ELETRODUTO DE AÇO GALVANIZADO CURVA 90° DE AÇO GALVANIZADO ELETRODUTO DE PVC RÍGIDO ELETRODUTO DE PVC RÍGIDO ELETRODUTO DE PVC RÍGIDO CAIXA DE EMBUTIR EM GESSO PARA TOMADAS ALTAS CAIXA DE EMBUTIR EM GESSO PARA TOMADAS MÉDIAS E INTERRUPTORES CAIXA DE EMBUTIR EM GESSO PARA TOMADAS BAIXAS FORRO UNIDUT METÁLICO
CORTE ESQUEMÁTICO - INSTALAÇÃO EMBUTIDA
SEM ESCALA
DOS COMPONENTES
ELETROCALHA DE INFRAESTRUTURA P/ ELÉTRICA OU TELECOMUNICAÇÕES 300 1100 2200TOMADAS PARA USO GERAL
SEM ESCALA
TOMADAS 2P+T 20A 250V CONFORME NBR 14.136/2002 EM CAIXA DE EMBUTIR EM PVC 4x4" PARA PAREDE DE GESSO ACARTONADOINSTALAÇÃO DOS ELETRODUTOS DE ELÉTRICA/LÓGICA
DISTÂNCIA MÍNIMA ENTRE CAIXAS - 15cm
SEM ESCALA
TOMADAS ELÉTRICAS EM CAIXA DE EMBUTIR EM PVC 4x4" PARA PAREDE DE GESSO ACARTONADO MÍNIMO 15 cm ELETRODUTO DE PVC RÍGIDO EMBUTIDO ELETRODUTO DE PVC RÍGIDO EMBUTIDO TOMADAS DE CABEAMENTO ESTRUTURADO EM CAIXA DE EMBUTIR EM PVC 4x4" PARA PAREDE DE GESSO ACARTONADO TOMADAS 2P+T 20A 250V CONFORME NBR 14.136/2002 EM CAIXA DE EMBUTIR EM PVC 2x4" PARA PAREDE DE GESSO ACARTONADOA
A
FIXAÇÃO DE ELETROCALHA
FIXAR A CADA 1,20m
SEM ESCALA
CORTE A-A
VISTA
MONTANTE ESTRUTURAL DA LAJE SECA (PERFIL C) GRAMPO "C" PARA SUSTENTAÇÃO DA ELETROCALHATIRANTE ROSCA TOTAL Ø1/4"
ELETROCALHA METÁLICA PERFURADA COM VIROLA DO TIPO "C" COM TAMPA (VER AS DIMENSÕES EM PROJETO) PERFILADO PERFURADO 38x19mm PARA SUSTENTAÇÃO DA ELETROCALHA
LAJE SECA (SEM FUNÇÃO DE SUSTENTAÇÃO)
MONTANTE ESTRUTURAL DA LAJE SECA (PERFIL C) GRAMPO "C" PARA SUSTENTAÇÃO DA ELETROCALHA
TIRANTE ROSCA TOTAL Ø1/4"
ELETROCALHA METÁLICA LISA COM VIROLA DO TIPO "C" COM TAMPA (VER AS DIMENSÕES EM PROJETO) PASSAGEM DOS CABOS DE
TELECOMUNICAÇÕES
ELETROCALHA METÁLICA PERFURADA COM VIROLA DO TIPO "C" COM TAMPA (VER AS DIMENSÕES EM PROJETO) PASSAGEM DOS CABOS DE ILUMINAÇÃO E TOMADAS PERFILADO PERFURADO 38x19mm PARA SUSTENTAÇÃO DA ELETROCALHA MÍNIMO 30cm 50 250 1200 250
DETALHE TÍPICO DE CONEXÃO DO
ELETRODUTO NA ELETROCALHA
SEM ESCALA
ELETRODUTO DE AÇO GALVANIZADO ELETROLITICAMENTE BUCHA E ARRUELA CONDULETE METÁLICO DO TIPO MÚLTIPLO ELETRODUTO DE AÇO GALVANIZADO ELETROLITICAMENTE ELETROCALHA METÁLICA PERFURADA COM VIROLA DO TIPO "C" COM TAMPAPAREDE DA ELETROCALHA ELETRODUTO
BUCHA ARRUELA
FIXAÇÃO DO ELETRODUTO NO TETO
SUPORTAR A CADA 1,20m
SEM ESCALA
MONTANTE ESTRUTURAL DA LAJE SECA (PERFIL C) GRAMPO "C" PARA SUSTENTAÇÃO DA ELETROCALHA
TIRANTE ROSCA TOTAL Ø1/4"
ABRAÇADEIRA DO TIPO "D"
ELETRODUTO DE AÇO GALVANIZADO
LAJE SECA (SEM FUNÇÃO DE SUSTENTAÇÃO)
LAJE SECA (SEM FUNÇÃO DE SUSTENTAÇÃO)
ELETRODUTO DE AÇO GALVANIZADO - PASSAGEM DOS CIRCUITOS DE ILUMINAÇÃO E TOMADAS
GRAMPO "C" FIXADO NO MONTANTE
ESTRUTURAL DA LAJE SECA PARA SUPORTE DO ELETRODUTO (VER DETALHE)
FORRO (TETO)
GRAMPO "C" FIXADO NO MONTANTE ESTRUTURAL DA LAJE SECA PARA PASSAGEM DO CABO DE AÇO QUE SUSTENTA A LUMINÁRIA MONTANTE ESTRUTURAL DA
LAJE SECA (PERFIL C)
CABO DE AÇO GALVANIZADO Ø1/8" PARA SUPORTE DA LUMINÁRIA
LUMINÁRIA EMBUTIDA EM FORRO
CABO TRIPOLAR 0,6/1,0kV 3#1,5mm² EM HEPR 90°C (LIVRE DE HALÓGENOS) PARA A LIGAÇÃO DA LUMINÁRIA
BASE CONECTORA
REATOR ELETRÔNICO DE ALTO FATOR DE POTÊNCIA
PLUGUE PADRÃO BRASILEIRO
CONDULETE EQUIPADO COM TOMADA PADRÃO BRASILEIRO PARA LIGAÇÃO DA LUMINÁRIA
FIXAÇÃO DAS LUMINÁRIAS DE EMBUTIR
SEM ESCALA
CONEXÃO ELETRODUTO/CAIXA ATRAVÉS DE CONJUNTO DE BUCHA E ARRUELA CONEXÃO ELETRODUTO/CAIXA ATRAVÉS DE CONJUNTO DE BUCHA E ARRUELA T r r T F FTOMADA 2P+T -10A (REF.: PIALPLUS DA LEGRAND), PARA ALIMENTAÇÃO DO PAINEL AUDIOVISUAL PARA SINALIZAÇÃO DE
EMERGÊNCIA. REF.: ALARME HB, EATON OU EQUIVALENTE.
INTERRUPTOR BIPOLAR SIMPLES, 10A/250V REF.: PIALPLUS DA LEGRAND. PARA ACIONAMENTO DA SINALIZAÇÃO DE EMERGÊNCIA DOS BANHEIROS DO TIPO ACESSÍVEIS (PNE) CAIXA DE SOBREPOR (MÍNIMO DE 105mmX105mm) COM SIRENE DE SINALIZAÇÃO INTERMITENTE E STROBE LIGHT, FONTE INTERNA DE 220Vca-12Vcc. FORNECIMENTO COMPLETO ALARME
PNE
SEM ESCALA
DETALHE ESQUEMÁTICO DE SINALIZAÇÃO PARA
BANHEIROS DO TIPO ACESSÍVEIS (PNE)
F
F r
r
CAIXAS METÁLICAS DE PASSAGEM DO TIPO CONDULETE - TIPOS C, E, T, TB, L, X e ED, RESPECTIVAMENTE. ELETROCALHA METÁLICA PERFURADA COM VIROLA DO TIPO "C", COM TAMPA. (DIMENSÕES: 150x100mm). ELETRODUTO LEVE EM AÇO GALVANIZADO ELETROLITICAMENTE, DO TIPO LEVE, INSTALAÇÃO APARENTE NO ENTREFORRO, Ø3/4" OU CONFORME INDICAÇÃO EM PLANTA.
ELETRODUTO EM PVC RÍGIDO EMBUTIDO NO TETO, PAREDE OU NO PISO, Ø3/4" OU CONFORME INDICAÇÃO EM PLANTA.
CAIXA DE EMBUTIR 4x4" EM PVC EMBUTIDA NA PAREDE (OU CONFORME INDICAÇÃO) INSTALADA A 30cm DO PISO ACABADO (OU CONFORME INDICAÇÃO) - CAIXA DE PASSAGEM DE CABOS.
SIMBOLOGIA - ILUMINAÇÃO E TOMADAS:
SÍMBOLO DESCRIÇÃO
QUADRO ELÉTRICO PARA DISTRIBUIÇÃO DE CIRCUITOS (QDC), METÁLICO, DE SOBREPOR, COM FLANGE PARA ELETROCALHA.
CAIXA DE EMBUTIR 4x4" EM PVC EMBUTIDA NA PAREDE (OU CONFORME INDICAÇÃO) INSTALADA A 220cm DO PISO ACABADO (OU CONFORME INDICAÇÃO) - CAIXA DE PASSAGEM DE CABOS.
BOTOEIRA SIMPLES PARA ACIONAMENTO DE SISTEMA DE ALARME PPNE, FORNECIDO COM TAMPA, A 30cm DO PISO ACABADO, 10A/250V.
TOMADA 2P+T PADRÃO BRASILEIRO 250V/20A EM CAIXA DE EMBUTIR 2x4" EM PVC EMBUTIDA NA PAREDE, INSTALADA A 30,0cm DO PISOACABADO (REF.: SILENTOQUE, DA LEGRAND),100VA OU COMO INDICADO.
DUAS TOMADAS 2P+T PADRÃO BRASILEIRO 250V/20A EM CAIXA DE EMBUTIR 4x4" EM PVC EMBUTIDA NA PAREDE, INSTALADAS A 30,0cm DO PISOACABADO (REF.: SILENTOQUE, DA LEGRAND),100VA OU COMO INDICADO.
DUAS TOMADAS 2P+T PADRÃO BRASILEIRO 250V/20A EM CAIXA DE EMBUTIR 4x4" EM PVC EMBUTIDA NA PAREDE, INSTALADAS A 110,0cm DO PISOACABADO (REF.: SILENTOQUE, DA LEGRAND), 100VA OU COMO INDICADO. TOMADA 2P+T PADRÃO BRASILEIRO 250V/20A EM CAIXA DE EMBUTIR 2x4" EM PVC EMBUTIDA NA PAREDE, INSTALADA A 110,0cm DO PISOACABADO (REF.: SILENTOQUE, DA LEGRAND),100VA OU COMO INDICADO. TOMADA 2P+T PADRÃO BRASILEIRO 250V/20A EM CAIXA DE EMBUTIR 2x4" EM PVC EMBUTIDA NA PAREDE, INSTALADA A 220,0cm DO PISOACABADO (REF.: SILENTOQUE, DA LEGRAND),100VA OU COMO INDICADO.
TOMADA 2P+T PADRÃO BRASILEIRO 250V/20A EM CAIXA DE EMBUTIR 2x4" INSTALADA DIRETAMENTE NO FORRO DO TETO ACABADO (REF.: PIALPLUS, DA LEGRAND),TENSÃO DE 127V - POTÊNCIA 100VA OU CONFORME INDICAÇÃO.
CAIXA DE DERIVAÇÃO PARA ELETRODUTOS COM LUVA ROSQUEADA EM PVC 2". (DIM.: 100X100X50mm) REF.: MEGA UMA TOMADA ALTA 2P+T PADRÃO BRASILEIRO 250V/20A CONFORME NBR 14.136. INSTALADA EM CAIXA DE EMBUTIR 2x4" EM PVC EMBUTIDA NA PAREDE A 15cm ACIMA DA PORTA DOS BANHEIROS PPNE (REF.: SILENTOQUE DA LEGRAND),POTÊNCIA 50W, PARA O SISTEMA DE SINALIZAÇÃO DE EMERGÊNCIA PPNE.
TOMADA ALTA 2P+T PADRÃO BRASILEIRO 250V/20A CONFORME NBR 14.136. INSTALADA EM CAIXA DE EMBUTIR 2x4" EM PVC EMBUTIDA NA PAREDE, INSTALADA A 250,0cm DO PISO ACABADO OU CONFORME INDICAÇÃO (REF.: SILENTOQUE DA LEGRAND). POTÊNCIA 25VA, PARA ATENDIMENTO AO BLOCO AUTÔNOMO.
LUMINÁRIA DE EMBUTIR PARA 2 LÂMPADAS FLUORESCENTES TUBULARES DE 32W, APROPRIADA PARA FORRO DE GESSO OU MODULADO COM PERFIL "T" DE ABA 25mm. CORPO EM CHAPA DE AÇO TRATADA COM ACABAMENTO EM PINTURA ELETROSTÁTICA EPÓXI-PÓ NA COR BRANCA. REFLETOR E ALETAS PARABÓLICAS EM ALUMÍNIO
ANODIZADO DE ALTO BRILHO. EQUIPADA COM PORTA-LÂMPADA ANTIVIBRATÓRIO EM POLICARBONATO, COM TRAVA DE SEGURANÇA E PROTEÇÃO CONTRA AQUECIMENTO NOS CONTATOS. REF.: MOD.: 2001 2xT26-32W, DA ITAIM (FORNECIDA COMPLETA, COM 2 LÂMPADAS T5 E REATOR ELETRÔNICO (AFP/PARTIDA RÁPIDA) COM TAXA DE DISTORÇÃO HARMÔNICA (THD) MENOR QUE 10%).
LUMINÁRIA DE EMBUTIR PARA 2 LÂMPADAS FLUORESCENTES TUBULARES DE 16W, APROPRIADA PARA FORRO DE GESSO OU MODULADO COM PERFIL "T" DE ABA 25mm. CORPO EM CHAPA DE AÇO TRATADA COM ACABAMENTO EM PINTURA ELETROSTÁTICA EPÓXI-PÓ NA COR BRANCA. REFLETOR E ALETAS PARABÓLICAS EM ALUMÍNIO
ANODIZADO DE ALTO BRILHO. EQUIPADA COM PORTA-LÂMPADA ANTIVIBRATÓRIO EM POLICARBONATO, COM TRAVA DE SEGURANÇA E PROTEÇÃO CONTRA AQUECIMENTO NOS CONTATOS. REF.: MOD.: 2001 2xT26-16W, DA ITAIM (FORNECIDA COMPLETA, COM 2 LÂMPADAS T5 E REATOR ELETRÔNICO (AFP/PARTIDA RÁPIDA) COM TAXA DE DISTORÇÃO HARMÔNICA (THD) MENOR QUE 10%).
LUMINÁRIA DE EMBUTIR PARA 2 LÂMPADAS FLUORESCENTES TUBULARES DE 32W, APROPRIADA PARA FORRO DE GESSO OU MODULADO COM PERFIL "T" DE ABA 25mm. CORPO / REFLETOR EM CHAPA DE AÇO TRATADA COM ACABAMENTO EM PINTURA ELETROSTÁTICA EPÓXI-PÓ NA COR BRANCA. DIFUSOR EM ACRÍLICO LEITOSO. EQUIPADA COM PORTA-LÂMPADA ANTIVIBRATÓRIO EM POLICARBONATO, COM TRAVA DE SEGURANÇA E PROTEÇÃO CONTRA AQUECIMENTO NOS CONTATOS. REF.: MOD.: 2109 2xT16-32W, DA ITAIM (FORNECIDA COMPLETA, COM 2 LÂMPADAS T5 E REATOR ELETRÔNICO (AFP/PARTIDA RÁPIDA) COM TAXA DE DISTORÇÃO HARMÔNICA (THD) MENOR QUE 10%).
LUMINÁRIA DE EMBUTIR PARA 2 LÂMPADAS FLUORESCENTES TUBULARES DE 16W, APROPRIADA PARA FORRO DE GESSO OU MODULADO COM PERFIL "T" DE ABA 25mm. CORPO / REFLETOR EM CHAPA DE AÇO TRATADA COM ACABAMENTO EM PINTURA ELETROSTÁTICA EPÓXI-PÓ NA COR BRANCA. DIFUSOR EM ACRÍLICO LEITOSO. EQUIPADA COM PORTA-LÂMPADA ANTIVIBRATÓRIO EM POLICARBONATO, COM TRAVA DE SEGURANÇA E PROTEÇÃO CONTRA AQUECIMENTO NOS CONTATOS. REF.: MOD.: 2109 2xT16-16W, DA ITAIM (FORNECIDA COMPLETA, COM 2 LÂMPADAS T5 E REATOR ELETRÔNICO (AFP/PARTIDA RÁPIDA) COM TAXA DE DISTORÇÃO HARMÔNICA (THD) MENOR QUE 10%).
LUMINÁRIA RETANGULAR DE SOBREPOR TIPO ARANDELA PARA 1 LÂMPADA FLUORESCENTE COMPACTA DE 23W. INSTALADA A 220cm DO PISO ACABADO OU CONFORME INDICAÇÃO EM PLANTA. CORPO EM CHAPA DE AÇO TRATADA COM PINTURA ELETROSTÁTICA EPÓXI-PÓ NA COR BRANCA. DIFUSOR EM VIDRO PLANO TEMPERADO JATEADO. REF.: MOD.: OLIVINO 1xTC-TSE-23W DA ITAIM, FORNECIDA COM 1 LÂMPADA FLUORESCENTE COMPACTA DE 23W-220V.
CAIXA DE LIGAÇÃO OU PASSAGEM REDONDA PARA UTILIZAÇÃO EM ÁREA COBERTA APARENTE. REF.: DAILET MÚLTIPLO REDONDA DA DAISA.
DOIS INTERRUPTORES BIPOLARES SIMPLES, 10A/250V EM CAIXA DE EMBUTIR 4x4" EM PVC EMBUTIDA NA PAREDE. ALTURA 110cm DO PISO ACABADO. REF.: SILENTOQUE DA LEGRAND.
SÍMBOLO
UM INTERRUPTOR BIPOLAR SIMPLES, 10A/250V EM CAIXA DE EMBUTIR 2x4" EM PVC EMBUTIDA NA PAREDE. ALTURA 110cm DO PISO ACABADO. REF.: SILENTOQUE DA LEGRAND.
TRÊS INTERRUPTORES BIPOLARES SIMPLES, 10A/250V EM CAIXA DE EMBUTIR 4x4" EM PVC EMBUTIDA NA PAREDE. ALTURA 110cm DO PISO ACABADO. REF.: SILENTOQUE DA LEGRAND.
DOIS INTERRUPTORES BIPOLARES PARALELOS, 10A/250V EM CAIXA DE EMBUTIR 4x4" EM PVC EMBUTIDA NA PAREDE. ALTURA 110cm DO PISO ACABADO. REF.: SILENTOQUE DA LEGRAND.
UM INTERRUPTOR BIPOLAR PARALELO, 10A/250V EM CAIXA DE EMBUTIR 2x4" EM PVC EMBUTIDA NA PAREDE. ALTURA 110cm DO PISO ACABADO. REF.: SILENTOQUE DA LEGRAND.
UM INTERRUPTOR INTERMEDIÁRIO SIMPLES, 10A/250V EM CAIXA DE EMBUTIR 2x4" EM PVC EMBUTIDA NA PAREDE. ALTURA 110cm DO PISO ACABADO. REF.: SILENTOQUE DA LEGRAND.
PERCURSO DE CABOS QUE SOBE, QUE PASSA E QUE DESCE EM NÍVEL. INDICAÇÃO EM PLANTA.
CAIXA DE PASSAGEM 15x15cm (OU CONFORME INDICAÇÃO) COM TAMPA REVERSÍVEL. CONSTRUÍDA EM LIGA DE ALUMÍNIO SILÍCIO, FUNDIDA EM MOLDE PERMANENTE, DE BOM ACABAMENTO, ALTA RESISTÊNCIA MECÂNICA E À PROVA CORROSÃO. TAMPA LISA FIXADA POR PARAFUSOS DE AÇO GALVANIZADO, DOTADAS DE JUNTA DE VEDAÇÃO. INSTALADA A 30cm DO PISO ACABADO OU CONFORME INDICAÇÃO. REF.: CP-1515-10 DA WETZEL. CABO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA 70°C 750V OU CONFORME INDICAÇÃO EM PLANTA. CLASSE 5 DE ENCORDOAMENTO - NEUTRO, FASE, RETORNO SIMPLES, RETORNO PARALELO E TERRA, RESPECTIVAMENTE - #2,5mm² OU CONFORME INDICAÇÃO EM PLANTA.
SIMBOLOGIA - ILUMINAÇÃO E TOMADAS:
1 - MEDIDAS EM MILÍMETROS, EXCETO ONDE INDICADO.
2 - CONSIDERAR AS COTAS PRIORITÁRIAS EM RELAÇÃO À ESCALA. 3 - AS ELEVAÇÕES INDICADAS TÊM COMO REFERÊNCIA O PISO ACABADO.
4 - AS TOMADAS INDICADAS EM 220V DEVERÃO SER VERMELHAS DE FÁBRICA, DIFERENTEMENTE DAS TOMADAS CONVENCIONAIS 127V, E ALÉM DISSO DEVERÃO RECEBER MARCAÇÃO INDELÉVEL COM OS DIZERES "220V", CONFORME DETALHE APRESENTADO NESTE PROJETO.
5 - TODOS OS CABOS TERMINAIS SERÃO DO TIPO CLASSE 5 DE ENCORDOAMENTO E TERÃO ISOLAMENTO EM DUPLA CAMADA POLIOLEFÍNICO NÃO HALOGENADO 70°C 750V EXCETO EM LOCAIS SUJEITO À UMIDADE, COMO TUBULAÇÕES ENTERRADAS NO SOLO, QUE DEVERÃO SER DO TIPO 0,6/1kV.
6 - TODOS OS CABOS DEVERÃO SER ANILHADOS (IDENTIFICAÇÃO DOS CIRCUITOS) EM TODAS AS CAIXAS, CAIXAS DE PASSAGEM E/OU CONDULETES.
7 - TODAS AS CONEXÕES DE CONDUTORES ENTRE SI E COM OUTROS COMPONENTES DA INSTALAÇÃO, DEVEM GARANTIR CONTINUIDADE ELÉTRICA DURÁVEL E ADEQUADA SUPORTABILIDADE E PROTEÇÃO MECÂNICA.
8 - EM TODAS AS DERIVAÇÕES UTILIZAR CAIXA DE PASSAGEM DO TIPO CONDULETE METÁLICO MÚLTIPLO.
9 - OS LANCES ENTRE DUAS CAIXAS DE PASSAGEM NÃO DEVERÃO CONTER MAIS DO QUE DUAS CURVAS, EVITANDO-SE TAMBÉM CURVAS REVERSAS SEMPRE QUE POSSÍVEL.
10 - NAS INTERLIGAÇÕES DOS ELETRODUTOS METÁLICOS COM AS ELETROCALHAS, UTILIZAR BUCHA E ARRUELA.
11 - SONDAR OS ELETRODUTOS COM CABO DE NYLON, DEIXANDO UMA SOBRA DE ± 1,0m EM CADA CAIXA PARA A PASSAGEM DE CABOS.
12 - TODOS OS ELETRODUTOS EM PVC DEVERÃO OBEDECER À NBR 15.465. NÃO SERÃO ACEITOS PRODUTOS IDENTIFICADOS COMO "MANGUEIRAS".
13 - NOS TRECHOS DE ELETRODUTOS APARENTES OU NO INTERIOR DE ESPAÇOS DE CONSTRUÇÃO (POR EXEMPLO, ENTREFORRO OU ENTREPISO) DEVERÃO SER UTILIZADOS ELETRODUTOS LEVES DE AÇO GALVANIZADO ELETROLITICAMENTE CONFORME NBR 13.057. NÃO UTILIZAR ELETRODUTOS PESADOS NAS ÁREAS INTERNAS À EDIFICAÇÃO. PARA INSTALAÇÕES EXTERNAS, UTILIZAR ELETRODUTOS DE AÇO GALVANIZADO A FOGO DO TIPO PESADO CONFORME NBR 5.624.
14 - ATERRAR TODAS AS PARTES METÁLICAS NÃO ENERGIZADAS DA INSTALAÇÃO (INCLUSIVE LUMINÁRIAS) ATRAVÉS DO CABO DE PROTEÇÃO Pe (CABO VERDE DOS CIRCUITOS, TERRA) MAIS PRÓXIMO.
15 - UM MESMO CABO DE PROTEÇÃO (TERRA) PODERÁ SER COMUM A VÁRIOS CIRCUITOS, DESDE QUE SUA BITOLA SEJA IDÊNTICA AO CABO FASE DE MAIOR SEÇÃO CONTIDO EM UM CONDUTO/NICHO DE ELETROCALHA.
16 - ONDE EXISTIR FORRO E/OU PISO ELEVADO, AS ELETROCALHAS DE PASSAGEM DOS CABOS ELÉTRICOS DEVERÃO SER INSTALADAS SOBRE O FORRO OU ABAIXO DO PISO ELEVADO. ESTAS DEVERÃO SER DE USO EXCLUSIVO PARA OS SISTEMA ELÉTRICO E DEVERÃO ESTAR DISTANTES PELO MENOS 30cm DAS ELETROCALHAS QUE CONTENHAM CABOS DE
TELECOMUNICAÇÕES.
17 - UTILIZAR O SEGUINTE CÓDIGO DE CORES PARA CABOS:
FASE: PRETO - NEUTRO: AZUL CLARO - TERRA: VERDE - RETORNO: BRANCO - RETORNO PARALELO: CINZA.
18 - EM SITUAÇÕES ONDE A VIGA ESTRUTURAL TORNAR INVIÁVEL A PASSAGEM DOS CONDUTOS ELÉTRICOS, A INSTALAÇÃO DEVERÁ SER FEITA ABAIXO DA VIGA PARA TRANSPOSIÇÃO DESTES OBSTÁCULOS UTILIZANDO-SE TIRANTES PARA EXTENSÃO DOS SUPORTES (VER DETALHES), PODENDO TAMBÉM UTILIZAR ELETRODUTOS METÁLICOS FLEXÍVEIS (SEALTUBE).
19 - TODO E QUALQUER PONTO DE CABEAMENTO ESTRUTURADO DEVERÁ SER ACOMPANHADO DE SEU RESPECTIVO PONTO ELÉTRICO, CONFORME INSTALAÇÕES DE CABEAMENTO (VER PROJETO ESPECÍFICO). PARA INSTALAÇÕES EMBUTIDAS, PREVER DISTÂNCIA MÍNIMA DE 15cm ENTRE AS CAIXAS DE ELÉTRICA E DE CABEAMENTO PARA ATENDER A UM MESMO EQUIPAMENTO.
20 - TODAS AS LUMINÁRIAS, POR SEGURANÇA, DEVERÃO SER FIXADAS ATRAVÉS DE CABO DE AÇO AOS MONTANTES ESTRUTURAIS DA LAJE (VER DETALHE)..
21 - OS ALIMENTADORES DO QDC A PARTIR DO PADRÃO DE ENTRADA (INCLUINDO O PADRÃO DE ENTRADA DE ENERGIA JUNTO À CONCESSIONÁRIA) DEVERÃO SER OBJETO DE PROJETO ESPECÍFICO.
22 - OS CHUVEIROS ELÉTRICOS DEVERÃO TER RESISTÊNCIA DO TIPO BLINDADA OU SER APROPRIADOS PARA INSTALAÇÕES EM CIRCUITOS PROTEGIDOS ATRAVÉS DE IDR (INTERRUPTOR DIFERENCIAL RESIDUAL) PARA EVITAR DESLIGAMENTOS INDEVIDOS.
23 - TODOS OS BANHEIROS DO TIPO ACESSÍVEIS (PNE) DEVERÃO POSSUIR SINALIZAÇÃO DE EMERGÊNCIA DE ACORDO COM A NBR-9050. PARA ESQUEMÁTICO DE FUNCIONAMENTO DO SISTEMA, VER DETALHE ESPECÍFICO NESTE PROJETO.
24 - PROJETO ELABORADO DE ACORDO COM AS ESPECIFICAÇÕES DA NBR-5410:2004, SEGUINDO AS NECESSIDADES APONTADAS PELO LAYOUT SUGERIDO PELO CLIENTE. QUALQUER ALTERAÇÃO DEVERÁ SER COMUNICADA AO PROJETISTA PARA VERIFICAÇÃO.
25 - O MEMORIAL DESCRITIVO E QUANTITATIVO FAZEM PARTES INTEGRANTES DESTE PROJETO, E DEVERÃO SER CONSULTADOS ANTES DE QUAISQUER ORÇAMENTOS OU INSTALAÇÕES.
NOTAS GERAIS:
1 - SISTEMA EM BAIXA TENSÃO TRIFÁSICO 220/127V - 60Hz - Icc MÍNIMO DE 5,0kA.
2 - A ILUMINÂNCIA MÉDIA DOS AMBIENTES DA EDIFICAÇÃO FORAM DETERMINADAS CONFORME RECOMENDADO PELA NBR-5413:1992.
3 - ESQUEMA DE ATERRAMENTO ADOTADO: TN-S.
4 - EM RELAÇÃO AS PRESCRIÇÕES DE PROTEÇÃO CONTRA INCÊNDIO, A EDIFICAÇÃO FOI CLASSIFICADA COMO BD-3 (TUMULTUADA).
5 - TEMPERATURAS CONSIDERADAS EM PROJETO: - TEMPERATURA AMBIENTE: 30°C;
- TEMPERATURA NO SOLO: 20°C.
6 - LIMITE MÁXIMO DE QUEDA DE TENSÃO ADMITIDA:
- 7% CALCULADO A PARTIR DOS TERMINAIS SECUNDÁRIOS DO TRANSFORMADOR MT/BT ATÉ O PONTO DE UTILIZAÇÃO.
7 - NORMAS APLICÁVEIS:
- ELETRODUTOS DE AÇO GALVANIZADO ELETROLÍTICO: ABNT NBR 13.057; - ELETRODUTOS DE PVC RÍGIDO: ABNT NBR 15.465;
- CONDUTORES DE COBRE 70°C 750V OU 0,6/1kV, NÃO-PROPAGANTES DE CHAMA, LIVRES DE HALOGÊNIO E COM BAIXA EMISSÃO DE FUMAÇA E GASES TÓXICOS: ABNT NBR 13.248;
- INTERRUPTORES PARA INSTALAÇÕES ELÉTRICAS FIXAS DOMÉSTICAS E ANÁLOGAS: ABNT NBR NM 60.669-1; - PLUGUES E TOMADAS PARA USO DOMÉSTICO E ANÁLOGO ATÉ 20A/250V EM CORRENTE ALTERNADA: ABNT NBR 14.136;
- DISJUNTORES TERMINAIS ATÉ 125A (MINI-DISJUNTORES): ABNT NBR IEC 60.947-2; - DISJUNTORES ACIMA DE 125A (CAIXA MOLDADA): ABNT NBR IEC 60.947-2; - DISJUNTORES PADRÃO CEMIG: NEMA (CONFORME HOMOLOGAÇÃO); - DISPOSITIVOS DIFERENCIAL RESIDUAL (DR): ABNT NBR NM 61.008; - DISPOSITIVOS PROTETORES DE SURTOS (DPS): NBR IEC 61.643-1;
- DUTOS CORRUGADOS DE POLIETILENO (PE) PARA INFRAESTRUTURAS DE ENERGIA E TELECOMUNICAÇÕES (PEAD): ABNT NBR 15.715;
- CONTATORES MODULARES PARA ILUMINAÇÃO: IEC 61.095;
- BLOCOS AUTÔNOMOS PARA ILUMINAÇÃO DE EMERGÊNCIA: ABNT NBR 10.898; - QUADROS ELÉTRICOS: ABNT NBR IEC 60.439-1.
PARÂMETROS GERAIS DE PROJETO:
ELETRODUTOS PVC/AÇO
e mm e mm 2,3 2,7 2,9 3,0 3,1 3,8 4,0 5,0 DIÂMETRO NOMINAL-DN mm POL EXTERNO-DE mm DIÂMETRO NOMINAL-DN mm 25 32 40 50 60 75 85 110 POL 3/4 1 1.1/4 1.1/2 2 2.1/2 3 4 EXTERNO-DE mm 25,9 33,0 42,0 47,4 59,0 74,7 87,6 113,1ELETRODUTOS DE AÇO CARBONO, TIPO LEVE I, CONF. NBR 13057 ESPESSURA NOMINAL DA PAREDE ELETRODUTOS DE PVC RÍGIDO ROSQUEÁVEL, CLASSE B, CONF. NBR 6150
ESPESSURA NOMINAL DA PAREDE
1,5 1,5 2,0 2,25 2,25 2,85 2,65 2,65 20 25 32 40 50 65 80 100 3/4 1 1.1/4 1.1/2 2 2.1/2 3 4 25,2 31,5 40,5 46,6 58,4 74,1 86,8 111,6
FORMATO INTERNACIONAL A1 ALONGADO (1026 x 594mm)
abrasip-mg
FOLHA:01
05
ETAPA:INSTALAÇÕES ELÉTRICAS
PROJETO EXECUTIVO
DETALHES CONSTRUTIVOS, NOTAS
GERAIS E SIMBOLOGIA
VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS
Av. Augusto de Lima, nº655 conj. 418 - Centro - BH Telefax: (31) 3324-2702 http://www.viabile.com.br viabile@viabile.com.br VERIFICAÇÃO DATA OBJETO REVISÃO DATA:
NOME DO ARQUIVO CAD: DESENVOLVIMENTO:
BRENO ASSIS DE OLIVEIRA
OUTUBRO/2013
UNIDADE: ESCALA:
INDICADA
MILÍMENTROS
CREA: 78.667/D RESPONSÁVEL TÉCNICO:
BRENO ASSIS DE OLIVEIRA
PROPRIETÁRIO:
SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS 460-UBSSS-R06-ELE-01-PE-T1A.DWG
UBS MINAS - PROJETO MODELO
DISCIPLINA:
PROJETO:
ENDEREÇO:
CONTEÚDO:
GERENCIAMENTO E PROJETO:
3-CONFERIR MEDIDAS NO LOCAL.
2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996. DOS RESPONSÁVEIS TÉCNICOS DO PROJETO.
NOTAS:
4-COTAS EM CENTÍMETROS.
SUBSECRETARIA DE INOVAÇÃO E LOGISTICA
SUPERINTENDENCIA DE GESTÃO
DIRETORIA DE GESTÃO DA REDE FÍSICA
SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE
SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA
DIRETORIA DE INFRAESTRUTURA FÍSICA
PROJETO MODELO UNIDADE BÁSICA DE SAÚDE
PROJETO DE ACORDO COM RDC-50/2002 E
É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO
COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO.
RESOLUÇÃO 1797/09 DA SES-MG
TIPO T1A - ACLIVE
1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO
Secretaria de Estado de Saúde de Minas Gerais Cidade Administrativa Presidente Tancredo Neves
Rodovia Pref. Américo Gianetti s/nº Bairro: Serra Verde B. Hte -Minas Gerais - CEP: 31630-900 SES-MG Predio -Minas - 12º e 13º andar
EMISSÃO INICIAL VIABILE
00 27/09/2012
ALIMENTAÇÃO DOS PONTOS DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS VIABILE
01 26/10/2012
EMISSÃO FINAL VIABILE
02 08/11/2012
ADEQUAÇÃO DA ARQUITETURA CONFORME VISA VIABILE
03 01/02/2013
READEQUAÇÃO DA ARQUITETURA E COMENTÁRIOS VIABILE
04 11/09/2013
REVISÃO DO DETALHAMENTO VIABILE
05 23/09/2013
ALTERAÇÃO PARA INSTALAÇÕES EMBUTIDAS VIABILE
VACINAÇÃO
SALA DE ESPERA
SALA DE REUNIÃO E EDUCAÇÃO
I.S. MASC.
RECEPÇÃO
TRIAGEM
COLETA
CIRCULAÇÃO
GINECOLOGIA
I. S.
VARANDA COBERTA
CIRCULAÇÃO
I.S. FEM.
RESÍDUOS
RESÍDUOS
TV SUSPENSACOMPRESSOR
VAGA PARA AMBULÂNCIA
FOSSO
ÁREA PERMEÁVEL ÁREA PERMEÁVEL
proj. da cobertura CALÇADA RUA
DML
proj. da coberturaSALA DE APOIO
AGENTES
ENDEMIAS
APOIO AGENTES
ENDEMIAS
SALA DE
CURATIVOS
CUIDADOS
BÁSICOS
ATENDIMENTO
MULTIPROFISSIONAL
ATENDIMENTO
MULTIPROFISSIONAL
GUARDA
MEDICAMENTOS
REBAIXO NA CALÇADA P/
ACESSO DE VEÍCULOS
REBAIXO NA CALÇADA P/
ACESSIBILIDADE
L6ab L6ab L6ac L6aa L6aa L6ac L6ac L6ac L6ac L6ac L6ad L6ad VER NOTA 5 VER NOTA 5 VER NOTA 5 VER NOTA 5 VER NOTA 5 VER NOTA 5 VER NOTA 5 L4bc L4bc L5bn L5bn L3av
DML
ALMOXARIFADO
ESCOVÁRIO
COPA
LAVAGEM E
DESINFECÇÃO DE MATERIAIS
ESTERILIZAÇÃO
GUICHÊCONSULTÓRIO
ODONTOLÓGICO
VESTIÁRIO
MASCULINO
VESTIÁRIO
FEMININO
#4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 FOLHA:02
05
ETAPA:INSTALAÇÕES ELÉTRICAS
PROJETO EXECUTIVO
PLANTAS DE ILUMINAÇÃO DO 1º E
2º PAVIMENTOS
VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS
Av. Augusto de Lima, nº655
conj. 418 - Centro - BH
Telefax: (31) 3324-2702
http://www.viabile.com.br
viabile@viabile.com.br
VERIFICAÇÃO
EMISSÃO INICIAL
VIABILE
00
27/09/2012
DATA OBJETO
REVISÃO
DATA:
NOME DO ARQUIVO CAD: DESENVOLVIMENTO:
BRENO ASSIS DE OLIVEIRA
SETEMBRO/2013
UNIDADE: ESCALA:
INDICADA
MILÍMETROS
CREA: 78.667/D RESPONSÁVEL TÉCNICO:
BRENO ASSIS DE OLIVEIRA
PROPRIETÁRIO:
SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS
460-UBSSS-R05-ELE-02-PE-T1A.DWG
UBS MINAS - PROJETO MODELO
DISCIPLINA:
PROJETO:
ENDEREÇO:
CONTEÚDO:
GERENCIAMENTO E PROJETO:
3-CONFERIR MEDIDAS NO LOCAL.
2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996.
1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO.
NOTAS:
4-COTAS EM CENTÍMETROS.
SUBSECRETARIA DE INOVAÇÃO E LOGISTICA
SUPERINTENDENCIA DE GESTÃO
DIRETORIA DE GESTÃO DA REDE FÍSICA
SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE
SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA
DIRETORIA DE INFRAESTRUTURA FÍSICA
PROJETO MODELO UNIDADE BÁSICA DE SAÚDE
PROJETO DE ACORDO COM RDC-50/2002 E
É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO
COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO.
RESOLUÇÃO 1797/09 DA SES-MG
TIPO T1A - ACLIVE
abrasip-mg
ALIMENTAÇÃO DOS PONTOS DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS
VIABILE
01
26/10/2012
Secretaria de Estado de Saúde de Minas Gerais
Cidade Administrativa Presidente Tancredo Neves
Rodovia Pref. Américo Gianetti s/nº Bairro: Serra Verde B. Hte
-Minas Gerais - CEP: 31630-900 SES-MG Predio -Minas - 12º e 13º andar
EMISSÃO FINAL
VIABILE
02
08/11/2012
ADEQUAÇÃO DA ARQUITETURA CONFORME VISA
VIABILE
03
31/01/2013
PLANTA DE ILUMINAÇÃO DO PRIMEIRO PAVIMENTO
ESCALA: ... 1/75
PLANTA DE ILUMINAÇÃO DO SEGUNDO PAVIMENTO
ESCALA: ... 1/75
READEQUAÇÃO DA ARQUITETURA E COMENTÁRIOS
VIABILE
04
17/09/2013
5-OS ELETRODUTOS PARA ALIMENTAÇÃO DAS ARANDELAS EXTERNAS DEVERÃO SER INSTALADOS SOBRE AS JANELAS,
A 2,70m DO PISO ACABADO.
REVISÃO DO DETALHAMENTO
VIABILE
T1-600VA
PLANTA DE TOMADAS DO PRIMEIRO PAVIMENTO
PLANTA DE TOMADAS DO SEGUNDO PAVIMENTO
T1 #4,0 T46 T1 #4,0 T1 #4,0 T1 T46 T2-2X200VA T46 T1 #4,0 T46 T46 T1 T2 T46 T1 T1 T1 T1 T46 T2 T2 T1 #4,0 #4,0 #4,0 T1 #4,0 T14a' T14a' T14a' T14 T14a' T1 T2 T46 T14 T16 T1 T2 T16 #4,0 T1 T14 T46 #4,0 T14 T14 T14b' T14b' T14b' T14b' #4,0 #4,0 #4,0 T16-1,11kW-220V T2-600VA T4-2X200VA T4 T17-1,11kW-220V T18-1,11kW-220V T3-4X200VA
A
B
T14B
T17 T18 #4,0C
T8D
T10 T11 #6,0 T9 T8 T5 T5E
F
T46F
T8F
T27 T28 #4,0 T26 T27 T28 #4,0 T26 T27 T28 #4,0 T28 #4,0 T6-2X200VA T46 T8 T5 T5 T6 T5 T6 T6 T6 T6 T6 T7-2X200VA T20-1,11kW-220V T21 #4,0 T20 T7 T7 T7 T7K
T7 T22 #4,0 T7 T21-1,11kW-220V T22-1,11kW-220VI
T6 T7 T7K
L
M
T10-600VA T11-1,8kVA T9-600VA T10 T11 #6,0 T9 T11 #6,0 T9 T9 T9 T9 T12 T12 T12 T24 T25 #4,0 T24 T25 #4,0 T12 T12 T46 T46J
T14 T12 T12 T12 T12-2X200VA T14 T24-1,11kW-220V T14 T14G
G
T13 T13 T13 T12 T13 T12 T25 #4,0H
T14 T13 T13 T13 T13 T14 T13 T23 #4,0O
T23-1,11kW-220VJ
T46 T46 T46 T44 #4,0 T7 T7 T7 T15 T14 T14M
N
O
T42-1,11kW-220V T37-200VA T37-200VA T37-2X200VA T37 T37 T37 T37 T37 T37 T37 T34-6500W T33-6500W T34 #4,0 T33 #4,0 T32 T34 #6,0 T37 T42 T32 #4,0 T32 T32 T37 T42 #4,0 T36-1,8kVA T49 T35 T36 T35 #4,0 T35 T35 T35 T35 T35 T35 T35 T32 T36 T35 T36 #4,0 T35-600VA T35 T35 T34 #6,0 T37 T42 T32 #4,0 T35 T36 T32 T32 T32 T32 T32 T32 T32 T32 T40 T41 #4,0 T40 T41 #4,0 T41 #4,0 T41-1,11kW-220V T40-1,11kW-220V T40 #4,0 T45-1kVA T31 T31R
T45 T31 T31T45 T31 T31 T31 T31S
T31T
V
U
T30-2X600VA T38-1,11kW-220V T38 #4,0 T29 T29 T29 T29 T29 T29 T29 T29 T30 T39-1,11kW-220V T39 #4,0 T29 T29 T29 T29 2XT29 T32 T32 T46 T46 T46 T46 T46 T46 T31 T31 T31 T31O
P
Q
R
#4,0 T47-1KVA T47 #4,0 T48 #4,0 T48-1KVA T14 T49 T49 T7 T49 T49 T49 T49 T49 T49 T3 T49 T49 T49 T49 T35 T32 T49 T49 T49 T49 T49 T14 T14 T32 T32 T14 T14VACINAÇÃO
SALA DE ESPERA
SALA DE REUNIÃO E EDUCAÇÃO
I.S. MASC.
RECEPÇÃO
TRIAGEM
COLETA
CIRCULAÇÃO
GINECOLOGIA
I. S.
DML
ALMOXARIFADO
VARANDA COBERTA
I.S. FEM.
ESCOVÁRIO
RESÍDUOS
RESÍDUOS
COPA
TV SUSPENSACOMPRESSOR
VAGA PARA AMBULÂNCIA
FOSSO
ÁREA PERMEÁVEL ÁREA PERMEÁVEL
proj. da cobertura CALÇADA RUA ALÇAPÃO
LAVAGEM E
DESINFECÇÃO DE MATERIAIS
ESTERILIZAÇÃO
GUICHÊDML
proj. da coberturaSALA DE APOIO
AGENTES
ENDEMIAS
APOIO AGENTES
ENDEMIAS
SALA DE
CURATIVOS
CUIDADOS
BÁSICOS
ATENDIMENTO
MULTIPROFISSIONAL
ATENDIMENTO
MULTIPROFISSIONAL
GUARDA
MEDICAMENTOS
REBAIXO NA CALÇADA P/
ACESSO DE VEÍCULOS
REBAIXO NA CALÇADA P/
ACESSIBILIDADE
CONSULTÓRIO
ODONTOLÓGICO
VESTIÁRIO
FEMININO
ESCALA: ... 1/75
ESCALA: ... 1/75
T4 #4,0 T4 #4,0 T4 #4,0 T5 T26 T27 T28 T14 #4,0 T14 #4,0 #4,0 #4,0 T1 T2 T46 T14 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 T8 T11 #6,0 T9 T5-2X200VA T15 T43 T43 T34 #4,0 T33 T34 #4,0 T33 T34 #4,0 T34 #4,0 T33 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0 #4,0A
LEGENDA PARA PERCURSO DE CABOS (QDC-T1/A):
B
T1 T46 T2T4T14T16C
D
E
F
#4,0G
H
T1 T3 T2T4 T48 #4,0 T46 T1 T3 T2 T4 #4,0 T17 T16 T1 T8 T2T4 T48 #4,0 T17 T16 T3 T1 T3 T2T4 T18 #4,0 T17 T16 T10 T9 T8 T5 T11 T1 T3 T2T4 T19 #4,0 T17 T16 T10 T9 T8 T5 T18 T11 T1 T3 T2T4 T28 #4,0 T17 T16 T10 T9 T8 T5 T18T19T26T27 T11 T1 T3 T2T4 T28 #4,0 T17 T16 T10 T9 T8 T6 T18T19T26T27 T11 T5 T12T13I
T3 T1T2T4 T28 #4,0 T17 T16 T10 T9 T8 T6 T18T19 T26T27 T11 T5 T12T13 T24 T25J
T3 T1T2T4 T28 #4,0 T17 T16 T10 T9 T8 T6 T18T19 T26T27 T11 T5 T7 T12T13 T20 T21T24 T25K
T3 T1T2 T4 #4,0 T17 T16 T10 T9 T8 T6 T18T19 T26T27 T11 T43 T7 T12T13 T20 T21T24 T25 T28L
T3 T1T2 T4 #4,0 T17 T16 T10 T9 T8 T6T7 T12T13 T18T19T20 T21T22T24 T25T26T27T28 T11M
T3 T1T2 T4 #4,0 T17 T16 T10 T9 T8 T6T7 T12T13 T18T19T20 T21T22 T23T24 T25T26T27T28 T11N
T3 T1T2 T4 #4,0 T17 T16 T10 T9 T8 T6T7 T12T13 T18T19T20 T21T22 T23T24 T25T26T27T28T44 T11O
T3 T1T2 T4 #4,0 T17 T16 T10 T9 T8 T6T7 T12T13T15 T18T19T20 T21T22 T23T24 T25T26T27T28T44 T11P
T3 T1T2 T4 #4,0 T17 T16 T10 T9 T8 T6T7 T12T13T15 T31 T18T19T20 T21T22 T23T24 T25T26T27T28T44 T11Q
T3 T1T2 T4 #4,0 T17 T16 T10 T9 T8 T6T7 T12T13T15T29T31 T18T19T20 T21T22 T23T24 T25T26T27T28T44 T11R
T3 T1T2 T4 #4,0 T17 T16 T10 T9 T8 T6T7 T12T13T15T29T31T32 T18T19T20 T21T22 T23T24 T25T26T27T28T38T44 T11S
T3 T1T2 T4 #4,0 T17 T16 T10 T9 T8 T6T7 T12T13T15T29T30T31T32 T45 T18T19T20 T21T22 T23T24 T25T26T27T28T38T44 T11T
T3 T1T2 T4 #4,0 T17 T16 T10T12T13T15T29T30T31T32 T45 T18T19T20 T21T22 T23T24 T25T26T27T28T38T39T44 T11U
T36 T40 T41T42 #6,0 #6,0 #6,0 #6,0 #6,0 #6,0 #6,0 #6,0 #6,0 #6,0 #6,0 #6,0 #6,0 #6,0 #6,0 #6,0 #4,0 T9 T8 T6 T7 T35 T32 T37 T1 T3 T2 T4 #4,0 T17 T16 T10 T11 T18T19 T26T27 T13 T12 T24 T25 T20 T21T22 T23 T28 T44 T15T29 T31T32 T38 T45 T30 T39 T9 T8 T6 T7V
T35 T37 T36 T40 T41 T42 #6,0 T46 T46 T46 T46 T46 T46 T46 T46 T46 T16 T48 T18 T18 T48 T48 T48 T48 T48 T48 T48 T48 T48 T48 T47 T47 T47 T47 T47 T47 T47 T49 T49 T49 T49 T49 T49 T49 T48 T48 T48 T48 T48 T48 T48 T49 T47 T49 T49 T47 T49 T47 T49 T47 T49 T47 T49 T47 T49 T47 T49 T47 T49 T47 T49 T47 T49 T47 T49 T47 T49 T47 T14 T14 T14 T14 T14 T14 T14 T14 T14 T14 T14 T14 T14 T14 T14 T14 T14 T14 T14 T14 T5 T5 T5 T5 T5 T5 T5 T5 T5 T5 T5 T49 T43 T46 T43 T46 T43 T46 T43 T46 T43 T46 T43 T46 T43 T46 T43 T46 T43 T46 T43 T46 #4,0 FOLHA:03
05
ETAPA:INSTALAÇÕES ELÉTRICAS
PROJETO EXECUTIVO
PLANTAS DE TOMADAS DO 1º E
2º PAVIMENTOS
VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS
Av. Augusto de Lima, nº655
conj. 418 - Centro - BH
Telefax: (31) 3324-2702
http://www.viabile.com.br
viabile@viabile.com.br
VERIFICAÇÃO
EMISSÃO INICIAL
VIABILE
00
27/09/2012
DATA OBJETO
REVISÃO
DATA:
NOME DO ARQUIVO CAD: DESENVOLVIMENTO:
BRENO ASSIS DE OLIVEIRA
SETEMBRO/2013
UNIDADE: ESCALA:
INDICADA
MILÍMETROS
CREA: 78.667/D RESPONSÁVEL TÉCNICO:
BRENO ASSIS DE OLIVEIRA
PROPRIETÁRIO:
SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS
460-UBSSS-R05-ELE-03-PE-T1A.DWG
UBS MINAS - PROJETO MODELO
DISCIPLINA:
PROJETO:
ENDEREÇO:
CONTEÚDO:
GERENCIAMENTO E PROJETO:
3-CONFERIR MEDIDAS NO LOCAL.
2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996.
1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO.
NOTAS:
4-COTAS EM CENTÍMETROS.
SUBSECRETARIA DE INOVAÇÃO E LOGISTICA
SUPERINTENDENCIA DE GESTÃO
DIRETORIA DE GESTÃO DA REDE FÍSICA
SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE
SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA
DIRETORIA DE INFRAESTRUTURA FÍSICA
PROJETO MODELO UNIDADE BÁSICA DE SAÚDE
PROJETO DE ACORDO COM RDC-50/2002 E
É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO
COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO.
RESOLUÇÃO 1797/09 DA SES-MG
TIPO T1A - ACLIVE
abrasip-mg
Secretaria de Estado de Saúde de Minas Gerais
Cidade Administrativa Presidente Tancredo Neves
Rodovia Pref. Américo Gianetti s/nº Bairro: Serra Verde B. Hte
-Minas Gerais - CEP: 31630-900 SES-MG Predio -Minas - 12º e 13º andar
ALIMENTAÇÃO DOS PONTOS DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS
VIABILE
01
26/10/2012
EMISSÃO FINAL
VIABILE
02
08/11/2012
ADEQUAÇÃO DA ARQUITETURA CONFORME VISA
03
31/01/2013
VIABILE
READEQUAÇÃO DA ARQUITETURA E COMENTÁRIOS
04
11/09/2013
VIABILE
REVISÃO DO DETALHAMENTO
VIABILE
R
S
T
BARRA 2 - PENTE TRIFÁSICO MÍNIMO 24 PINOS - 80A TERRA
Pe R S T N
#10,0
QDC-T1/A - DIAGRAMA MULTIFILAR
BARRA 1 - IN MÍNIMO: 150A - TRIFÁSICO - Icc MÍNIMO: 10kA #10,0 #10,0 #10,0 DPS 175V CLASSE I/II 12,5kA - 10/350us 20kA - 8/20us #10,0 #10,0 #10,0 FUSÍVEL MODULAR 63A L1 16A #4,0
VEM DO PADRÃO DE ENTRADA VER PROJETO ESPECÍFICO DE ALIMENTADORES/IMPLANTAÇÃO NEUTRO DR L2 16A #4,0 40A (C) 63A (C) 63A (C) #16,0 NEUTRO #10,0 #10,0 #16,0
BARRA 3 - PENTE TRIFÁSICO MÍNIMO 24 PINOS - 80A DISJUNTOR GERAL 200A MÍNIMO DE 10kA L4 16A #2,5 R S T R S T
BARRA 4 - PENTE TRIFÁSICO MÍNIMO 24 PINOS - 80A
DETALHE SUGESTIVO DO QUADRO
QUADRO METÁLICO DE SOBREPOR C/ CAPACIDADE MÍNIMA DE 96 PÓLOS
INTERRUPTOR TETRAPOLAR DR3-In 40A SENS. 30mA TIPO AC R S T
BARRA 5 - PENTE TRIFÁSICO MÍNIMO 23 PINOS - 80A T19 16A #4,0 T17 16A #4,0 16A #4,0 16A T40 16A #4,0 T1 16A #4,0 T6 16A #4,0 T13 16A #4,0 T8 T12 T25 16A #4,0 T23 16A #4,0 T44 16A #4,0 T9 16A #4,0 T33 32A #6,0 63A (C) #16,0 T2 16A #4,0 T3 16A #4,0 T4 T5 16A #4,0 16A #4,0 16A #4,0 16A #4,0 T16 16A #4,0 T45 T18 16A #4,0 T20 16A #4,0 T21 16A #4,0 T22 16A #4,0 T24 16A #4,0 T26 16A #4,0 T27 16A #4,0 T28 16A #4,0 T29 16A #4,0 T30 16A #4,0 T37 16A #4,0 T38 #4,0 T39 T41 16A #4,0 T42 16A #4,0 16A #4,0 T46 16A #2,5 RES. T10 16A #4,0 T11 16A #6,0 T14 16A #4,0 T31 16A #4,0 T32 16A #4,0 T34 32A #6,0 T35 16A #4,0 T36 16A #4,0 RES. #10,0 T7 16A #4,0 T43 16A #2,5 #2,5 #2,5 #4,0 #4,0 L3 16A #2,5 L5 16A #4,0
RES. RES. RES.
T47 16A #4,0 T15 16A #4,0 RES. T48 16A #4,0 T49 16A #4,0 L6 16A #2,5
01 - TODOS OS DISJUNTORES DOS CIRCUITOS TERMINAIS OBEDECERÃO À NBR IEC-60.947-2
(MINI-DISJUNTORES PADRÃO EUROPEU CURVAS B, C OU D CONFORME INDICAÇÃO NOS QUADROS DE CARGAS) E SERÃO DIMENSIONADOS PARA Icc = 5,0kA/220V. OS DISJUNTORES GERAIS FORAM
DIMENSIONADOS PARA Icc >= 10kA/220V E DEVERÃO SER DO TIPO TERMOMAGNÉTICO EM CAIXA MOLDADA . 02 - TODOS OS DISJUNTORES NO INTERIOR DOS QUADROS DEVERÃO SER IDENTIFICADOS ATRAVÉS DE ETIQUETAS ACRÍLICAS DE IDENTIFICAÇÃO CONFORME NOMES DOS CIRCUITOS CONSTANTES NO QUADRO DE CARGAS.
03 - FORAM PREVISTOS ESPAÇOS RESERVAS MÍNIMOS PARA AMPLIAÇÕES FUTURAS, COM BASE NO NÚMERO DE CIRCUITOS EFETIVAMENTE INSTALADO NO QDC E DE ACORDO COM A NBR-5410:2004. 04 - O QUADRO SERÁ METÁLICO, DE SOBREPOR (PREVER ESTRUTURA NO STEEL FRAME PARA
SUSTENTAÇÃO), COM NO MÍNIMO IP-30 (EXCEÇÃO AOS QUADROS LOCALIZADOS AO TEMPO, QUE DEVERÃO POSSUIR GRAU DE PROTEÇÃO MÍNIMO IP-54), PROVIDO DE ALETAS PARA VENTILAÇÃO, PORTA DE TRINCO COM CHAVE, NÃO ESTAR INSTALADO EM ÁREAS MOLHADAS OU ÚMIDAS, LONGE DE GÁS, DOTADO DE FÁCIL ACESSO E NÃO SER OBSTRUÍDO, DEVENDO POSSUIR SOBRETUDO, CERTIFICAÇÃO DE TESTES SEGUNDO NBR IEC 60.439-1 EMITIDO POR EMPRESA ESPECIALIZADA NA MONTAGEM DE QUADROS ELÉTRICOS. 05 - O QUADRO DEVERÁ POSSUIR, ALÉM DOS DISJUNTORES TERMINAIS DESCRITOS NO QUADRO DE CARGAS, DISPOSITIVOS DR, DPS DE ENTRADA COM PROTEÇÃO BACKUP, BARRAS DE TERRA E NEUTRO, SENDO AS BARRAS DE NEUTRO PARA DR SEGREGADAS DA BARRA DE NEUTRO GERAL DO QUADRO, CONFORME LAYOUT SUGESTIVO PRESENTE NO DIAGRAMA MULTIFILAR.
06 - O QUADRO DEVERÁ POSSUIR PLACA DE MONTAGEM INTERNA NA COR LARANJA, CANALETAS PARA A PASSAGEM DE CABOS (RESPEITANDO A TAXA DE OCUPAÇÃO MÁXIMA DOS CABOS NESTAS CANALETAS, SEGUNDO ORIENTAÇÕES DA NBR-5410), BASE CONECTORA PARA A DISTRIBUIÇÃO DOS CABOS (ENTRADA E SAÍDA) E IDENTIFICAÇÃO DE NOME, TENSÃO E FREQUÊNCIA EM SUA PORTA, EM ETIQUETA ACRÍLICA DE FUNDO PRETO E LETRAS BRANCAS. TAMBÉM DEVERÁ POSSUIR UMA PLACA DE ADVERTÊNCIA INTERNA AO QUADRO, CONFORME DIZERES NESTA FOLHA. PREVER SOBRETUDO ESPAÇOS PARA DR E DPS CONFORME DETALHADO NO DIAGRAMA MULTIFILAR.
07- NO QUADRO DEVERÁ SER FIXADO, ATRAVÉS DE DISPOSITIVO PRÓPRIO, O SEU DIAGRAMA , CONTENDO TODAS AS PROTEÇÕES ENVOLVIDAS CONFORME EXECUTADO .
08- AS TERMINAÇÕES DOS ELETRODUTOS NO QUADRO ELÉTRICO DEVERÃO SER COM CONECTOR TIPO BOX RETO, COM BUCHA E ARRUELA DE ACABAMENTO, ADEQUADAS ÀS BITOLAS DO MESMO. AS ELETROCALHAS DEVERÃO SER PROVIDAS DE FLANGES PRÉ-MOLDADOS CONFORME DIMENSÕES DE PROJETO.
09- AS TERMINAÇÕES DOS CABOS NO QUADRO ELÉTRICO DEVERÃO RECEBER TEMINAL DO TIPO AGULHA PARA CONEXÃO COM OS BORNES DOS DISJUNTORES E TERMINAL TIPO OLHAL PARA CONEXÃO AOS BARRAMENTOS. TODOS OS TERMINAIS DEVERÃO SER COMPRIMIDOS ATRAVÉS DE FERRAMENTA ADEQUADA.
10- O QUADRO DEVERÁ ESTAR LIMPO, LIVRE DE ARGAMASSAS, POEIRA, CAPA DE CABOS, FILAMENTOS DE CABOS DE COBRE E OUTROS MATERIAIS ESTRANHOS À INSTALAÇÃO.
11- OS TERMINAIS DAS BARRAS DE CONEXÃO NÃO UTILIZADOS DEVERÃO SER ISOLADOS POR CAPA PROTETORA ADEQUADA, DO MESMO FABRICANTE DAS BARRAS DE CONEXÃO .
12- TODOS OS CABOS ALIMENTADORES DOS CIRCUITOS INTERNOS AO QUADRO SERÃO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA 70 ºC 750V. DEVERÃO SOBRETUDO,RECEBER ETIQUETAS DE IDENTIFICAÇÃO (TAG´s), INDELÉVEIS, COM INDICAÇÃO DO CIRCUITO A QUE ESTÁ LIGADO, CONFORME DESCRIÇÃO DO CAMPO "CIRCUITO" DO QUADRO DE CARGAS
CORRESPONDENTE.
13 - ATERRAR TODAS AS PORTAS DOS QUADROS ATRAVÉS DE CABO DE COBRE #6,0mm² ISOLAÇÃO VERDE EM PVC 70°C 750V.
INTERRUPTOR DIFERENCIAL RESIDUAL (IDR). CARACTERÍSTICAS TÉCNICAS:
- TIPO AC;
- CORRENTE NOMINAL (In): CONFORME INDICAÇÃO;
- SENSIBILIDADE: 30mA; TENSÃO MÁXIMA: 415Vca TETRAPOLAR; FREQUÊNCIA: 60Hz.
SIMBOLOGIA P/ QUADRO:
CABO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA, 70°C 750V, CLASSE 5 DE ENCORDOAMENTO (FASES - COR PRETA). DISPOSITIVO PROTETOR DE SURTOS (DPS) PARA FASES. CARACTERÍSTICAS TÉCNICAS DOS DPS's CLASSE I E CLASSE II, SEGUNDO NBR5410:
- OBEDECER A NBR IEC 61.643-1; Up (NÍVEL DE PROTEÇÃO): INFERIOR A 1,5kV;
- Uc (MÁXIMA TENSÃO DE OPERAÇÃO CONTÍNUA): 175V; - Iimp (CORRENTE DE IMPULSO): SUPERIOR A 12,5kA (10/350us); - In (CORRENTE NOMINAL DE DESCARGA): SUPERIOR A 20kA (8/20us) PARA REDES TRIFÁSICAS;
UTILIZAR NAS FASES COMO PROTEÇÃO BACKUP, FUSÍVEIS MODULARES NH-63A gG/gL.
DISJUNTORES TERMO-MAGNÉTICOS (MINI DISJUNTORES), CURVAS B, C OU D CONFORME INDICAÇÃO NOS QUADROS, SEGUNDO A NORMA IEC-60947-2 E DIMENSIONADOS PARA Icc = 5,0kA/220V( MONOPOLAR, BIPOLAR E TRIPOLAR, RESPECTIVAMENTE).
DISJUNTOR GERAL:
- TIPO EM CAIXA MOLDADA, TERMOMAGNÉTICO E DIMENSIONADOS PARA Icc MÍNIMO = 10,0kA/220V.
CABO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA, 70°C 750V, CLASSE 5 DE ENCORDOAMENTO (NEUTRO - COR AZUL CLARO).
CABO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA, 70°C 750V, CLASSE 5 DE ENCORDOAMENTO (TERRA - COR VERDE).
NOTAS GERAIS DOS QUADROS:
1- QUANDO UM DISJUNTOR OU
FUSÍVEL ATUA, DESLIGANDO ALGUM CIRCUITO OU A
INSTALAÇÃO INTEIRA, A CAUSA PODE SER UMA SOBRECARGA OU UM CURTO-CIRCUITO.
DESLIGAMENTOS FREQUENTES
SÃO SINAL DE SOBRECARGA. POR ISSO, NUNCA TROQUE
SEUS DISJUNTORES OU
FUSÍVEIS POR OUTRO DE MAIOR CORRENTE (MAIOR AMPERAGEM)
SIMPLESMENTE. COMO REGRA, A TROCA DE UM DISJUNTOR OU
FUSÍVEL POR OUTRO DE
MAIOR CORRENTE REQUER, ANTES, A TROCA DOS FIOS E CABOS
ELÉTRICOS, POR OUTROS
DE MAIOR SEÇÃO (BITOLA).
2- DA MESMA FORMA, NUNCA DESATIVE OU REMOVA A CHAVE
AUTOMÁTICA DE PROTEÇÃO
CONTRA CHOQUES
ELÉTRICOS (DISPOSITIVOS DR), MESMO EM CASO DE DESLIGAMENTOS
SEM CAUSA APARENTE. SE OS DESLIGAMENTOS FOREM FREQUENTES E, PRINCIPALMENTE,
SE AS TENTATIVAS DE RELIGAR A CHAVE
NÃO TIVEREM ÊXITO, ISSO SIGNIFICA, MUITO
PROVAVELMENTE, QUE A
INSTALAÇÃO ELÉTRICA APRESENTA ANOMALIAS INTERNAS, QUE
SÓ PODEM SER IDENTIFICADAS E CORRIGIDAS POR PROFISSIONAIS QUALIFICADOS. A
DESATIVAÇÃO OU REMOÇÃO DA CHAVE SIGNIFICA A ELIMINAÇÃO DE MEDIDA PROTETORA
CONTRA CHOQUES ELÉTRICOS E RISCO DE VIDA PARA OS USUÁRIOS DA INSTALAÇÃO.
DETALHE DA ADVERTÊNCIA SEGUNDO A NBR 5410
A SER FIXADA NO INTERIOR DO QUADRO ELÉTRICO
ADVERTÊNCIA
ATÉ 6
2
7 A 12
3
13 A 30
4
N>30
0,15xN
QUANTIDADE DE CIRCUITOS
EFETIVAMENTE DISPONÍVEL
N
ESPAÇO MÍNIMO DESTINADO A
RESERVA (EM NÚMEROS DE
CIRCUITOS)
TABELA 1: ESPAÇO RESERVA
FOLHA:
04
05
ETAPA:INSTALAÇÕES ELÉTRICAS
PROJETO EXECUTIVO
QDC-T1/A
DIAGRAMA MULTIFILAR
VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS
Av. Augusto de Lima, nº655
conj. 418 - Centro - BH
Telefax: (31) 3324-2702
http://www.viabile.com.br
viabile@viabile.com.br
VERIFICAÇÃO
EMISSÃO INICIAL
VIABILE
00
27/09/2012
DATA OBJETO
REVISÃO
DATA:
NOME DO ARQUIVO CAD: DESENVOLVIMENTO:
BRENO ASSIS DE OLIVEIRA
SETEMBRO/2013
UNIDADE: ESCALA:
INDICADA
MILÍMETROS
CREA: 78.667/D RESPONSÁVEL TÉCNICO:
BRENO ASSIS DE OLIVEIRA
PROPRIETÁRIO:
SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS
460-UBSSS-R05-ELE-04-PE-T1A.DWG
UBS MINAS - PROJETO MODELO
DISCIPLINA:
PROJETO:
ENDEREÇO:
CONTEÚDO:
GERENCIAMENTO E PROJETO:
3-CONFERIR MEDIDAS NO LOCAL.
2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996.
1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO.
NOTAS:
4-COTAS EM CENTÍMETROS.
SUBSECRETARIA DE INOVAÇÃO E LOGISTICA
SUPERINTENDENCIA DE GESTÃO
DIRETORIA DE GESTÃO DA REDE FÍSICA
SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDE
SUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA
DIRETORIA DE INFRAESTRUTURA FÍSICA
PROJETO MODELO UNIDADE BÁSICA DE SAÚDE
PROJETO DE ACORDO COM RDC-50/2002 E
É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO
COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO.
RESOLUÇÃO 1797/09 DA SES-MG
TIPO T1A - ACLIVE
abrasip-mg
Secretaria de Estado de Saúde de Minas Gerais
Cidade Administrativa Presidente Tancredo Neves
Rodovia Pref. Américo Gianetti s/nº Bairro: Serra Verde B. Hte
-Minas Gerais - CEP: 31630-900 SES-MG Predio -Minas - 12º e 13º andar
ALIMENTAÇÃO DOS PONTOS DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS
VIABILE
01
26/10/2012
EMISSÃO FINAL
VIABILE
02
08/11/2012
ADEQUAÇÃO DA ARQUITETURA CONFORME VISA
VIABILE
03
01/02/2013
READEQUAÇÃO DA ARQUITETURA E COMENTÁRIOS
VIABILE
04
11/09/2013
REVISÃO DO DETALHAMENTO
VIABILE
QDC-T1/A – RELAÇÃO DE CARGAS E MEMÓRIA DE CÁLCULO CIRCUITO DESCRIÇÃO 16 32 23 25 50 85 170 510 850 1530 6500 1110 L1 4 42 0 0 0 0 0 0 0 0 0 0 L2 6 30 0 0 0 0 0 0 0 0 0 0 L3 22 2 1 0 0 0 0 0 0 0 0 0 L4 0 12 0 0 0 0 0 0 0 0 0 0 L5 0 20 0 0 0 0 0 0 0 0 0 0
L6 ILUMINAÇÃO VARANDA COBERTA, ARANDELAS EXTERNAS 0 0 12 0 0 0 0 0 0 0 0 0
L7 RESERVA 0 0 0 0 0 0 0 0 0 0 0 0
L8 RESERVA 0 0 0 0 0 0 0 0 0 0 0 0
T1 TOMADAS SALA DE ESPERA/ VACINAÇÃO – 1º PAVTO. 0 0 0 0 0 5 0 1 0 0 0 0
T2 TOMADAS VACINAÇÃO – 1º PAVTO. 0 0 0 0 0 0 2 1 0 0 0 0
T3 TOMADAS RECEPÇÃO – 1º PAVTO. 0 0 0 0 0 0 4 0 0 0 0 0
T4 TOMADAS TRIAGEM/ COLETA – 1º PAVTO. 0 0 0 0 0 3 4 0 0 0 0 0
T5 TOMADAS ATENDIMENTO MULTIPROFISSIONAL 1 – 1º PAVTO. 0 0 0 0 0 3 2 0 0 0 0 0
T6 TOMADAS ATENDIMENTO MULTIPROFISSIONAL 2 – 1º PAVTO. 0 0 0 0 0 3 2 0 0 0 0 0
T7 TOMADAS CUIDADOS BÁSICOS/ RESÍDUOS – 1º PAVTO. 0 0 0 0 0 6 2 0 0 0 0 0
T8 TOMADAS SALA DE REUNIÃO – 1º PAVTO. 0 0 0 0 0 5 0 0 0 0 0 0
T9 TOMADAS SALA DE REUNIÃO – 1º PAVTO. 0 0 0 0 0 2 0 1 0 0 0 0
T10 TOMADA GELADEIRA SALA DE REUNIÃO – 1º PAVTO. 0 0 0 0 0 0 0 1 0 0 0 0
T11 TOMADA MICRO-ONDAS SALA DE REUNIÃO – 1º PAVTO. 0 0 0 0 0 0 0 0 0 1 0 0
T12 TOMADAS GINECOLOGIA – 1º PAVTO. 0 0 0 0 0 4 2 0 0 0 0 0
T13 TOMADAS SALA DE CURATIVOS/ GUARDA MEDICAMENTOS – 1º PAVTO. 0 0 0 0 0 4 2 0 0 0 0 0
T14 0 0 0 0 2 8 0 0 0 0 0 0
T15 PONTO DE FORÇA COMPRESSOR – 1º PAVTO. 0 0 0 0 0 0 0 0 0 0 0 0
T16 PONTO DE FORÇA AR-CONDICIONADO VACINAÇÃO – 1º PAVTO. 0 0 0 0 0 0 0 0 0 0 0 1
T17 PONTO DE FORÇA AR-CONDICIONADO TRIAGEM – 1º PAVTO. 0 0 0 0 0 0 0 0 0 0 0 1
T18 PONTO DE FORÇA AR-CONDICIONADO COLETA – 1º PAVTO. 0 0 0 0 0 0 0 0 0 0 0 1
T19 0 0 0 0 0 0 0 0 0 0 0 1
T20 0 0 0 0 0 0 0 0 0 0 0 1
T21 PONTO DE FORÇA AR-CONDICIONADO CUIDADOS BÁSICOS 1 – 1º PAVTO. 0 0 0 0 0 0 0 0 0 0 0 1
T22 PONTO DE FORÇA AR-CONDICIONADO CUIDADOS BÁSICOS 2 – 1º PAVTO. 0 0 0 0 0 0 0 0 0 0 0 1
T23 PONTO DE FORÇA AR-CONDICIONADO SALA DE CURATIVOS – 1º PAVTO. 0 0 0 0 0 0 0 0 0 0 0 1
T24 PONTO DE FORÇA AR-CONDICIONADO GINECOLOGIA – 1º PAVTO. 0 0 0 0 0 0 0 0 0 0 0 1
T25 PONTO DE FORÇA AR-CONDICIONADO GUARDA MEDICAMENTOS – 1º PAVTO. 0 0 0 0 0 0 0 0 0 0 0 1
T26 PONTO DE FORÇA AR-CONDICIONADO SALA DE REUNIÃO 1 – 1º PAVTO. 0 0 0 0 0 0 0 0 0 0 0 1
T27 PONTO DE FORÇA AR-CONDICIONADO SALA DE REUNIÃO 2 – 1º PAVTO. 0 0 0 0 0 0 0 0 0 0 0 1
T28 PONTO DE FORÇA AR-CONDICIONADO SALA DE ESPERA – 1º PAVTO. 0 0 0 0 0 0 0 0 0 0 0 1
T29 TOMADAS CONSULTÓRIO ODONTOLÓGICO – 2º PAVTO. 0 0 0 0 0 9 0 0 0 0 0 0
T30 TOMADAS CONSULTÓRIO ODONTOLÓGICO – 2º PAVTO. 0 0 0 0 0 0 0 2 0 0 0 0
T31 0 0 0 0 0 7 0 0 0 0 0 0
T32 0 0 0 0 0 10 0 0 0 0 0 0
T33 PONTO DE FORÇA CHUVEIRO VESTIÁRIO MASCULINO – 220V – 2º PAVTO. 0 0 0 0 0 0 0 0 0 0 1 0
T34 PONTO DE FORÇA CHUVEIRO VESTIÁRIO FEMININO – 220V – 2º PAVTO. 0 0 0 0 0 0 0 0 0 0 1 0
T35 TOMADAS COPA – 2º PAVTO. 0 0 0 0 0 4 0 1 0 0 0 0
T36 TOMADA COPA – MICROONDAS – 2º PAVTO. 0 0 0 0 0 0 0 0 0 1 0 0
T37 TOMADAS AGENTES DE SAÚDE – 2º PAVTO. 0 0 0 0 0 3 4 0 0 0 0 0
T38 0 0 0 0 0 0 0 0 0 0 0 1
T39 0 0 0 0 0 0 0 0 0 0 0 1
T40 PONTO DE FORÇA AR-CONDICIONADO ESTERILIZAÇÃO – 2º PAVTO. 0 0 0 0 0 0 0 0 0 0 0 1
T41 0 0 0 0 0 0 0 0 0 0 0 1
T42 PONTO DE FORÇA AR-CONDICIONADO AGENTES DE SAÚDE – 2º PAVTO. 0 0 0 0 0 0 0 0 0 0 0 1
T43 TOMADA DML-1° PAVTO 0 0 0 0 0 1 0 0 0 0 0 0
T44 PONTO DE FORÇA PARA PLATAFORMA ELEVATÓRIA – TRIFÁSICO 220V 0 0 0 0 0 0 0 0 0 0 0 0
T45 PONTO DE FORÇA AUTOCLAVE 0 0 0 0 0 0 0 0 1 0 0 0
T46 BLOCO AUTONOMO 0 0 0 9 0 0 0 0 0 0 0 0
T47 TOMADA RACK 0 0 0 0 0 0 0 0 1 0 0 0
T48 TOMADA RACK SONORIZAÇÃO 0 0 0 0 0 0 0 0 1 0 0 0
ILUMINAÇÃO (W) BLOCO AUTONOMO (W) SINALIZAÇÃO (W) TOMADAS (W) CHUVEIROS (W) AR CONDICIONADO (W) ILUMINAÇÃO VACINAÇÃO,SALA DE
ESPERA, RECEPÇÃO, TRIAGEM, COLETA, SALA DE REUNIÃO E EDUCAÇÃO, ATENDIMENTO MULTIPROFISSIONAL 1
ILUMINAÇÃO ATENDIMENTO MULTIPROFISSIONAL 2, GUARDA MEDICAMENTOS, GINECOLOGIA, CUIDADOS BÁSICOS URGÊNCIA E
EMERGÊNCIA, SALA DE CURATIVOS, RESÍDUOS 1, RESÍDUOS 2, COMPRESSOR ILUMINAÇÃO CIRCULAÇÃO, BANHEIROS, APOIO AGENTE ENDEMIAS, DML, ARANDELAS EXTERNAS, VARANDA COBERTA
ESCOVÁRIO, CONSULTÓRIO ODONTOLÓGICO, AGENTES DE SAÚDE, ALMOXARIFADO
COPA, VESTIÁRIO MASCULINO, VESTIÁRIO FEMININO, LAVAGEM E DESINFECÇÃO DE MATERIAIS, ESTERILIZAÇÃO, DML, CIRCULAÇÃO
TOMADAS I.S./ SALA DE APOIO AGENTES ENDEMIAS/ CIRCULAÇÃO/ BEBEDOURO – 1º PAVTO.
PONTO DE FORÇA AR-CONDICIONADO ATENDIMENTO MULTIPROFISSIONAL 1 – 1º PAVTO.
PONTO DE FORÇA AR-CONDICIONADO ATENDIMENTO MULTIPROFISSIONAL 2 – 1º PAVTO.
TOMADAS ESCOVÁRIO/ DML/ ALMOXARIFADO/ ESTERILIZAÇÃO – 2º PAVTO.
TOMADAS LAVAGEM E DESINFECÇÃO DE MATERIAIS/ CIRCULAÇÃO/ VESTIÁRIO MASC. E FEM./ BEBEDOURO – 2º PAVTO.
PONTO DE FORÇA AR-CONDICIONADO CONSULTÓRIO ODONTOLÓGICO 1 – 2º PAVTO.
PONTO DE FORÇA AR-CONDICIONADO CONSULTÓRIO ODONTOLÓGICO 2 – 2º PAVTO.
PONTO DE FORÇA AR-CONDICIONADO LAVAGEM E DESINFECÇÃO DE MATERIAIS – 2º PAVTO.
F.P. POTÊNCIA TOTAL TENSÃO FASES EQUILÍBRIO
PROTEÇÃO
P In CURVA
1471 850 (kW) (kVA) (V) R S T (A) (A)
0 0 0,95 1,41 1,48 220 RS 0,74 0,74 0,00 6,74 2 x 16 C 0 0 0,95 1,06 1,11 220 TR 0,56 0,00 0,56 5,05 2 x 16 C 0 0 0,95 0,44 0,46 220 ST 0,00 0,23 0,23 2,10 2 x 16 C 0 0 0,95 0,38 0,40 220 RS 0,20 0,20 0,00 1,84 2 x 16 C 0 0 0,95 0,64 0,67 220 TR 0,34 0,00 0,34 3,06 2 x 16 C 0 0 0,95 0,28 0,29 220 RS 0,15 0,15 0,00 1,32 2 x 16 C 0 0 0,95 0,00 0,00 127 S 0,00 0,00 0,00 0,00 1 x 16 C 0 0 0,95 0,00 0,00 127 T 0,00 0,00 0,00 0,00 1 x 16 C 0 0 0,85 0,94 1,10 127 R 1,10 0,00 0,00 8,66 1 x 16 C 0 0 0,85 0,85 1,00 127 S 0,00 1,00 0,00 7,87 1 x 16 C 0 0 0,85 0,68 0,80 127 T 0,00 0,00 0,80 6,30 1 x 16 C 0 0 0,85 0,94 1,10 127 R 1,10 0,00 0,00 8,66 1 x 16 C 0 0 0,85 0,60 0,70 127 S 0,00 0,70 0,00 5,51 1 x 16 C 0 0 0,85 0,60 0,70 127 T 0,00 0,00 0,70 5,51 1 x 16 C 0 0 0,85 0,85 1,00 127 R 1,00 0,00 0,00 7,87 1 x 16 C 0 0 0,85 0,43 0,50 127 S 0,00 0,50 0,00 3,94 1 x 16 C 0 0 0,85 0,68 0,80 127 R 0,80 0,00 0,00 6,30 1 x 16 C 0 0 0,85 0,51 0,60 127 S 0,00 0,60 0,00 4,72 1 x 16 C 0 0 0,85 1,53 1,80 127 T 0,00 0,00 1,80 14,17 1 x 16 C 0 0 0,85 0,68 0,80 127 T 0,00 0,00 0,80 6,30 1 x 16 C 0 0 0,85 0,68 0,80 127 R 0,80 0,00 0,00 6,30 1 x 16 C 0 0 0,85 0,78 0,92 127 R 0,92 0,00 0,00 7,23 1 x 16 C 0 1 0,85 0,85 1,00 220 ST 0,00 0,50 0,50 4,55 2 x 16 C 0 0 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 2 x 16 C 0 0 0,85 1,11 1,31 220 TR 0,65 0,00 0,65 5,94 2 x 16 C 0 0 0,85 1,11 1,31 220 ST 0,00 0,65 0,65 5,94 2 x 16 C 0 0 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 2 x 16 C 0 0 0,85 1,11 1,31 220 TR 0,65 0,00 0,65 5,94 2 x 16 C 0 0 0,85 1,11 1,31 220 ST 0,00 0,65 0,65 5,94 2 x 16 C 0 0 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 2 x 16 C 0 0 0,85 1,11 1,31 220 TR 0,65 0,00 0,65 5,94 2 x 16 C 0 0 0,85 1,11 1,31 220 ST 0,00 0,65 0,65 5,94 2 x 16 C 0 0 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 2 x 16 C 0 0 0,85 1,11 1,31 220 TR 0,65 0,00 0,65 5,94 2 x 16 C 0 0 0,85 1,11 1,31 220 ST 0,00 0,65 0,65 5,94 2 x 16 C 0 0 0,85 1,11 1,31 220 ST 0,00 0,65 0,65 5,94 2 x 16 C 0 0 0,85 0,77 0,90 127 T 0,00 0,00 0,90 7,09 1 x 16 C 0 0 0,85 1,02 1,20 127 R 1,20 0,00 0,00 9,45 1 x 16 C 0 0 0,85 0,60 0,70 127 S 0,00 0,70 0,00 5,51 1 x 16 C 0 0 0,85 0,85 1,00 127 T 0,00 0,00 1,00 7,87 1 x 16 C 0 0 1,00 6,50 6,50 220 RS 3,25 3,25 0,00 29,55 2 x 32 C 0 0 1,00 6,50 6,50 220 TR 3,25 0,00 3,25 29,55 2 x 32 C 0 0 0,85 0,85 1,00 127 S 0,00 1,00 0,00 7,87 1 x 16 C 0 0 0,85 1,53 1,80 127 T 0,00 0,00 1,80 14,17 1 x 16 C 0 0 0,85 0,94 1,10 127 S 0,00 1,10 0,00 8,66 1 x 16 C 0 0 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 2 x 16 C 0 0 0,85 1,11 1,31 220 TR 0,65 0,00 0,65 5,94 2 x 16 C 0 0 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 2 x 16 C 0 0 0,85 1,11 1,31 220 TR 0,65 0,00 0,65 5,94 2 x 16 C 0 0 0,85 1,11 1,31 220 ST 0,00 0,65 0,65 5,94 2 x 16 C 0 0 0,85 0,09 0,10 127 S 0,00 0,10 0,00 0,79 1 x 16 C 1 0 0,85 1,47 1,73 220 RST 0,58 0,58 0,58 4,54 3 x 16 C 0 0 0,85 0,85 1,00 127 T 0,00 0,00 1,00 7,87 1 x 16 C 0 0 0,85 0,23 0,26 127 R 0,26 0,00 0,00 2,08 1 x 16 C 0 0 0,85 0,85 1,00 127 S 0,00 1,00 0,00 7,87 1 x 16 C 0 0 0,85 0,85 1,00 127 T 0,00 0,00 1,00 7,87 1 x 16 C PLATAFORMA ELEVATÓRIA (W) COMPRESSOR (W) CORRENTE NOMINAL MEMÓRIA DE CÁLCULO QUEDA DE TENSÃO LIMITE: (m) 3,00% 4,0 40 1,05% 4,0 30 0,59% 2,5 45 0,59% 2,5 18 0,21% 4,0 14 0,17% 2,5 63 0,52% 4,0 44 0,00% 4,0 44 0,00% 4,0 44 2,58% 4,0 44 2,35% 4,0 42 1,79% 4,0 40 2,35% 4,0 37 1,38% 4,0 32 1,19% 4,0 29 1,55% 4,0 40 1,07% 4,0 41 1,75% 4,0 41 1,31% 6,0 41 2,62% 4,0 32 1,36% 4,0 33 1,41% 4,0 48 2,35% 4,0 20 0,36% 4,0 43 1,00% 4,0 39 0,90% 4,0 39 0,90% 4,0 32 0,74% 4,0 32 0,74% 4,0 29 0,67% 4,0 24 0,56% 4,0 28 0,65% 4,0 33 0,77% 4,0 34 0,79% 4,0 36 0,84% 4,0 36 0,84% 4,0 36 0,84% 4,0 15 0,72% 4,0 9 0,58% 4,0 22 0,82% 4,0 11 0,59% 4,0 13 1,50% 4,0 15 1,73% 4,0 16 0,85% 4,0 15 1,44% 4,0 17 1,00% 4,0 15 0,35% 4,0 12 0,28% 4,0 14 0,32% 4,0 14 0,32% 4,0 14 0,32% 2,5 11 0,09% 4,0 15 0,23% 4,0 10 0,53% 2,5 50 1,13% 4,0 40 2,13% 4,0 40 2,13% CONDUTOR (mm²) COMPRIMENTO MÁXIMO DO CIRCUITO QUEDA DE TENSÃO EFETIVA T49 TOMADAS CFTV 0 0 0 0 0 7 0 0 0 0 0 0 TOTAL 32,00 106,00 13,00 9,00 2,00 84,00 24,00 7,00 3,00 2,00 2,00 18,00 0 0 0,85 0,60 0,70 127 S 0,00 0,70 0,00 5,51 1 x 16 C 4,0 40 1,49% 1,00 1,00 0,89 60,23 68,04 220 RST 24,08 20,88 23,09 178,78 3 x 200 D - - -FOLHA:
05
05
ETAPA:INSTALAÇÕES ELÉTRICAS
PROJETO EXECUTIVO
QDC-T1/A
QUADRO DE CARGAS
VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS
Av. Augusto de Lima, nº655
conj. 418 - Centro - BH
Telefax: (31) 3324-2702
http://www.viabile.com.br
viabile@viabile.com.br
VERIFICAÇÃO
EMISSÃO INICIAL
VIABILE
00
27/09/2012
DATA OBJETO
REVISÃO
DATA:
NOME DO ARQUIVO CAD: DESENVOLVIMENTO:
BRENO ASSIS DE OLIVEIRA
SETEMBRO/2013
UNIDADE: ESCALA:
INDICADA
MILÍMETROS
CREA: 78.667/D RESPONSÁVEL TÉCNICO:
BRENO ASSIS DE OLIVEIRA
PROPRIETÁRIO:
SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS
460-UBSSS-R05-ELE-05-PE-T1A.DWG
UBS MINAS - PROJETO MODELO
DISCIPLINA:
PROJETO:
ENDEREÇO:
CONTEÚDO:
GERENCIAMENTO E PROJETO: