2. EXTERNAL DIMENSIONS

1347

Intake air

Front view

Refrigerant service valve <gas>

Refrigerant service valve <liquid>

Intake air

Intake air

Discharge air Left side view Rear view

Refrigerant service valve <gas>

Refrigerant service valve <liquid>

2

5 6 8

(Mounting pitch)

Bottom view

(Mounting pitch)

2×5-ø4.6 Hole (Make hole at the plastic fan guard for snow hood attachment) <Snow hood attachment hole>

T op view

Sling hole Detachable leg (front and back, 2 points) Note 2*

2×2-14×31 Oval hole 2×2-14×20 Oval hole(without detachable leg)

Intake air

Service panel

Control box (INV Box)Control box (MAIN Box)

Model

Diameter Refrigerant pipe Service valve For transmission cables

For wires

For pipes

UsageNO.Specifications Front through hole Bottom through hole Front through hole Front through holeBottom through hole Bottom through holeFront through hole

148 × 84 Knockout hole ø65 or ø40 Knockout hole ø52 or ø27 Knockout hole ø65 Knockout hole ø52 Knockout hole ø34 Knockout hole

150 × 94 Knockout hole

P250ø9.52ø22.2 Brazed

ø9.52 Brazed ø22.2

P200

Connecting pipe specifications LiquidGasLiquidGas ø9.52 Brazed (ø12.7 Brazed) *1,*3 ø34 Knockout hole

Note 1.Please refer to the next page for information regarding necessary spacing around the unit and foundation work. 2.The detachable leg can be removed at site. 3.At brazing of pipes, wrap the refrigerant service valve with wet cloth and keep the temperature of refrigerant service valve under 120°C. ø9.52 Brazed (ø12.7 Brazed) *1,*2,*4 *1 Connect the refrigerant pipe to the service valve according to the Installation Manual. *2 Indicates dimensions and connection specifications in the case the unit is used in combination with other outdoor units. *3 Furthest piping length (OU from IU)≥90m *4 Furthest piping length (OU from IU)≥40m Bottom through hole

P300 132 207 256

148125

90 110 125 1495

303

1798 (60)

1858

565620 54592

110 185

681(678~684) 29.5

(740)

8076080

166 181

152172

216 160243

150128

94 79

198 29.5

84 71

35 92019.519.5881

740

150

600=150×4 70

54

20

116 (60)

1 2 43 5 6 7 8

PUHY-P200, 250, 300YNW-A1 (-BS) Unit: mm

PUHY-P-Y(S)NW-A1

2. EXTERNAL DIMENSIONS

Y-Series

Front Front <T op view> <Unit:mm> <T op view> <Side view> M10 anchor bolt <field supply required> Fixing plate <field supply required>

<To be left open>

Front W all <H>

<T o be left open>

Front

<Unit:mm> Fixing plate <field supply required> M10 anchor bolt <field supply required>

W all <H>

<To be left open>

<To be left open>

<To be left open>

Front W all <H>

W all <H>

Wall <H>

Wall <H>

Front Front

<T o be left open> W all <H> Front W all <H>

<To be left open>

<To be left open>

Front Front Front

W all <H> W all <H> Front

<To be left open>

<T o be left open> Detachable leg Fig.A (without detachable legs) Fig.B (with detachable legs)

Fig.C (without detachable legs) Fig.D (with detachable legs)

Detachable leg

1.Required space around the unit ●In case of single installation 1 Secure enough space around the unit as shown in the figure below . · With a space of at least 2 When the height of the walls on the front, back or on the sides<H> 2.Foundation work 1 Take into consideration the surface strength, water drainage route, piping route, and wiring route when preparing the installation site. <Note that the drain water comes out of the unit during operation.> 2 Build the foundation in such way that the corner of the installation leg is securely supported as shown in the right figure.(Fig.A,B) When using a rubber isolating cushion, please ensure it is large enough to cover the entire width of each of the unit's legs. 3 The protrusion length of the anchor bolt must not exceed 30mm.(Fig.A,B) 4 Use four fixing plates as shown in the right figure <field supply required> when using post-installed anchor bolts.(Fig.C,D) 5 To prevent small animals and water and snow from entering the unit and damaging its parts, close the gap around the edges of through holes for pipes and wires with filler plates <field supply required>. 6 When the pipes or cables are routed at the bottom of the unit, make sure that the through hole at the base of the unit does not get blocked with the installation base. 7 Refer to the Installation Manual when installing units on an installation base.

●In case of collective installation 1 When multiple units are installed adjacent to each other , secure enough space to allow for air circulation and walkway between groups of units as shown in the figures below . 2 At least two sides must be left open. 3 As with the single installation, add the height that exceeds the height limit<h> to the figures that are marked with an asterisk. 4 If there is a wall at both the front and the rear of the unit, install up to six units consecutively in the side direction and provide a space of 1000mm or more as inlet space/ passage space for each six units.

300mm to the wall on the back of the unit

· With a space of at least 100mm to the wall on the back of the unit exceeds the wall height limit as defined below add the height that exceeds the height limit <h> to the figures that are marked with an asterisk. 15 min.* 15 min.* 50 min.* 50 min.*

300 min.

*

100 min. 30 min. 450 min.* 450 min. 450 min. 100 min.*

450 min.

*

100 min.

* *

450 min.

1000 min.*

900 min.

900 min.

min.*

300

min.*

300

min.*

300

15 min.

*

450 min. 450 min.

450 min.

*

300 min.

*

450 min.

*

100 min.

*

30mm max. 30mm max.

<W all height limit> Front : Up to the unit height Back : Up to the unit height Side   : Up to the unit height

Front

Unit height h

H Unit height h

H

Unit: mm

PUHY-P200, 250, 300YNW-A1 (-BS)

PUHY-P-Y(S)NW-A1

2. EXTERNAL DIMENSIONS

Y-Series

5 6 8

Refrigerant service valve <gas>

Refrigerant service valve <liquid>

Refrigerant service valve <gas>

Refrigerant service valve <liquid>

(Mounting pitch)

Bottom view

(Mounting pitch)

2×2-14×31 Oval hole 2×2-14×20 Oval hole(without detachable leg)

Sling hole Detachable leg (front and back, 2 points) Note 2*

Control box

Service panel

Intake airIntake air

Discharge air Intake airIntake air

2×6-ø4.6 Hole (Make hole at the plastic fan guard for snow hood attachment) <Snow hood attachment hole>

T op view Front view Rear view Left side view

For transmission cables

For wires

For pipes

UsageSpecifications Front through hole Bottom through hole Front through hole Front through holeBottom through hole Bottom through holeFront through hole

148 × 84 Knockout hole ø65 or ø40 Knockout hole ø52 or ø27 Knockout hole ø65 Knockout hole ø52 Knockout hole ø34 Knockout hole 150 × 94 Knockout hole

Connecting pipe specifications ø34 Knockout hole

Note 1.Please refer to the next page for information regarding necessary spacing around the unit and foundation work. 2.The detachable leg can be removed at site. 3.At brazing of pipes, wrap the refrigerant service valve with wet cloth and keep the temperature of refrigerant service valve under 120°C. *1 Connect the refrigerant pipe to the service valve according to the Installation Manual. *2 Indicates dimensions and connection specifications in the case the unit is used in combination with other outdoor units. (Except for P650) Bottom through hole

Model

Diameter Refrigerant pipe Service valve P400ø12.7

ø12.7 Brazed ø28.58

P350LiquidGasLiquidGas ø12.7 Brazed (ø15.88 Brazed) *1,*2ø28.58 Brazed ø15.88 Brazed *1 P450

740

70 150 85

85 130

150

18120418 1240

110

(740)

185

29.5 681(678~684) 29.5

79 94 179 181

160

243

150128

125

132 207 256

90 110

84 71

35

56

116 (60)

20 5459254

2056 148 152216

166 125

(60)

303 1495

1798 1858

90106090

172

NO. 1 2 43 5 6 7 8

1347 2

PUHY-P350, 400, 450YNW-A1 (-BS) Unit: mm

PUHY-P-Y(S)NW-A1

2. EXTERNAL DIMENSIONS

Y-Series

Front Front <T op view> <Unit:mm> <T op view> M10 anchor bolt <field supply required> Fixing plate <field supply required>

<T o be left open>

Front W all <H>

<T o be left open>

Front

<Unit:mm> Fixing plate <field supply required> M10 anchor bolt <field supply required>

W all <H>

<T o be left open>

<T o be left open>

<T o be left open>

Front W all <H>

W all <H>

Wall <H>

Wall <H>

Front Front

<T o be left open> W all <H> Front W all <H>

<T o be left open>

<T o be left open>

Front Front Front

W all <H> W all <H> Front

<T o be left open>

<T o be left open> Detachable leg Fig.A (without detachable legs) Fig.B (with detachable legs)

Fig.C (without detachable legs) Fig.D (with detachable legs)

1.Required space around the unit ●In case of single installation 1 Secure enough space around the unit as shown in the figure below . · With a space of at least 2 When the height of the walls on the front, back or on the sides<H> 2.Foundation work 1 Take into consideration the surface strength, water drainage route, piping route, and wiring route when preparing the installation site. <Note that the drain water comes out of the unit during operation.> 2 Build the foundation in such way that the corner of the installation leg is securely supported as shown in the right figure.(Fig.A,B) When using a rubber isolating cushion, please ensure it is large enough to cover the entire width of each of the unit's legs. 3 The protrusion length of the anchor bolt must not exceed 30mm.(Fig.A,B) 4 Use four fixing plates as shown in the right figure <field supply required> when using post-installed anchor bolts.(Fig.C,D) 5 To prevent small animals and water and snow from entering the unit and damaging its parts, close the gap around the edges of through holes for pipes and wires with filler plates <field supply required>. 6 When the pipes or cables are routed at the bottom of the unit, make sure that the through hole at the base of the unit does not get blocked with the installation base. 7 Refer to the Installation Manual when installing units on an installation base.

●In case of collective installation 1 When multiple units are installed adjacent to each other , secure enough space to allow for air circulation and walkway between groups of units as shown in the figures below . 2 At least two sides must be left open. 3 As with the single installation, add the height that exceeds the height limit<h> to the figures that are marked with an asterisk. 4 If there is a wall at both the front and the rear of the unit, install up to six units consecutively in the side direction and provide a space of 1000mm or more as inlet space/ passage space for each six units.

300mm to the wall on the back of the unit

· With a space of at least 100mm to the wall on the back of the unit exceeds the wall height limit as defined below add the height that exceeds the height limit <h> to the figures that are marked with an asterisk.

15 min.*

300 min.*

100 min.30 min.450 min.450 min.*450 min.100 min.*

450 min.*

100 min.*

450 min.*

1000 min.*

900 min.

300 min.*

900 min.

300 min.* 300 min.*

15 min.*

450 min.450 min.

450 min.*

300 min.*

450 min.*

100 min.*

15 min.* 50 min.* 50 min.*

30mm max. 30mm max.

Detachable leg

<Side view>

<W all height limit> Front : Up to the unit height Back : Up to the unit height Side   : Up to the unit height

Front

Unit height h

H Unit height h

H

PUHY-P350, 400, 450YNW-A1 (-BS) Unit: mm

PUHY-P-Y(S)NW-A1

2. EXTERNAL DIMENSIONS

Y-Series

NO. 1 2 43 5 6 7 8

(740)

132650148

84 71

110 125

90

207 256

116 (60) 127

35 740

83183119.519.5

70 150 600=150×4

1750

49

185

152

1495 303

1798 (60)

1858

172216

166 110

29.5 681(678~684) 29.5

80

685768

653150

94 79 181

185

79579580

20 5459254

206060

Control box

Refrigerant service valve <gas>

Refrigerant service valve <liquid>

Intake airIntake air

Discharge air 5 68

Intake airIntake air Detachable leg (front and back, 3 points) Note 2*

2×7-ø4.6 Hole (Make hole at the plastic fan guard for snow hood attachment) <Snow hood attachment hole>

T op view

1

Service panel

Refrigerant service valve <gas>

Refrigerant service valve <liquid>

2

(Mounting pitch)

Bottom view

(Mounting pitch)

Front view Left side view Rear view

Sling hole (Mounting pitch)

2×3-14×31 Oval hole 2×3-14×20 Oval hole(without detachable leg)

For transmission cables

For wires

For pipes

UsageSpecifications Front through hole Bottom through hole Front through hole Front through holeBottom through hole Bottom through holeFront through hole

148 × 84 Knockout hole ø65 or ø40 Knockout hole ø52 or ø27 Knockout hole ø65 Knockout hole ø52 Knockout hole ø34 Knockout hole

150 × 94 Knockout hole

Connecting pipe specifications ø34 Knockout hole

Note 1.Please refer to the next page for information regarding necessary spacing around the unit and foundation work. 2.The detachable leg can be removed at site. 3.At brazing of pipes, wrap the refrigerant service valve with wet cloth and keep the temperature of refrigerant service valve under 120°C. Bottom through hole

ModelDiameter Refrigerant pipe Service valve P500ø15.88ø28.58

LiquidGasLiquidGas ø28.58 Brazed ø15.88 Brazed 3 4 7

PUHY-P500YNW-A1 (-BS) Unit: mm

PUHY-P-Y(S)NW-A1

2. EXTERNAL DIMENSIONS

Y-Series

<T op view> <Unit:mm> <T op view> M10 anchor bolt <field supply required> Fixing plate <field supply required>

<Unit:mm> Fixing plate <field supply required> M10 anchor bolt <field supply required>

Detachable leg Fig.A (without detachable legs) Fig.B (with detachable legs)

Fig.C (without detachable legs) Fig.D (with detachable legs)

Front Front

<T o be left open>

Front W all <H>

W all <H>

<T o be left open>

<T o be left open>

Front W all <H>

W all <H>

<T o be left open>

<T o be left open>

Front Wall <H>

Wall <H>

Front Front

<T o be left open>

Front Front Front

W all <H>

W all <H> Front W all <H>

<T o be left open>

<T o be left open>

W all <H> Front

<T o be left open>

<T o be left open>

1.Required space around the unit ●In case of single installation 1 Secure enough space around the unit as shown in the figure below . · With a space of at least 2 When the height of the walls on the front, back or on the sides<H> 2.Foundation work 1 Take into consideration the surface strength, water drainage route, piping route, and wiring route when preparing the installation site. <Note that the drain water comes out of the unit during operation.> 2 Build the foundation in such way that the corner of the installation leg is securely supported as shown in the right figure.(Fig.A,B) When using a rubber isolating cushion, please ensure it is large enough to cover the entire width of each of the unit's legs. 3 The protrusion length of the anchor bolt must not exceed 30mm.(Fig.A,B) 4 Use six fixing plates as shown in the right figure <field supply required> when using post-installed anchor bolts.(Fig.C,D) 5 To prevent small animals and water and snow from entering the unit and damaging its parts, close the gap around the edges of through holes for pipes and wires with filler plates <field supply required>. 6 When the pipes or cables are routed at the bottom of the unit, make sure that the through hole at the base of the unit does not get blocked with the installation base. 7 Refer to the Installation Manual when installing units on an installation base.

●In case of collective installation 1 When multiple units are installed adjacent to each other , secure enough space to allow for air circulation and walkway between groups of units as shown in the figures below . 2 At least two sides must be left open. 3 As with the single installation, add the height that exceeds the height limit<h> to the figures that are marked with an asterisk. 4 If there is a wall at both the front and the rear of the unit, install up to three units consecutively in the side direction and provide a space of 1000mm or more as inlet space/ passage space for each three units.

300mm to the wall on the back of the unit

· With a space of at least 100mm to the wall on the back of the unit exceeds the wall height limit as defined below add the height that exceeds the height limit <h> to the figures that are marked with an asterisk.

30mm max. 30mm max.

450 min.

*

300 min.

*

15 min.

*

15 min.

*

50 min.

*

50 min.

*

450 min.

*

100 min.

*

30 min.100 min.450 min.

*

450 min.450 min.100 min.

*

15 min.

*

450 min.450 min.

900 min.

300 min.

* *

300 min.

1000 min.

*

300 min.

*

900 min.

300 min.

* *

450 min.

100 min.

* *

450 min.

Detachable leg

<Side view>

<W all height limit> Front : Up to the unit height Back : Up to the unit height Side   : Up to the unit height

Front

Unit height h

H Unit height h

H

PUHY-P500YNW-A1 (-BS) Unit: mm

PUHY-P-Y(S)NW-A1

2. EXTERNAL DIMENSIONS

Y-Series

Outdoor unit 2 Outdoor unit 1 Discharge air Front view

c b

ae Detachable leg Note 5*

Left view

df

To indoor unit Liquid Twinning pipe<optional parts> To indoor unit Gas Twinning pipe<optional parts> Twinning pipe connection size Component unit nameOutdoor unit 1Package unit name Outdoor Twinning Kit(optional parts)Outdoor unit 2 ø12.7 ø28.58

CMY-Y100VBK3

PUHY-P400YSNW-A1(-BS) PUHY-P200YNW-A1(-BS) PUHY-P200YNW-A1(-BS) PUHY-P450YSNW-A1(-BS) PUHY-P250YNW-A1(-BS) PUHY-P200YNW-A1(-BS) PUHY-P500YSNW-A1(-BS) PUHY-P250YNW-A1(-BS) PUHY-P250YNW-A1(-BS) PUHY-P550YSNW-A1(-BS) PUHY-P300YNW-A1(-BS) PUHY-P250YNW-A1(-BS) PUHY-P600YSNW-A1(-BS) PUHY-P300YNW-A1(-BS) PUHY-P300YNW-A1(-BS) ø15.88

d or fc or eUnit model Twinning pipe~Outdoor unitP200ø9.52ø22.2 P250 P300ø9.52ø22.2 ø12.7ø22.2

GasLiquid Indoor unit~Twinning pipea bLiquid Gas Note 1.Connect the pipes as shown in the figure above. Refer to the table above for the pipe size. 2.Twinning pipes should not be tilted more than 15 degrees from the horizontal plane. Be sure to see the Installation Manual for details of Twinning pipe installation. 3.The pipe section before the Twinning pipe (sections "a" and "b" in the figure) must have at least 500mm of straight section (*including the straight pipe that is supplied with the Twinning pipe). 4.Only use the Twinning pipe by Mitsubishi (optional parts). 5.The detachable leg can be removed at site.

Intake air Intake air

Intake air Intake air

92030920740

1858

1798 (60)

PUHY-P400, 450, 500, 550, 600YSNW-A1 (-BS) Unit: mm

PUHY-P-Y(S)NW-A1

2. EXTERNAL DIMENSIONS

Y-Series

Outdoor unit 2 Front view

Outdoor unit 1

Intake air Intake air

Discharge air

Intake air

c b

ae df

Left view Detachable leg Note 5*

To indoor unit Liquid Twinning pipe<optional parts> To indoor unit Gas Twinning pipe<optional parts>

Intake air

Twinning pipe connection size ø28.58

CMY-Y100VBK3

PUHY-P650YSNW-A1(-BS) PUHY-P400YNW-A1(-BS) PUHY-P250YNW-A1(-BS) ø15.88 d or fc or eUnit model Twinning pipe~Outdoor unitP250 P400ø9.52ø22.2 ø12.7ø28.58

Component unit name

Package unit name Outdoor Twinning Kit(optional parts)GasLiquid Indoor unit~Twinning pipeLiquid Gas

Outdoor unit 1 Outdoor unit 2 a b Note 1.Connect the pipes as shown in the figure above. Refer to the table above for the pipe size. 2.Twinning pipes should not be tilted more than 15 degrees from the horizontal plane. Be sure to see the Installation Manual for details of Twinning pipe installation. 3.The pipe section before the Twinning pipe (sections "a" and "b" in the figure) must have at least 500mm of straight section (*including the straight pipe that is supplied with the Twinning pipe). 4.Only use the Twinning pipe by Mitsubishi (optional parts). 5.The detachable leg can be removed at site.

920740124030

1858

1798 (60)

PUHY-P650YSNW-A1 (-BS) Unit: mm

PUHY-P-Y(S)NW-A1

2. EXTERNAL DIMENSIONS

Y-Series

Outdoor unit 2 Front view

Outdoor unit 1

Intake air Intake air

Discharge air

Intake air

c b

ae df

Left view

Detachable leg Note 5*

To indoor unit Liquid Twinning pipe<optional parts> To indoor unit Gas Twinning pipe<optional parts>

Intake air

Twinning pipe connection size ø34.93ø19.05CMY-Y200VBK2 PUHY-P700YSNW-A1(-BS) PUHY-P350YNW-A1(-BS) PUHY-P350YNW-A1(-BS) PUHY-P750YSNW-A1(-BS) PUHY-P400YNW-A1(-BS) PUHY-P350YNW-A1(-BS) PUHY-P800YSNW-A1(-BS) PUHY-P450YNW-A1(-BS) PUHY-P350YNW-A1(-BS) PUHY-P850YSNW-A1(-BS) PUHY-P450YNW-A1(-BS) PUHY-P400YNW-A1(-BS) PUHY-P900YSNW-A1(-BS) PUHY-P450YNW-A1(-BS) PUHY-P450YNW-A1(-BS) ø41.28

d or fc or eUnit model Twinning pipe~Outdoor unitP350ø12.7ø28.58 P400 P450ø15.88 ø15.88ø28.58 ø28.58

Component unit name

Package unit name Outdoor Twinning Kit(optional parts) GasLiquid Indoor unit~Twinning pipeLiquid Gas

Outdoor unit 1 Outdoor unit 2 a b Note 1.Connect the pipes as shown in the figure above. Refer to the table above for the pipe size. 2.Twinning pipes should not be tilted more than 15 degrees from the horizontal plane. Be sure to see the Installation Manual for details of Twinning pipe installation. 3.The pipe section before the Twinning pipe (sections "a" and "b" in the figure) must have at least 500mm of straight section (*including the straight pipe that is supplied with the Twinning pipe). 4.Only use the Twinning pipe by Mitsubishi (optional parts). 5.The detachable leg can be removed at site.

7401240

1858

1798 (60)

124030

PUHY-P700, 750, 800, 850, 900YSNW-A1 (-BS) Unit: mm