INSTALLATION AND OPERATION INSTRUCTION

1B95050 - P100006323

Brasil Singapore . 03/2014

FlowCon International assumes no responsibility for mistakes, if any, in any printed material.

Denmark Dubai USA

THERMAL ACTUATORS FlowCon FT actuators

- 1 -

FlowCon FT.0.2, FT.0.3 and FT.0.4 actuators

360º Figure 2 Figure 1

A 20625-00 FT.0.3

1403

MadeinGerman y 230 V NC 1,2 W

A 20625-00 FT.0.3

1403

MadeinGerman y 230 V NC 1,2 W A 20625-00 FT.0.3

1403

MadeinGerman y 230 V NC 1,2 W

A 20625-00 FT.0.3

1403

MadeinGerman y 230 V NC 1,2 W

A 20625-00 FT.0.3

1403

MadeinGerman y 230 V NC 1,2 W

>click<

The actuator type FlowCon FT.0.2 is a thermal mo- dulating actuator, NC. FlowCon FT.0.3 and FT.0.4are thermal ON/OFF actuators, NC.

Fitting the FlowCon FT actuator:

Actuators are supplied with a separate black colored adaptor ring. First, screw on the adaptor ring finger

tight to the connection thread at the top of the insert.

Do not use additional tools (figure 1,

and

). For

FlowCon FT.0.2 connect the cable before fitting the actuator on to the adaptor ring. FlowCon FT.0.3 and FT.0.4 comes with fixed cable and can be fitted im- mediately onto the adaptor ring (

). A click noise will indicate that the actuator is fitted correctly (

).

Removing the FlowCon FT actuator:

Actuators are equipped with a front push button to activate the release mechanism. When pushed, the actuator is released and can be removed from the adaptor ring. A special feature on the FlowCon FT.0.2 will allow the actuator to become tamper proof as the bush button can be removed for protection.

Installation of the FlowCon FT actuator:

To ensure that the valve is in an open position during commissioning of the system, all mentioned actuators will be delivered in a Normally Open position and re- main in this position until they are electrically operat- ed first time. FIRST TIME POWERING requires ope- rating voltage applied for approximately 6 minutes.

Upside down installation is allowed for all FT-actua- tors along with the standard horizontal and vertical installation (figure 2).

(2)

Denmark Dubai USA

1B95050 - P100006323 Brasil Singapore . 03/2014

FlowCon International assumes no responsibility for mistakes, if any, in any printed material.

THERMAL ACTUATORS FlowCon FT actuators

- 2 -

Blue Black Red

FT.0.2 Actuator

Power 24V AC Ground/common 0-10V DC

Blue Brown

FT.0.3 / FT.0.4 Actuator

Power Ground/common

24V AC/DC 230V AC Open

Close Figure 3

Connection and actuator wiring:

For power supply, use safety isolating transformer according to EN 61558-2-6 (Europe) or class II (North America) and for FlowCon FT.0.2 also with a maximum power output of 100VA.

Wiring diagram for actuator type FT.0.2 (24V AC), FT.0.3 (230V AC) and FT.0.4 (24V AC/DC) are shown in figure 3.

Warranty obligation:

Failure to abide by all recommendations as per this installation and operation instruction will void warranty.