 0.51 0.35 0.1 0 0.04 0 0 0.03

60 0.2 0.02 0.75 0 0 0.05 0.1 0 0.07

65 0.2 0.01 3.03 0.1 0 0.22 0 0 0.26

70 2.9 1.46 0.81 0 0 0.12 0.1 0 0.23

75 0.2 1.94 10.99 0 0 3.65 0 0 9.95

80 11 5.64 15.60 3.4 1.79 3.72 10 5.13 14.78

85 15.7 11.71 0.37 3.5 2.79 0.08 15 11.12 0.09

90 0.2 7.84 6.77 0.1 1.74 3.56 0 7.5 4.79

95 6.8 5.63 2.92 3.5 2.91 0.05 5 4.16 0.06

100 2.9 1.98 0.32 0.1 0.71 0.16 0 1 0.22

105 0.1 2.43 0.54 0 0 0.06 0.1 0 0.07

110 0.2 0.03 0.59 0 0 0.12 0.1 0 0.16

115 0.2 0.01 0.58 0 0 0.19 0.1 0 0.19

TABLE VI.RESULTS FROM TEST II.

THD(%) U3(%) U5(%)

Time (s)

Class S

Class A Ref

Class S

Class A Ref

Class S

Class A Ref

0 0.3 0.01 0.40 0.1 0 0.01 0.1 0 0.08

5 0.3 0.01 0.43 0 0 0.02 0.1 0 0.02

10 0.3 0.49 2.91 0.1 0 0.02 0 0 0.08

15 2.9 2.9 0.46 0 0 0.16 0.1 0 0.12

20 0.3 0.5 11.0 0.1 0 3.52 0 0 9.99

25 11 9.15 0.28 3.5 2.9 0.13 10 8.33 0.07

30 0.3 1.84 15.6 0.1 0.58 4.01 0 1.66 14.5

35 15.7 10.45 0.94 3.5 2.32 0.28 15 9.99 0.17

THD(%) U3(%) U5(%)

Time (s)

Class S

Class A Ref

Class S

Class A Ref

Class S

Class A Ref

40 0.3 5.23 6.76 0 1.16 3.72 0 5 4.94

45 6.8 3.39 0.39 3.5 1.75 0.05 5 2.5 0.02

50 0.4 3.38 2.89 0.1 1.75 0.08 0.1 2.5 0.07

55 2.9 1.16 0.52 0.1 0 0.09 0 0 0.08

60 0.3 1.93 0.66 0 0 0.09 0 0 0.02

65 0.3 0.01 0.65 0.1 0 0.09 0.1 0 0.12

70 0.2 0.01 0.39 0.1 0 0.10 0 0 0.08

75 0.2 0.01 0.31 0 0 0.05 0 0 0.04

80 0.3 0.01 2.92 0.1 0 0.22 0 0 0.31

85 2.9 2.28 0.61 0.1 0 0.36 0 0 0.23

90 0.4 0.52 10.9 0.1 0.01 3.69 0 0 10.0

95 11 8.57 0.83 3.5 2.73 0.20 10 7.79 0.21

100 0.3 3.67 15.6 0.1 1.17 3.97 0 3.33 14.6

105 15.7 7.85 0.76 3.5 1.75 0.29 15.1 7.49 0.35

110 0.2 7.84 6.93 0 1.75 3.71 0 7.5 5.04

115 6.8 3.39 1.26 3.5 1.74 0.33 5 2.5 0.33

120 0.3 4.5 3.17 0 2.33 0.36 0 3.33 0.31

125 0.3 0.97 1.12 0 0 0.23 0 0 0.11

TABLE VII.RESULTS FROM TEST III.

THD(%) U3(%) U5(%)

Time Class S

Class

A Ref

Class S

Class A Ref

Class S

Class A Ref

0 3 1.94 2.96 0.1 0 0.09 0 0 0.16

5 3 2.9 0.96 0 0 0.09 0.1 0 0.06

10 0.3 1.95 11.10 0.1 0 3.48 0.1 0 9.95 15 11 7.33 11.00 3.5 2.33 3.54 10 6.67 10.08 20 10.9 10.98 15.70 3.4 3.49 3.67 9.9 10 14.94 25 15.7 9.85 15.70 3.6 2.55 3.50 15.1 9.24 15.02 30 15.7 15.04 0.86 3.5 3.35 0.00 15 14.4 0.23 35 0.3 10.45 6.80 0 2.33 3.61 0 10 4.89 40 6.8 5.63 6.91 3.4 2.91 3.52 5.1 4.16 5.11 45 6.9 6.76 3.02 3.6 3.49 0.10 5.1 5 0.02 50 3 2.78 2.98 0.1 1.18 0.11 0 1.67 0.07 55 2.9 2.91 0.97 0 0 0.09 0.1 0 0.03 60 0.3 2.79 3.03 0.1 0 0.08 0 0 0.22 65 2.9 2.01 3.01 0 0 0.07 0.1 0 0.20 70 2.9 2.9 11.00 0.1 0 3.58 0.1 0 10.04 75 11 2.8 10.90 3.6 0.58 3.61 10 1.66 9.97 80 11 10.98 0.93 3.5 3.49 0.11 10 10 0.19

0 2 4 6 8 10 12 14 16

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115

U

5

(%

)

TIME(s)

(6)

THD(%) U3(%) U5(%)

Time Class S

Class

A Ref

Class S

Class A Ref

Class S

Class A Ref 85 0.4 9.16 15.70 0.1 2.91 3.60 0.1 8.33 15.02 90 15.7 7.88 15.60 3.6 1.76 3.55 15 7.5 15.13 95 15.7 15.67 0.91 3.5 3.49 0.10 15 14.99 0.14 100 0.3 9.81 6.80 0.1 2.7 3.56 0 9.01 4.96 105 6.8 6.45 6.82 3.5 3.34 3.60 5.1 4.77 4.92 110 6.8 5.63 3.03 3.6 2.91 0.25 5 4.16 0.05 115 3 1.46 3.02 0.1 0 0.13 0.1 0 0.14

IV.DISCUSSIONS AND CONCLUSIONS

The results show that under time-varying conditions different instruments (Class A and Class S) give different results due to a number of factors including differences in protocol and synchronization issues. Therefore, special attention must be paid when dealing with time-varying harmonics, particularly in high distortion cases.

This paper evaluated the performance of commercial power quality (PQ) instruments under time-varying conditions. Using a high precision programmable voltage and current source, two meters from different manufacturers were analyzed and compared. The results demonstrated significant differences between different instruments when measuring harmonic distortions under time-varying conditions, which can lead to wrong conclusions and decisions.

VI.REFERENCES

[1] R. C. Dugan; et al. “Electrical Power Systems Quality”. 3rd. Ed.. McGraw-Hill. 2012.

[2] J. Arrilaga; et al. “Power System Quality Assessment”. John Wiley and Sons. 2000.

[3] P. F. Ribeiro. Et al. “Considerations on power quality measurements and measurement instrumentation.” 7ª EPQU - International Conference on Electrical Power Quality and Utilisation. 2003. [4] A. D. Femine. D. Gallo. C. Landi. M. Luiso. “Performance Analysis of

Power Quality Monitoring Instruments. IEEE International Instrumentation and Measurement Technology Conference. Canada. 2008.

[5] K. Chmielowiec; M. Zietek; K. Piatek; A. Firlit; R. Szkoda; P. Balawender. Comparative tests of power quality analyzers - harmonic distortion. IEEE 15th International Conference on Harmonics and Quality of Power (ICHQP). 2012.

[6] IECElectromagnetic Compatibility (EMC) - Part 4-30: Testing and Measurements TechniquesPower Quality Measurement Methods.

IEC 61000-4-30. 2008.

[7] IEC 62586-1 - Power quality measurement in power supply systems - Part 1: Power quality instruments. 2013.

[8] R. P. Bingham. Recent Advancements in Monitoring the Quality of the Supply. Power Engineering Society Summer Meeting. 2001.

[9] D. Gallo; C. Landi; R. Langella; A. Testa; ‘Implementation of a Test System for Advanced Calibration and Performance Analyses of Flickermeters’. IMTC - Instrumentation and Measurement Technology Conference.. 2003.

[10] IEC Electromagnetic compatibility (EMC) - Part 4-15: Testing and measurement techniques - Flickermeter - Functional and design specifications. IEC 61000-4-15 Ed 2; 2010.

[11] D. Gallo. C. Landi. N. Pasquino. N. Polese; ‘A New Methodological Approach to Quality Assurance of Energy Meters Under Nonsinusoidal Conditions’; IEEE Transactions on Instrumentation and Measurement. Vol. 56. No. 5. October 2007.

[12] A. Ferrero; M. Lazzaroni; S. Salicone; A calibration procedure for a digital instrument for electric power quality measurement. IEEE Transactions on Instrum. and Meas.. Vol. 51. No. 4. August 2002.

[13] S. H. Laskar. M. Muhammad. Power Quality Monitoring by Virtual Instrumentation using LabVIEW. 46th Int. Eng. Conf. (UPEC). 2011. [14] S. K Bath. S. Kumra. Simulation and Measurement of Power

Waveform Distortions using LabVIEW. IEEE International Power Modulators and High Voltage Conference. 2008.

[15] D. Pradhan; L. Lakshminarayanan; V. Patil; A LabVIEW based power analyzer. Int. Conf. on Advances in Energy Conversion Techn. (ICAECT). 2014.

[16] Y. Y. Phang; M. V. Chilukuri; Remote power quality monitoring and analysis system using LabVIEW software. IEEE Conference on Inst. and Meas. Tech.. 2009.

[17] I. Búa-Núñez. Et al; Instrumentation System for Location of Partial Discharges Using Acoustic Detection With Piezoelectric Transducers and Optical Fiber Sensors. IEEE Trans. Instrum. Meas.. Vol. 63. no. 5. May 2014.

[18] A. P. J. Chandra. C. R. Venugopal; Novel Design Solutions for Remote Access. Acquire and Control of Laboratory Experiments on DC Machines. IEEE Trans. Instrum. Meas. Vol. 61. No. 2. Feb 2012. [19] ANEEL – Brazilian Electricity Agency PRODIST – the Module 8 –

“Power Quality”. 4th Revision. 2012. www.aneel.gov.br.

[20] IEEE Standard Dictionary of Electrical and Electronics Terms. ANSI/IEEE Std.100-1992 (Fifth Edition). The Inst. Of Electrical and Electronics Engineers. Inc. New York. 1992. pp. 373. 758 and 996. [21] C. A. Duque; P. M. Silveira; P. F. Ribeiro. Visualizing time-varying

harmonics using filter banks. Electric Power Systems Research (Print), v. 81, p. 974-983, 2011.

[22] Jinglin Xu. FPGA-Based Rear Time Processing of Time-Varying Waveform Distortions and Power Disturbances in Power Systems. 2007. Doutorado. Florida State University.

[23] P. F. Ribeiro, Time-Varying Waveform Distortions in Power Systems Hardcover – Aug 24 2009

[24] IEC Electrom. Comp. (EMC) – Part 4-7: Testing and Measurement Techniques - General Guide on Harmonics and Interharmonics Measurements and Instrumentation. For Power Supply Systems and Equipment Connected Thereto. IEC 61000-4-7 Ed 2.1. 2009.

[25] Programmable source CMC256 plus. Omicron -

https://www.omicron.at/en/products/all/secondary-testing-calibration/cmc-256plus . accessed in 2015-02-26.

[26] DAQ Aquisition NI USB 6212 -

Imagem

Fig. 3.  Setup to test the PQ where instruments were connected to the  Programmable Source
Fig 4. Comparison of THD between the instruments - Test I.
Fig 8. Comparison of U 3  (%) between the instruments - Test II.
Fig 12. Comparison of U 5  (%) between the instruments - Test III.

Referências

Documentos relacionados

Desta forma, diante da importância do tema para a saúde pública, delineou-se como objetivos do es- tudo identificar, entre pessoas com hipertensão arterial, os

magnitude of Brazilian tobacco farming and the scarcity of studies on the Brazilian rural popula- tion, this study aimed to describe the prevalence of heavy drinking and

Os 170 artigos selecionados foram classifica- dos em 8 categorias criadas a partir do objeto de estudo dos artigos, que se torna o critério de in- clusão e exclusão nas categorias:

Brazil - LTA mortality among young people aged 10 to 29 years, according to the main types of victims. Outros ATT Pedestrian Cyclist Motorcyclist Car passenger

Pa- tients with rural occupations had a mean surviv- al time of 75.02 months, patients with non-rural occupations 42.14 months; Patients residing in metropolitan area – Espírito

could be avoided, since the problems related to medications associated with patients, main- ly adhesion to treatment and lack of follow-up (observed as being the most frequent

Volviendo sobre nuestra hipótesis, puede ob- servarse que el discurso científico al plantear “los hechos” como tales, invisibiliza que su construc- ción es también un discurso

ingestão de médias mais elevadas de retinol e vi- tamina B12 por indivíduos com alta adesão a este padrão permite inferir que o mesmo pode suprir maiores quantidades de