• Nenhum resultado encontrado

Air-Cooled Mini Chiller

N/A
N/A
Protected

Academic year: 2023

Share "Air-Cooled Mini Chiller"

Copied!
180
0
0

Texto

PCB - MC01 Magnetic Contactor LCD Panel - Cooler Panel CE Mark Rotary Compressor Rotary Compressor Terminal Block Water Tank + Pump Only Pump Expansion Tank Gold Fin Antifreeze and Automatic Pump in Phase Protector CCH (Car Heater) Single Phase Fan Motor Pipe capillary. PCB - MC01 Magnetic contactor LCD panel - Cooler panel CE mark Rotary compressor Rotary compressor Isolation switch Terminal block Gold fin Water tank + pump Expansion tank Only anti-freeze pump and automatic pump on CCH phase protector (keel heater) TXV Capillary Tube Single Phase Motorized Fan. PCB - MC01 Magnetic Contactor LCD Panel - Cooler Panel CE Brand Rotary Compressor Terminal Block Gold Fin Water Tank + Pump Expansion Tank Only Antifreeze & Automatic Pump on TXV Capillary Tube.

For the MAC/M4AC080~150C/CR models, the water flows through the BPHE in one channel alone, while the refrigerant, due to the two compressors, flows through two more separate channels. Under abnormal conditions, the chiller panel controller will shut down the unit and then display the operating errors. The cooler control will force the unit into heat mode if the outside ambient air temperature becomes too cold.

To facilitate the controller, a rocker switch is provided to turn off the supply to the PCB. However, turning off the switch will not disconnect the main incoming power supply to the chiller unit.

Water / Refrigerant Circuit Diagram

WATER / REFRIGERANT

WATER / REFRI

Safety Consideration

  • General Installation Recommendations

General Description

  • General
  • Features

Panel Position

Chiller Panel Controller

Hardware Description

  • Key Explanation

5 Switch to heat mode shortcut key 6 Switch to cooling mode shortcut key 7 Switch ON/OFF shortcut key 8 Show alarm key.

  • Installation 1 Chiller Bus

Chiller Network

Supported up to 50 units of Chiller

5 way wire (CM8) Chiller

Communication bus

Others Configuration

JH2 in the heatsink should be left open (place the jumper header on only one pin) at all times unless the user needs to reset the CMOS on that particular board. You should leave the JH3 open (place the jumper on only one pin) all the time.

Installation of the Chiller Panel Controller

Bus Wiring Diagram

Software Description

  • Introduction

Status viewing

Menu Structures

Menu Structure Diagram for Chiller

Chiller Menu Structure 1 Summary Pages

Water Out : 25.6°C Outdoor Air : 32.2°C

Main Menu

  • Operation Menu
  • Settings Menu

Press UP or DOWN to select submenus, ENTER to enter the submenu, or press ESC to exit to [Summary Pages]. Press UP or DOWN to select each option, ENTER to start the setting or press ESC here to exit [Main Menu]. This menu allows the user to select a compressor to go into defrost cycle manually as long as the environment meets the defrost requirement.

Press UP or DOWN to select settings, ENTER to start setting or press ESC here to exit to [Main Menu]. There are 7 sets of advanced parameters that the user needs to set in this menu, Press UP or DOWN to select the set, ENTER to go to the set or ESC to exit to [Settings Menu].

5.3.2.2.3 Panel Option

5.3.2.2.4 Set Panel ID

Please enter the Panel ID

Time Menu

ENTER to start the setting or press ESC here to exit to [Main Menu]

5.3.2.3.1 Set Clock

Set Time

5.3.2.3.2 Set Date

5.3.2.3.3 Set Schedule

Alarm Menu

5.3.2.4.1 Show Alarms

5.3.2.4.2 Erase All Alarms

Dispaly Menu

Are you sure ? Press Enter to erase,

5.3.2.5.1 Defrost Sensor

5.3.2.5.2 Discharge Sensor

5.3.2.5.3 Comp Run Time

Comp Run Time Comp 1 : 13579h

Operation User Manual

  • Starting
  • Chiller Operation Control .1 Starting

When the Panel ID is set to '0' it will act as a Master panel, while it will be a Slave panel if the Panel ID is set to any other number (1-50). The main panel can choose to control each chiller or all chillers on the network at once. While powering up the chiller panel, it should take several times to gather information from the chiller.

When the process is complete, user can start controlling the chiller using the panel. Choose "Select All" and press ENTER if the user wants to control all Chilelr in the network, or choose "Select One". Select a chiller ID via UP or DOWN and press ENTER to confirm or ESC to cancel.

Switching ON/OFF

Switching Mode

Cook - Press and hold the HEAT button again (if it allows to set). . ii) [Business List]. In [Operation Menu], select "Mode" and press ENTER to start setting or ESC to exit to [Main Menu]. Toggle ON/OFF via UP or DOWN button, then press ENTER to confirm the change or ESC to cancel.

Cooling Heating Boiling

Chiller Model

Mode

Changing Mode Set Temperature

General 2. Sensor

Manual Defrost

The user can select which compressor to go into manual defrost cycle by using the cooling panel as long as the defrost mode condition is met.

Defrost Compressor Comp 1

Advance Parameter Settings

CAUTION : INPROPER SETTINGS WILL CAUSE PERMANENT DAMAGE TO THE CHILLER !!!

General

Sensor

Regulator

Compressor

Condenser Defrost

Cool Mode Antifreeze

Alarm and Contact

P8 RO Reset : Manual P9 FS Reset : Manual

P15 FO Contact : Normal P16 PO Contact : Normal

Changing Password

Press ENTER to start entering the 2nd digit and the rest, or ESC to exit at any time. Same as previous, UP DOWN to change value, ENTER to go to next digit, ESC to exit. If new password is accepted, this message will be displayed and then exit to [Settings Menu].

Please enter the Old password

Please enter the New password

New password Has been set

New password

Clock Setting

Date Setting

Set Time

6.2.11 7 days Programmable Setting

UP or DOWN select day of week, ENTER to select event or ESC to exit to [Timer Menu]

Set Date Set Schedule

Viewing Alarm / Erase Alarm Record

When a new error/alarm occurs, a message will appear to show the error/alarm. If the fault/alarm is not resolved from the chiller, a sign [A] will be shown in the [Summary Pages] (from pop-up menu) automatically if the fault/alarms are resolved. While the error/alarms are not resolved (sign [A]), user can check that error/alarm by going to [Alarm Menu].

If all faults/alarms have been resolved, the user can also view the fault/alarm history records in [Alarm Menu]. If the panel ID is set to 0 (Master panel), it can receive and view all errors/alarms from all coolers in the network.

New Alarm 1 Comp 1 overload

Erase Alarm ? Please Enter to Erase,

  • Viewing Defrost Sensor Temperature
  • Viewing Compressor Discharge Temperature
  • Viewing/ Clear Compressor Run Time
  • Miscellaneous Settings
  • Power OFF the panel
  • Close the jumper JH2 with the provided jumper header
  • Power ON the panel and the LCD panel should display as follow
  • Remove the jumper header (put the jumper header on 1 pin only), power OFF and then power ON the panel

The user can view/clear the compressor run time for the chiller in [Comp Run Time] in [Display Menu]. Remove the jumper header (only put the jumper header on 1 pin), turn the panel OFF and then back ON.

CMOS reset completed ! Please remove JUMPER

Adjust the contrast setting for the LCD panel

Symptoms Possible Cause Troubleshooting

Problem And Troubleshooting

Appendix

Special Precautions When Dealing With Refrigerant R407C Unit

What is new refrigerant R407C?

Components

Check list before installation/servicing

Precautions and Installation

This vacuum level is more stringent than the R22 system to ensure that there is no incompressible gas and moisture in the system. This is to ensure that only the original composition of R407C is supplied into the system. However, if the dip tube is not available, invert the cylinder or can to draw fluid out of the valve at the bottom. . g) When servicing leaks, the filling method commonly used for the R22 system is not recommended for the R407C system.

Unlike R22, where the refrigerant is a single component, the composition of R407C, which consists of three different components, may have changed during the leak. As a result, topping up may not ensure that the R407C in the system is of original composition.

Special Precautions When Dealing With Refrigerant R410A Unit

What Is New Refrigerant R410A?

Check List Before Installation / Servicing

This is to ensure that only the original composition of R410A is delivered to the system. However, if the riser tube is not available, you must invert the cylinder or can to draw fluid from the valve at the bottom.

Installations

Warning

Safety Precautions

Before installing the air conditioner unit, please read the following safety precautions carefullyFor multiple unit installation (mm)

Caution

Please take note of the following important points when installing

Installation Location

Transportation

CAUTION

Electrical And Wiring

5HFRPPHQGHGIXVHDQGFDEOHVL]HV

Water Piping System Setup

Refrigerant Circuit

Safety And Caution

WARNING

Control Operation Guide

Handset location

LED Display (microprocessor board)

LCD display (contoller handset)

Controller functioning specification

MAC/M4AC030C/CR NC CURVE

MAC/M4AC040C/CR NC CURVE

MAC/M4AC060C/CR NC CURVE

MAC/M4AC050C/CR NC CURVE

MAC/M4AC080C/CR NC CURVE

MAC/M4AC 100C/CR NC CURVE

MAC/M4AC 120C/CR NC CURVE

MAC/M4AC 150C/CR NC CURVE

M5AC030C/CR NC CURVE

M5AC040C/CR NC CURVE

M5AC050C/CR NC CURVE

M5AC055C/CR NC CURVE

Water Pressure Drop vs Flow Rate

Model : MAC/M4AC020C/CR

Model : MAC/M4AC025C/CR

Model : MAC/M4AC080C/CR

Model : MAC/M4AC100C/CR

Model : MAC/M4AC120C/CR

Model : MAC/M4AC150C/CR

GYLCOL % WATER FLOW PRESSURE DROP

CAPACITY FACTOR GLYCOL

General Data - R22 Cooling only

ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW

General Data - R22 Heat pump

NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW

General Data - R407C Cooling only

General Data - R407C Heat pump

General Data - R410A Heat pump

Components Data - R22 Cooling only

Parts Data - R22 Cooling Only. 1) ALL SPECIFICATIONS SUBJECT TO CHANGE BY MANUFACTURER WITHOUT NOTICE.

Components Data - R22 Heat pump

Component Information - R22 Heat Pump. 1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT NOTICE.

Components Data - R407C Cooling only

Components Data-R407C Cooling only. 1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

Components Data - R407C Heat pump

Components Data - R407C Heat Pump. 1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

Components Data - R410A Heat pump

Component data - R410A Heat pump. 1) ALL SPECIFICATIONS SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

Safety Devices - R22 Cooling only & Heat pump

Safety Devices - R407C Cooling only & Heat pump

Safety Devices - R410A Heat pump

AMBIENT TEMPERATURE (°C) 40 2035

AMBIENT TEMPERATURE (°C) 354042

Model : M4AC/ MAC040 / 050 / 060C/CROutline and Dimension

Base Leg Hole

Accessory Hydraulic Kit (Optional)

Electrical Data - R22 Cooling only

ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151

Electrical Data - R22 Heat pump

Electrical Data - R407C Cooling only

Electrical Data - R407C Heat pump

Electrical Data - R410A Heat pump

Model : M4AC/ MAC020C

Model : M4AC/ MAC025 / 030C

Model : M4AC/ MAC080 / 100C (With Isolated Switch)

Model : M4AC / MAC 120/ 150C (With Isolated Switch)

Model : M4AC/ MAC080 / 100C (With Terminal Block)

Model : M4AC / MAC 120 / 150C (With Terminal Block)

Model : M4AC / MAC 025 / 030CR

DISCHARGE SENSOR COMP (1) OUTSIDE AIR TEMP SENSOR WATER OUT SENSOR WATER INLET SENSOR TN12VTB212V12VN1N1N1N112O/FC/H4WVHTRAL INAL OUT LPHPFL4WV.

Model : M4AC / MAC 080 / 100CR (With Isolated Switch)

Model : M4AC / MAC 120 / 150CR (With Isolated Switch)

Model : M4AC / MAC 080 / 100CR (With Terminal Block)

Model : M4AC / MAC 120 / 150CR (With Terminal Block)

Model : M5AC020 / 025CR

COMP OUTPUT SENSOR (2) COMP OUTPUT SENSOR (1) OUTDOOR AIR TEMP SENSOR LEAVING WATER SENSOR INLET WATER SENSOR.

Servicing

Maintenance

Phase Proctector (Optional)

Model : MAC/ M4AC020 / 025/ 030C

ALL SPECIFICATION ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

Model : M4AC/ MAC080 / 100C/CR

Model : M4AC/ MAC120 / 150C/CR

Model : M5AC 020 / 025CR

Model : M5AC040 / 050/ 055CR

Referências

Documentos relacionados

Results: A single bout of both moderate and high intensity exercise induced significant increases in serum CRP and IL-6 levels (p<0.05), however, no significant difference