PCB - MC01 Magnetic Contactor LCD Panel - Cooler Panel CE Mark Rotary Compressor Rotary Compressor Terminal Block Water Tank + Pump Only Pump Expansion Tank Gold Fin Antifreeze and Automatic Pump in Phase Protector CCH (Car Heater) Single Phase Fan Motor Pipe capillary. PCB - MC01 Magnetic contactor LCD panel - Cooler panel CE mark Rotary compressor Rotary compressor Isolation switch Terminal block Gold fin Water tank + pump Expansion tank Only anti-freeze pump and automatic pump on CCH phase protector (keel heater) TXV Capillary Tube Single Phase Motorized Fan. PCB - MC01 Magnetic Contactor LCD Panel - Cooler Panel CE Brand Rotary Compressor Terminal Block Gold Fin Water Tank + Pump Expansion Tank Only Antifreeze & Automatic Pump on TXV Capillary Tube.
For the MAC/M4AC080~150C/CR models, the water flows through the BPHE in one channel alone, while the refrigerant, due to the two compressors, flows through two more separate channels. Under abnormal conditions, the chiller panel controller will shut down the unit and then display the operating errors. The cooler control will force the unit into heat mode if the outside ambient air temperature becomes too cold.
To facilitate the controller, a rocker switch is provided to turn off the supply to the PCB. However, turning off the switch will not disconnect the main incoming power supply to the chiller unit.
Water / Refrigerant Circuit Diagram
WATER / REFRIGERANT
WATER / REFRI
Safety Consideration
- General Installation Recommendations
General Description
- General
- Features
Panel Position
Chiller Panel Controller
Hardware Description
- Key Explanation
5 Switch to heat mode shortcut key 6 Switch to cooling mode shortcut key 7 Switch ON/OFF shortcut key 8 Show alarm key.
- Installation 1 Chiller Bus
Chiller Network
Supported up to 50 units of Chiller
5 way wire (CM8) Chiller
Communication bus
Others Configuration
JH2 in the heatsink should be left open (place the jumper header on only one pin) at all times unless the user needs to reset the CMOS on that particular board. You should leave the JH3 open (place the jumper on only one pin) all the time.
Installation of the Chiller Panel Controller
Bus Wiring Diagram
Software Description
- Introduction
Status viewing
Menu Structures
Menu Structure Diagram for Chiller
Chiller Menu Structure 1 Summary Pages
Water Out : 25.6°C Outdoor Air : 32.2°C
Main Menu
- Operation Menu
- Settings Menu
Press UP or DOWN to select submenus, ENTER to enter the submenu, or press ESC to exit to [Summary Pages]. Press UP or DOWN to select each option, ENTER to start the setting or press ESC here to exit [Main Menu]. This menu allows the user to select a compressor to go into defrost cycle manually as long as the environment meets the defrost requirement.
Press UP or DOWN to select settings, ENTER to start setting or press ESC here to exit to [Main Menu]. There are 7 sets of advanced parameters that the user needs to set in this menu, Press UP or DOWN to select the set, ENTER to go to the set or ESC to exit to [Settings Menu].
5.3.2.2.3 Panel Option
5.3.2.2.4 Set Panel ID
Please enter the Panel ID
Time Menu
ENTER to start the setting or press ESC here to exit to [Main Menu]
5.3.2.3.1 Set Clock
Set Time
5.3.2.3.2 Set Date
5.3.2.3.3 Set Schedule
Alarm Menu
5.3.2.4.1 Show Alarms
5.3.2.4.2 Erase All Alarms
Dispaly Menu
Are you sure ? Press Enter to erase,
5.3.2.5.1 Defrost Sensor
5.3.2.5.2 Discharge Sensor
5.3.2.5.3 Comp Run Time
Comp Run Time Comp 1 : 13579h
Operation User Manual
- Starting
- Chiller Operation Control .1 Starting
When the Panel ID is set to '0' it will act as a Master panel, while it will be a Slave panel if the Panel ID is set to any other number (1-50). The main panel can choose to control each chiller or all chillers on the network at once. While powering up the chiller panel, it should take several times to gather information from the chiller.
When the process is complete, user can start controlling the chiller using the panel. Choose "Select All" and press ENTER if the user wants to control all Chilelr in the network, or choose "Select One". Select a chiller ID via UP or DOWN and press ENTER to confirm or ESC to cancel.
Switching ON/OFF
Switching Mode
Cook - Press and hold the HEAT button again (if it allows to set). . ii) [Business List]. In [Operation Menu], select "Mode" and press ENTER to start setting or ESC to exit to [Main Menu]. Toggle ON/OFF via UP or DOWN button, then press ENTER to confirm the change or ESC to cancel.
Cooling Heating Boiling
Chiller Model
Mode
Changing Mode Set Temperature
General 2. Sensor
Manual Defrost
The user can select which compressor to go into manual defrost cycle by using the cooling panel as long as the defrost mode condition is met.
Defrost Compressor Comp 1
Advance Parameter Settings
CAUTION : INPROPER SETTINGS WILL CAUSE PERMANENT DAMAGE TO THE CHILLER !!!
General
Sensor
Regulator
Compressor
Condenser Defrost
Cool Mode Antifreeze
Alarm and Contact
P8 RO Reset : Manual P9 FS Reset : Manual
P15 FO Contact : Normal P16 PO Contact : Normal
Changing Password
Press ENTER to start entering the 2nd digit and the rest, or ESC to exit at any time. Same as previous, UP DOWN to change value, ENTER to go to next digit, ESC to exit. If new password is accepted, this message will be displayed and then exit to [Settings Menu].
Please enter the Old password
Please enter the New password
New password Has been set
New password
Clock Setting
Date Setting
Set Time
6.2.11 7 days Programmable Setting
UP or DOWN select day of week, ENTER to select event or ESC to exit to [Timer Menu]
Set Date Set Schedule
Viewing Alarm / Erase Alarm Record
When a new error/alarm occurs, a message will appear to show the error/alarm. If the fault/alarm is not resolved from the chiller, a sign [A] will be shown in the [Summary Pages] (from pop-up menu) automatically if the fault/alarms are resolved. While the error/alarms are not resolved (sign [A]), user can check that error/alarm by going to [Alarm Menu].
If all faults/alarms have been resolved, the user can also view the fault/alarm history records in [Alarm Menu]. If the panel ID is set to 0 (Master panel), it can receive and view all errors/alarms from all coolers in the network.
New Alarm 1 Comp 1 overload
Erase Alarm ? Please Enter to Erase,
- Viewing Defrost Sensor Temperature
- Viewing Compressor Discharge Temperature
- Viewing/ Clear Compressor Run Time
- Miscellaneous Settings
- Power OFF the panel
- Close the jumper JH2 with the provided jumper header
- Power ON the panel and the LCD panel should display as follow
- Remove the jumper header (put the jumper header on 1 pin only), power OFF and then power ON the panel
The user can view/clear the compressor run time for the chiller in [Comp Run Time] in [Display Menu]. Remove the jumper header (only put the jumper header on 1 pin), turn the panel OFF and then back ON.
CMOS reset completed ! Please remove JUMPER
Adjust the contrast setting for the LCD panel
Symptoms Possible Cause Troubleshooting
Problem And Troubleshooting
Appendix
Special Precautions When Dealing With Refrigerant R407C Unit
What is new refrigerant R407C?
Components
Check list before installation/servicing
Precautions and Installation
This vacuum level is more stringent than the R22 system to ensure that there is no incompressible gas and moisture in the system. This is to ensure that only the original composition of R407C is supplied into the system. However, if the dip tube is not available, invert the cylinder or can to draw fluid out of the valve at the bottom. . g) When servicing leaks, the filling method commonly used for the R22 system is not recommended for the R407C system.
Unlike R22, where the refrigerant is a single component, the composition of R407C, which consists of three different components, may have changed during the leak. As a result, topping up may not ensure that the R407C in the system is of original composition.
Special Precautions When Dealing With Refrigerant R410A Unit
What Is New Refrigerant R410A?
Check List Before Installation / Servicing
This is to ensure that only the original composition of R410A is delivered to the system. However, if the riser tube is not available, you must invert the cylinder or can to draw fluid from the valve at the bottom.
Installations
Warning
Safety Precautions
Before installing the air conditioner unit, please read the following safety precautions carefullyFor multiple unit installation (mm)
Caution
Please take note of the following important points when installing
Installation Location
Transportation
CAUTION
Electrical And Wiring
5HFRPPHQGHGIXVHDQGFDEOHVL]HV
Water Piping System Setup
Refrigerant Circuit
Safety And Caution
WARNING
Control Operation Guide
Handset location
LED Display (microprocessor board)
LCD display (contoller handset)
Controller functioning specification
MAC/M4AC030C/CR NC CURVE
MAC/M4AC040C/CR NC CURVE
MAC/M4AC060C/CR NC CURVE
MAC/M4AC050C/CR NC CURVE
MAC/M4AC080C/CR NC CURVE
MAC/M4AC 100C/CR NC CURVE
MAC/M4AC 120C/CR NC CURVE
MAC/M4AC 150C/CR NC CURVE
M5AC030C/CR NC CURVE
M5AC040C/CR NC CURVE
M5AC050C/CR NC CURVE
M5AC055C/CR NC CURVE
Water Pressure Drop vs Flow Rate
Model : MAC/M4AC020C/CR
Model : MAC/M4AC025C/CR
Model : MAC/M4AC080C/CR
Model : MAC/M4AC100C/CR
Model : MAC/M4AC120C/CR
Model : MAC/M4AC150C/CR
GYLCOL % WATER FLOW PRESSURE DROP
CAPACITY FACTOR GLYCOL
General Data - R22 Cooling only
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW
General Data - R22 Heat pump
NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW
General Data - R407C Cooling only
General Data - R407C Heat pump
General Data - R410A Heat pump
Components Data - R22 Cooling only
Parts Data - R22 Cooling Only. 1) ALL SPECIFICATIONS SUBJECT TO CHANGE BY MANUFACTURER WITHOUT NOTICE.
Components Data - R22 Heat pump
Component Information - R22 Heat Pump. 1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT NOTICE.
Components Data - R407C Cooling only
Components Data-R407C Cooling only. 1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
Components Data - R407C Heat pump
Components Data - R407C Heat Pump. 1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
Components Data - R410A Heat pump
Component data - R410A Heat pump. 1) ALL SPECIFICATIONS SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
Safety Devices - R22 Cooling only & Heat pump
Safety Devices - R407C Cooling only & Heat pump
Safety Devices - R410A Heat pump
AMBIENT TEMPERATURE (°C) 40 2035
AMBIENT TEMPERATURE (°C) 354042
Model : M4AC/ MAC040 / 050 / 060C/CROutline and Dimension
Base Leg Hole
Accessory Hydraulic Kit (Optional)
Electrical Data - R22 Cooling only
ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151
Electrical Data - R22 Heat pump
Electrical Data - R407C Cooling only
Electrical Data - R407C Heat pump
Electrical Data - R410A Heat pump
Model : M4AC/ MAC020C
Model : M4AC/ MAC025 / 030C
Model : M4AC/ MAC080 / 100C (With Isolated Switch)
Model : M4AC / MAC 120/ 150C (With Isolated Switch)
Model : M4AC/ MAC080 / 100C (With Terminal Block)
Model : M4AC / MAC 120 / 150C (With Terminal Block)
Model : M4AC / MAC 025 / 030CR
DISCHARGE SENSOR COMP (1) OUTSIDE AIR TEMP SENSOR WATER OUT SENSOR WATER INLET SENSOR TN12VTB212V12VN1N1N1N112O/FC/H4WVHTRAL INAL OUT LPHPFL4WV.
Model : M4AC / MAC 080 / 100CR (With Isolated Switch)
Model : M4AC / MAC 120 / 150CR (With Isolated Switch)
Model : M4AC / MAC 080 / 100CR (With Terminal Block)
Model : M4AC / MAC 120 / 150CR (With Terminal Block)
Model : M5AC020 / 025CR
COMP OUTPUT SENSOR (2) COMP OUTPUT SENSOR (1) OUTDOOR AIR TEMP SENSOR LEAVING WATER SENSOR INLET WATER SENSOR.
Servicing
Maintenance
Phase Proctector (Optional)
Model : MAC/ M4AC020 / 025/ 030C
ALL SPECIFICATION ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
Model : M4AC/ MAC080 / 100C/CR
Model : M4AC/ MAC120 / 150C/CR
Model : M5AC 020 / 025CR
Model : M5AC040 / 050/ 055CR