• Nenhum resultado encontrado

Line-up of Outdoor Units of R410A CITY MULTI Heat Recovery R2-Series

N/A
N/A
Protected

Academic year: 2023

Share "Line-up of Outdoor Units of R410A CITY MULTI Heat Recovery R2-Series"

Copied!
177
0
0

Texto

Connection hose specifications *1 Connect the refrigerant hose to the service valve according to the installation manual. With at least 100mm of space to the wall at the back of the unit.

PURY-P-Y(S)NW-A Outdoor unit 2 Front view

Unit component name Outdoor unit 1 Package name Outdoor Twinning Kit (optional parts) BC controller ~Twinning tube. Twin pipe connection size Low pressure d or f High pressure c or e Unit model Twin pipe~Outdoor unit P500ø22.2ø28.58 P550.

PURY-P200, 250, 300YNW-A (-BS)

PURY-P350, 400, 450YNW-A (-BS)

PURY-P500, 550YNW-A (-BS)

HIC bypass, Controls coolant flow in HIC circuit For opening/closing the exhaust suction bypassSV2 Pipe temperature. LED2 Normal operation (Light)/Error (Beep) In operation (Light)/In stop (Unilluminated) LED3SW6-10 is OFF and SW4-1~10 is OFF Function setting by SW4 enable (Light)/disable (Unilluminated) SW6- 10 is ON LED4USB connection With(Illuminated)/Without(Unilluminated) LED101Normal operation(Illuminated)/IC Error(Unilluminated) LED102Normal operation(Illuminated)/Error(Sound) for central control transmission LED103Normal operation(Illuminated)/Fault(Sound) for indoor /outdoor transmission *8.

PURY-P200, 250, 300YNW-A(-BS)

L Search coil (for high frequency noise reduction) For inrush current prevention ResistorR1.5 HIC bypass, Controls coolant flow in HIC circuit For opening/closing the discharge suction bypass SV2SV1aLEV2a,b. LED2Normal operation (Light)/Fault (Beep) LED3SW6-10 is OFF and SW4-1~10 is OFF In operation (Light)/In stop (Unilluminated) SW6-10 is ON Function setting by SW4 enable (Light)/disable (Unilluminated) LED4USB connection With(Illuminated)/Without(Unilluminated) LED101Normal operation(Illuminated)/IC Error(Unilluminated) LED102Normal operation(Illuminated)/Error(Sound) for central control transmission LED103Normal operation(Illuminated)/Error(Sound) for indoor/outdoor transfer *10.

PURY-P350, 400, 450YNW-A(-BS)

Symbol 63H1 63HS1 63LS21S4b C1~C8 LEV1 *10DCL Pressure control, Coolant flow rate control Solenoid valve For opening/closing the bypass circuit during O/SH Heat exchanger capacity control (only. LED2Normal operation(Listen)/Fault(flashing) LED3SW6-10 are OFF and SW4 -1~10 is OFFI operation(On)/Instop(Not on) SW6-10 is ONFunction setting at SW4 enable(On)/disable(Off) LED4USB connection With(On)/Without(Off) ) LED101Normal operation(On) /IC error(off) LED102Normal operation(on)/error(blinking) of central control transmission LED103Normal operation(on)/error(blinking) of indoor/outdoor transmission *8.

PURY-P500, 550YNW-A(-BS)

Symbol 63H1 63HS1 63LS ACCT1,ACCT221S4b,c DCL LEV1 *10 Pressure control, Coolant speed control Solenoid valve For opening/closing the bypass circuit under O/SHeat exchanger capacity control (Switch only. of cooling/heating 9 control, Coolant flow rate control Heat exchanger for inverter LEV9 *9,10 For opening/closing the bypass circuit SV9 *8 For continuous heating SV10,11 *8 TH2 *8 Subcooling outlet temperature Thermistor TH6 *8Temperature of liquid subcoolant.

5-1. Sound levels in cooling mode

Measurement condition

It is recommended to install the BC controller in places such as ceilings of corridors, toilets and technical rooms. It is recommended to install the BC controller in places such as ceilings of corridors, toilets and technical rooms.

Measurement condition PURY-P500, 550YNW-A(-BS)

Depending on operating conditions, the unit generates noise caused by valve actuation, coolant flow, and pressure changes when operating normally. The system can return to normal operation from low noise mode automatically in case the operating condition is severe.

Measurement condition PURY-P650YSNW-A(-BS)

Measurement condition PURY-P950YSNW-A(-BS)

PURY-P1000, 1050, 1100YSNW-A(-BS)

5-2. Sound levels in heating mode

PURY-P200-550YNW, PURY-P400-1100YSNW]

Combination of cooling/heating operation (Cooling main or Heating main)Range for continuous operation

Heating only

How to determine the capacity when less than or equal 100% indoor model size units are connected in total

How to determine the capacity when greater than 100% indoor model size units are connected in total

Design Condition

Cooling Calculation

1) Temporary Selection of Indoor Units Room1

4) Total Indoor Units Capacity Correction Calculation Room1

5) Outdoor Unit Correction Calculation

6) Determination of Maximum System Capacity (CTx)

7) Comparison with Essential Load

Against the essential load 19.0kW, the maximum system capacity is 21.0kW: Proper outdoor units have been selected

8) Calculation of Maximum Indoor Unit Capacity of Each Room CTx = CTo, thus, calculate by the calculation below

Heating Calculation

Indoor Design Dry Bulb Temperature Correction (25ºC) 0.80 (See Fig.4) CTi = Σ (Indoor Unit Rating × Indoor Design Temperature Correction). Comparison of capacity between total indoor unit capacity (CTi) and total outdoor unit capacity (CTo) CTi = 20.0 < CTo = 21.1, therefore select CTi.

Against the essential load 18.5kW, the maximum system capacity is 20.0kW: Proper outdoor units have been selected

8) Calculation of Maximum Indoor Unit Capacity of Each Room CTx = CTi, thus, calculate by the calculation below

Power input of outdoor unit

3) No need to consider Coefficient of the partial load (CTi/CTo)

4) Outdoor power input (PIo)

3) Coefficient of the partial load (CTi/CTo)

8-2. Correction by temperature

P200YNW-A 22.4

P250YNW-A 28.0

5.97PURY-

Outdoor unit temperature correction

Indoor unit temperature correction

Values ​​in the heating temperature correction diagram in the range below -20°C (-4°F) are reference values ​​and not guaranteed values. When applying the product below -20°C (-4°F), consult your design engineer for best practices in cold climate applications, including the use of a backup source of heating.

P200YNW-A 25.0

P250YNW-A 31.5

6.06PURY-

P300YNW-A 33.5

P350YNW-A 40.0

Outdoor unit temperature correction To be used to correct outdoor unit only

P350YNW-A 45.0

P400YNW-A 45.0

P450YNW-A 50.0

P500YNW-A 56.0

12.72PURY-

P450YNW-A 56.0

P500YNW-A 63.0

P550YNW-A 63.0

Outdoor unit temperature correction To be used only to correct outdoor unit To be used only to correct outdoor unit.

P400YSNW-A 45.0

P450YSNW-A 50.0

P500YSNW-A 56.0

12.29PURY-

P450YSNW-A 56.0

P550YSNW-A 63.0

P600YSNW-A 69.0

P650YSNW-A 73.0

18.19PURY-

P700YSNW-A 80.0

20.72PURY-

Indoor unit temperature correction To be used to correct indoor unit capacity only

Indoor unit temperature correction To be used only to correct indoor unit capacity To be used only to correct indoor unit capacity.

P600YSNW-A 76.5

P650YSNW-A 81.5

19.35PURY-

P700YSNW-A 88.0

PURY- kW

P750YSNW-A 85.0

22.30PURY-

P800YSNW-A 90.0

P850YSNW-A 96.0

P900YSNW-A 101.0

25.76PURY-

P950YSNW-A 108.0

P1000YSNW-A 113.0

26.45PURY-

P800YSNW-A 100.0

P850YSNW-A 108.0

P900YSNW-A 113.0

28.03PURY-

P950YSNW-A 119.5

P1000YSNW-A 127.0

31.74PURY-

P1050YSNW-A 118.0

P1100YSNW-A 124.0

P1050YSNW-A 132.0

P1100YSNW-A 140.0

37.52PURY-

Correction by temperature (COP Priority Mode only for heating)

13.48P400YNW-A

15.28COP Priority Mode

P550YNW-A 69.0

17.91Heating

P400YSNW-A 50.0

P500YSNW-A 63.0

12.51COP Priority Mode

P550YSNW-A 69.0

21.56PURY-

24.86Heating

28.03 P950YSNW-A

31.74COP Priority Mode

37.52COP Priority Mode

8-3. Correction by total indoor

PURY-P250YNW-APURY-P200YNW-A

PURY-P300YNW-A

PURY-P350YNW-A

PURY-P450YNW-A

PURY-P400YNW-A

PURY-P500YNW-A

PURY-P550YNW-A

PURY-P400YSNW-A

PURY-P450YSNW-A

PURY-P500YSNW-A

PURY-P550YSNW-A

PURY-P600YSNW-A

PURY-P650YSNW-A

PURY-P700YSNW-A

PURY-P750YSNW-A

PURY-P800YSNW-A

PURY-P850YSNW-A

PURY-P900YSNW-A

PURY-P950YSNW-A

PURY-P1000YSNW-A

PURY-P1050YSNW-A

PURY-P1100YSNW-A

8-4. Correction by refrigerant piping length

8-5. Correction by port counts of the BC controller

8-6. Correction at frost and defrost

1 PURY-P200YNW-A(-BS)

9-1. JOINT and REDUCER

CMY-Y102SS-G2

-R204S-G For high pressure For low pressure For liquid line mm. Outer diameter) (Outer diameter) (Outer diameter) (Outer diameter).

9-2. OUTDOOR TWINNING KIT

CMY-R100VBK4

CMY-R200VBK4

  • Use the attached pipe to braze the port-opening of the distributer
  • Pipe diameter is indicated by inside diameter
  • Refer to the figure below for the installation
    • Only use the Twinning pipe by Mitsubishi (optional parts)
  • Indoor units are allowed to connect to 1 port of BC controller or 2 combined ports of BC controller using CMY-
    • Piping at the installation site

When the internal downstream capacity is above P80, the common kit CMY-R160-J1 is needed to combine 2 ports of the BC controller to expand the capacity, such as group 2 and 3 in Fig. When connecting indoor units with 1 BC controller port or 2 combined BC controller ports using CMY-R160-J1 or CMY-Y102SS-G2 are applicable, such as group 1 and 2 in Fig. The connection of the CMY-R160-J1 to the BC controller and the pipe leading to the indoor units can be referred to Fig.

The Joint kit include following items

Attention: Mixed mode of cooling and heating at the same time for indoor units connected to 1 port or 2 combined ports is not available. After the wiring and air tightness test, the joint and pipe insulation must be performed. The BC controller common kit "CMY-R160-J1" is used to combine 2 BC controller ports in a PURY/PQRY system to enable indoor performance down above P80 as shown in the picture.

9-4. FIN GUARD

For rear surface of XL module (a set of two pieces of the same type) PAC-FG03B-E.

10-1. General cautions

NOOK

10-2. Power supply for Outdoor unit

10-3. Power cable specifications

10-4. Power supply examples

3 The shield wire of the transmission cable must be connected to the ground terminal on the outdoor unit. The shield wire of the central control cable must be grounded on the outdoor unit whose CN41 is changed to CN40. 7 If you use 1 or 2 (main/sub) MA remote controllers to control more than 1 indoor unit, use the MA transfer cable to connect all the TB15 terminals of the indoor units.

11-1. Transmission cable length limitation

11-2. Transmission cable specifications

11-3. System configuration restrictions

Maximum 2 remote controllers for 1 group;

Maximum 3 System controllers are connectable when connecting to TB3 of the Outdoor/Heat source unit

A maximum of 6 system controller are connectable to TB3 and TB7 of Outdoor/Heat source unit

Also, count from TB7 on the TB7 side a total of the same number of system controller units, etc. Outdoor unit/heat source unit Transmission amplifier (No. 1) must be used when the total equivalent number of indoor units, OA process units and ME remote controllers reaches 40, or when the total equivalent transmission power consumption reaches 32. 1. Total equivalent number of units of indoor units, OA process units and ME remote controller must not exceed 40.

CAUTION

System controllers can be connected to TB3

  • Connecting to TB3 of the Outdoor/Heat source unit and receiving power from the Outdoor/Heat source unit
  • Connecting to TB7 of the Outdoor/Heat source unit and receiving power from the Outdoor/Heat source unit

If you connect only the LM-AP, the power supply unit PAC-SC51KUA is not required. The PAC-SC51KUA power supply unit is not needed if only the BM ADAPTER is connected. The PAC-SC51KUA power supply unit is not needed if you only connect the AE-200E/AE-50E/EW-50E.

BM ADAPTER

Outdoor units OC and OS in one refrigerant circuit system are automatically detected

No address setting is needed

Indoor units should be set with a branch number

Address setting is required if a sub BC controller is connected

NOTE

PURY

Factory setting

Setting at the site

  • Address should be set to Indoor units and centralized controller
  • Address should be set to Indoor units, Lossnay, and system controller
  • Assign an address to each of the sub BC controllers which equals the sum of the smallest address of the indoor units that are connected to each sub BC controller and 50
  • Address should be set to Indoor units and ME remote controllers
  • Address should be set to Indoor units, Lossnay, centralized controller, and ME remote controllers

1 For wireless remote controls and signal receivers (SRU), channels 1, 2 and 3 are selectable and must be set to the same channel. If the SC is connected to the TB7 side, change the jumper from CN41 to CN40 on the outdoor unit module to supply power to the SC. MA remote control, Multi-coolant system, System controller on TB7/TB3 side, Booster for long M-NET wiring.

ME R/C ME R/CIndoor unit

  • Indoor units should be set with a branch number
  • Assign an address to each of the sub BC controllers which equals the sum of the smallest address of the indoor units that are connected to each sub BC controller and 50
  • Group 2
  • Group 4

Assign an address to each BC sub-controller equal to the sum of the smallest address of the indoor units connected to each BC sub-controller and 50. When the address assigned to a BC sub-controller overlaps with the addresses of any other unit, including outdoor units (OC/OS ) or the master controller BC, the slave controller BC will have priority in obtaining the address. If applicable, set the BC auxiliary controllers in the PURY system in the following order:.

ME R/CME R/C

It is necessary to change the connector to CN40 on the outdoor unit control board (one outdoor unit only) when setting the group among other cooling systems. It is necessary to set the remote control manually when the group turns on another refrigerant system.

ME R/CBC controller

4 When a PAR-CT01MA or PAR-3X MA series (X indicates 1, 2...) is connected to a group, no other MA remote controllers can be connected to the same group. 2 When a PAR-CT01MA or PAR-3X MA series (X indicates 1, 2...) is connected to a group, no other MA remote controllers can be connected to the same group. 2 When a PAR-CT01MA or PAR-3X MA series (X indicates 1, 2...) is connected to a group, no other MA remote controllers can be connected to the same group.

EW-50EHUB

BACnet ® BM ADAPTER

12-1. R410A Piping material

Type-O: Soft copper pipe (annealed copper pipe), can be easily bent with human's hand

Type-1/2H pipe: Hard copper pipe (Straight pipe), being stronger than Type-O pipe of the same radical thickness

Procedures for installing the branched pipes

Horizontal installation Vertical installation (The branched pipes must face up.)

12-2. Piping Design

IF more than 16 ports are in use, or more than one BC controller is in use for one outdoor unit.

Bent equivalent length

P300YNW-A P350YNW-A

P450YNW-A P550YNW-A

Pipe length between main controller or sub BC and indoor unit (m) Pipe length between main controller BC, sub controller BC and indoor unit (m). 3, increase the size of high pressure pipe and liquid pipe between main BC and sub BC by one size. IF more than 16 ports are in use or if there is more than one BC controller in use for two outdoor units outdoor units.

P550YSNW-A 0.50 [1.64']

P600YSNW-A 0.50 [1.64']

P1050YSNW-A P1100YSNW-A

P650YSNW-A

P950YSNW-A P1000YSNW-A

P400YSNW-A 0.50 [1.64']

P450YSNW-A 0.50 [1.64']

P500YSNW-A 0.50 [1.64']

P800YSNW-A P850YSNW-A

P700YSNW-A P750YSNW-A

P1000YSNW-A P1050YSNW-A

P600YSNW-A P650YSNW-A

P450YSNW-A P500YSNW-A

PURY-P400, 450, 500, 550, 600YSNW-A]

PURY-P650YSNW-A]

12-3. Refrigerant charging calculation

Sample connection (with 5 BC controllers and 8 indoor units) (PURY-P700YSNW-A)

The result of the above calculation of the amount of refrigerant to be charged must be below the value in the table below. When the piping length from the outdoor unit to the furthest indoor unit is longer than 30.5 m (100 ft) Quantity e. Total capacity of outdoor units Quantity (To be added for G1/GA1/HA1 type BC controller).

13-1. Requirement on installation site

No direct thermal radiation to the unit

No possibility of annoying the neighbors by the sound of the unit

Valves and refrigerant flow on the outdoor unit may generate noise

Avoid the sites where strong winds blow

With strength to bear the weight of the unit

Drain flow from the unit is cared at heating mode

Enough space for installation and service as shown at 13-2

Avoid the sites where acidic solutions or chemical sprays (sulfuric compounds) are used frequently

The unit should be secure from combustible gas, oil, steam, chemical gas like acidic solution, sulfur gas and so on

13-2. Spacing

When installing multiple units, be sure to consider factors such as providing enough room for people to pass through, enough space between unit blocks, and enough room for air flow. When the wall is on the right or left side of the unit block. When two walls are L-shaped (2) Face-to-face installation. 3) Combination of side-by-side and side-by-side installation Unit height.

13-3. Piping direction

Exercise caution when transporting products

Install the unit in such a way that the corner of the angle bracket at the bottom of the unit shown in the figure is securely supported. When using a rubber pad, it must be installed so that the pad covers the entire width of the unit's legs. Install the unit in such a way that the corner of the angle bracket at the bottom of the unit shown in the figure below is securely supported.

WARNING

Install the unit on a durable base made of materials such as concrete or angle steel. When routing the pipes and/or cables at the bottom of the unit, make sure that the through hole at the base of the unit is not blocked with the installation base. To prevent small animals, water and snow from entering the unit and damaging its parts, close the.

To prevent small animals, water and snow from entering the unit and damage its parts, close the

Installation base parallel to the unit's front panel Installation base perpendicular to the unit's front panel. The pipe from several outdoor units must be installed so that under certain conditions oil does not accumulate in the pipe. In the figure on the right, because the pipe slopes upwards, the oil accumulates in the pipe when unit 1 is operating and unit 2 is stopped.

13-4. Countermeasure to wind

13-5. Precautions for installing a panel heater

  • Install the salt-resistant unit out of direct exposure to sea breeze, and minimize the exposure to salt water mist
  • Avoid installing a sun shade over the outdoor unit, so that rain will wash away salt deposits off the unit
  • Install the unit horizontally to ensure proper water drainage from the base of the unit. Accumulation of water in the base of the outdoor unit will significantly accelerate corrosion
  • Periodically wash salt deposits off the unit, especially when the unit is installed in a coastal area
  • Repair all noticeable scratches after installation and during maintenance
  • Periodically check the unit, and apply anti-rust agent and replace corroded parts as necessary

The AUTO mode of the local remote controller is available only when the fresh air intake type indoor unit is connected to the outdoor unit R2 or WR2 series. The unit is forced to run Thermo OFF (fan operation) when the outside air temperature is as follows. Depending on the load of the air conditioning system, the outside temperature and due to the activation of protection functions, the outlet temperature may fluctuate.

1-1. Refrigerant property

1-2. Confirm the Critical concentration and take countermeasure

Critical concentration

Let-out (making V bigger)

Fresh air in from the ceiling (Ventilation)

Referências

Documentos relacionados

Refer to the page on the troubleshooting of the high pressure sensor.page 229 2 Pressure sensor failure 3 Shorted-circuited pressure sensor cable due to torn outer rubber 4 A pin on