E-101
OPTIONAL PARTS
This kit (L/N/Earth) is used when the power supply of the indoor unit and the outdoor unit is separated.
(For PUHZ applications only)
Photo
Specifications
PSA-RP·KA series PCA-M·KA series
Power Supply Terminal Kit PAC-SG96HR-E
Unit : mm
Descriptions
Applicable Models
Dimensions
for new A-Control indoor units (L/N/Earth)
N L
53.8 24
39.2 120
Connector 2P (Blue)
Denatured melamine Terminal block material
30A/330V Terminal block capacity
Terminal block (with lead wires connect- ed) x 1, Screw x 1, Fastener (for binding lead wires)
Parts composition
OPTIONALPARTS
This kit (L/N) is used when the power supply of the indoor unit and the outdoor unit is separated.
(For PUHZ applications only)
Photo
Specifications
PCA-RP71HAQ PEAD-M·JA series
Power Supply Terminal Kit PAC-SG97HR-E
Unit : mm
Descriptions
Applicable Models
Dimensions
for new A-Control indoor units (L/N)
L N
36 18.5
38 80
Connector 2P (Blue)
Denatured melamine Terminal block material
15A/264V Terminal block capacity
Terminal block (with lead wires connect- ed) x 1, Screw x 1, Fastener (for binding lead wires)
Parts composition
E-103
OPTIONAL PAR
TS
Power Supply Terminal Kit for new A-Control Indoor units PAC-SG96,97HR-E
How to Use / How to Install
1. Overview
This kit is used when the power supply of the indoor unit and the outdoor unit is separated.
(for PUHZ applications only)
Refer to the installation manual of the indoor unit as well.
2. Provided parts
Comfirm the following parts are included.
Terminal block (lead wires already wired) x 1 Screw (to attach terminal block) x 1 Fastener (to tie lead wires) x 1 Screw (to secure ground wire) x 1
For PAC-SG96HR-E For PAC-SG97HR-E For PAC-SG96HR-E only
1:1 System
Simultaneous twin/triple/four system
L N
S1 S2 S3
S1 S2 S3 1 2 L N
<For models without heater>
•The indoor power supply terminal kit is required.
•Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
•Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
AOutdoor unit power supply BEarth leakage breaker
CWiring circuit breaker or isolating switch DOutdoor unit
EIndoor unit / outdoor unit connecting cords FRemote controller
GIndoor unit HOption
JIndoor unit power supply
<For models without heater>
•The indoor power supply terminal kits are required.
AOutdoor unit power supply BEarth leakage breaker
CWiring circuit breaker or isolating switch DOutdoor unit
EIndoor unit / outdoor unit connecting cords FRemote controller
GIndoor unit HOption
JIndoor unit power supply KIndoor unit earth
A B C J B C H
E
E
F
F D
D G
K K K
H G
G H
G H
G H
L N L
N
S1 S2 S3 S1
S2 S3
1 2
L N
S1 S2 S3 1 2
L N
S1 S2 S3 1 2
L N
S1 S2 S3 1 2
A B C J B C
N
L N
L NN
2 1
2 1
3 3
Change the yellow and blue relay connectors.
Terminal block attachment hole Terminal block attachment hole
Relay connector (blue) Relay connector (blue)
Relay connector (yellow)
Relay connector (yellow) 44
3. Attachment method
■ PAC-SG96HR
1.Remove the cover of electric parts
box. 2. Attach terminal block 1 using screw
2 in the direction shown in the figure.
3. Change the relay connectors of blue and yellow lead wires, secure the ground wire using screw 4 at the position shown in the figure, and then bundle the lead wires using fastener 3.
Ceiling suspended, PCA-M∙KA type:
OPTIONALPARTS
Terminal block attachment hole Terminal block attachment hole
Relay connector (yellow)
Relay connector (yellow)
Relay connector (blue) Relay connector (blue)
Change the yellow and blue relay connectors.
1
1 2 2
3 3
1 2 2 1
Relay connector (blue)
Relay connector (blue)
Relay connector (yellow) Relay connector (yellow)
Change the yellow and blue relay connectors.
1.Remove the terminal block cover of electric parts box.
■ PAC-SG97HR
Ceiling suspended for kitchens, PCA- RP 71HA Q type:
2. Attach terminal block
1using screw
2 in the direction shown in the figure.3. Change the relay connectors of blue and yellow lead wires, and then bundle the lead wires using fastener
3.
3.Change the relay connectors of blue and yellow lead wires.
T
Terminal block attachment hole erminal block attachment hole
Ceiling concealed, PEAD-M.JA type 1.Remove the cover of electric parts
box.
2. Attach terminal block 1 using screw
2in the direction shown in the figure.
Power Supply Terminal Kit for new A-Control Indoor units PAC-SG96,97HR-E
E-105
OPTIONAL PAR
TS
4. Electric wiring
Be sure to do the electric wiring following the steps in each indoor unit installation manual.
6. DIP switch settings of the outdoor unit control board
It is necessary to change the settings of DIP switch on the outdoor unit control board.
7. Test run
Perform a test run following the steps in the installation manual of the outdoor unit.
5. Paste the labels enveloped in the instruction document of indoor unit near the electric wiring diagrams of both indoor and outdoor units.
Three types of labels (labels A-C) are provided: Paste the label B.
(Separate indoor unit/outdoor unit power supplies... Label B)
ON OFF 1 2
3
<SW8>
Outdoor unit DIP switch settings (when using separate indoor unit / outdoor unit power supplies only)
Change of connectors (except PCA-M·KA type)
(PCA-M·KA type)
Indoor unit control board
Connectors (connections of initial setting are for indoor unit power supplied from outdoor unit)
Connectors Indoor unit power supplied from outdoor unit
(initial setting)
BLACK CN01
L BLUE
YELOW YELOWBLUE CN01
Option
S1 S2 S3 N
L
S1 S2 S3 N
Indoor unit control board
Separate indoor unit / outdoor unit power supplies BLACK CN01
BLUE
YELOWBLUE YELOW CN01
Option
If the indoor and outdoor units have separate power supplies, change the connections of the connectors as shown in the following figure.
Indoor unit control board
Connectors Indoor unit power supplied from outdoor unit
(initial setting)
ORANGE CND
L BLUE
YELOW YELOWBLUE CND
S1 S2 S3 N
L
S1 S2 S3 N
Indoor unit control board
Separate indoor unit / outdoor unit power supplies ORANGE CND
BLUE
YELOWBLUE YELOW CND
Connectors (connections of initial setting are for indoor unit power supplied from outdoor unit) Option
If the indoor and outdoor units have separate power supplies, change the connections of the connectors as shown in the following figure.